Technical data
13.1 Input
Gauge pressure measuring limits
● Measuring cell with inert oil
30 mbar a/3 kPa a/0.44 psi a
● Measuring cell with FDA-compliant oil
100 mbar a/10 kPa a/1.45 psi a
Upper measuring limit
100% of max. range (for oxygen measurement: max. 100 bar/10 MPa/
1450 psi and 60 °C ambient temperature/medium temperature)
Lower range value
Between the measuring limits (continuously adjustable)
1) For devices with functional safety, the minimum permissible measuring span is limited by the
spread. Therefore, ensure that the configured spread is no higher than 5:1.
2) For 250 mbar/25 kPa/3.6 psi measuring cells, the low measuring limit is 750 mbar a/75 kPa a/
10.8 psi a. The measuring cell is vacuum-tight down to 30 mbar a/3 kPa a/0.44 psi a.
13.1.2
Gauge pressure with front-flush diaphragm
Gauge pressure input with front-flush diaphragm
Measured variable
Gauge pressure
Measuring span (continuous-
Measuring span1)
Maximum permissible
Maximum test
ly adjustable) or measuring
operating pressure MAWP
pressure
range, max. operating pres-
(PS)
sure and max. test pressure
0.01 … 1 bar
Refer to the information on the nameplate of the pressure
transmitter and the data on the mounting flange2)
1 ... 100 kPa
0.15 … 14.5 psi
0.04 … 4 bar
4 ... 400 kPa
0.58 … 58 psi
0.16 … 16 bar
0.016 ... 1.6 MPa
2.3 … 232 psi
0.6 … 63 bar
0.063 ... 6.3 MPa
9.1 … 914 psi
1) For devices with functional safety, the minimum permissible measuring span is limited by the
spread. Therefore, ensure that the configured spread is no higher than 5:1.
2) The MAWP value of the pressure transmitter can be lower than the PN value of the mounting
flange and vice versa. To determine the maximum permissible operating pressure and the
maximum permissible test pressure, use the lowest value as reference.
Gauge pressure measuring limits with front-flush diaphragm
Lower measuring limit
● Measuring cell with silicone oil filling
100 mbar a/10 kPa a/1.45 psi a
● Measuring cell with inert oil
100 mbar a/10 kPa a/1.45 psi a
SITRANS P320/P420 with 4 to 20 mA/HART
200
Technical data
13.1 Input
Gauge pressure measuring limits with front-flush diaphragm
● Measuring cell with FDA-compliant oil
100 mbar a/10 kPa a/1.45 psi a
Upper measuring limit
100% of max. range
13.1.3
Gauge pressure from the differential pressure series
Gauge pressure input from the differential pressure series
Measured variable
Gauge pressure and differential pressure
Measuring span (continuous-
Measuring span1)
Maximum permissible
Max. permissible
ly adjustable) and maximum
operating pressure
test pressure
operating pressure (accord-
MAWP (PS)
ing to 2014/68/EU Pressure
1 ... 20 mbar
160 bar
240 bar
Equipment Directive)
0.1 ... 2 kPa
16 MPa
24 MPa
0.4015 … 8.031 inH2O
2320 psi
3480 psi
1 ... 60 mbar
160 bar
240 bar
0.1 ... 6 kPa
16 MPa
24 MPa
0.4015 … 24.09 inH2O
2320 psi
3480 psi
2.5 ... 250 mbar
160 bar
240 bar
0.2 ... 25 kPa
16 MPa
24 MPa
1.004 … 100.4 inH2O
2320 psi
3480 psi
6 ... 600 mbar
160 bar
240 bar
0.6 ... 60 kPa
16 MPa
24 MPa
2.409 … 240.9 inH2O
2320 psi
3480 psi
16 ... 1600 mbar
160 bar
240 bar
1.6 ... 160 kPa
16 MPa
24 MPa
6.424 … 642.4 inH2O
2320 psi
3480 psi
50 ... 5000 mbar
160 bar
240 bar
5 ... 500 kPa
16 MPa
24 MPa
20.08 … 2008 inH2O
2320 psi
3480 psi
0.3 … 30 bar
160 bar
240 bar
0.03 ... 3 MPa
16 MPa
24 MPa
4.35 … 435 psi
2320 psi
3480 psi
5 … 100 bar
160 bar
240 bar
0.5 ... 10 MPa
16 MPa
24 MPa
76.9 … 1450 psi
2320 psi
3480 psi
1) For devices with functional safety, the minimum permissible measuring span is limited by the
spread. Therefore, ensure that the configured spread is no higher than 5:1.
Gauge pressure measuring limits from differential pressure
series
Lower measuring limit
● Measuring cell with silicone oil filling
30 mbar a/3 kPa a/0.44 psi a
SITRANS P320/P420 with 4 to 20 mA/HART
201
Technical data
13.1 Input
Gauge pressure measuring limits from differential pressure
series
● Measuring cell with inert oil
30 mbar a/3 kPa a/0.44 psi a
● Measuring cell with FDA-compliant oil
100 mbar a/10 kPa a/1.45 psi a
Upper measuring limit
100% of max. range (for oxygen measurement: max. 100 bar/
10 MPa/1450 psi and 60 °C ambient temperature/medium
temperature)
Lower range value
Between the measuring limits (continuously adjustable)
13.1.4
Absolute pressure from the gauge pressure series
Absolute pressure input from the gauge pressure series
Measured variable
Absolute pressure
Measuring span (continuous-
Measuring span1)
Maximum permissible
Maximum test
ly adjustable) or measuring
operating pressure MAWP
pressure
range, max. operating pres-
(PS)
sure (in accordance with
8.3 … 250 mbar a
4 bar a
6 bar a
2014/68/EU Pressure Equip-
0.83 ... 25 kPa a
0.4 MPa a
0.6 MPa a
ment Directive) and max. test
pressure (in accordance with
3 … 100 inH2O a
58 psi a
87 psi a
DIN 16086)
43 … 1300 mbar a
6.6 bar a
10 bar a
4.3 ... 130 kPa a
0.66 MPa a
1 MPa a
17 … 525 inH2O a
95 psi a
145 psi a
166 … 5000 mbar a
20 bar a
30 bar a
16.6 ... 500 kPa a
2 MPa a
3 MPa a
2.41 … 72.5 psi a
290 psi a
435 psi a
1 … 30 bar a
65 bar a
100 bar a
0.1 ... 3 MPa a
6.5 MPa a
10 MPa a
14.5 … 435 psi a
942 psi a
1450 psi a
5.3 … 160 bar a
240 bar a
380 bar a
0.53 ... 16 MPa a
24 MPa a
38 MPa a
77 … 2321 psi a
3480 psi a
5511 psi a
13.3 … 400 bar a
400 bar a
600 bar a
1.3 ... 40 MPa a
40 MPa a
60 MPa a
192 ... 5801 psi a
5801 psi a
8702 psi a
23.3 … 700 bar a
800 bar a
800 bar a
2.3 ... 70 MPa a
80 MPa a
80 MPa a
337 ... 10152 psi a
11603 psi a
11603 psi a
SITRANS P320/P420 with 4 to 20 mA/HART
202
Technical data
13.1 Input
1)
For devices with functional safety, the minimum permissible measuring span is limited by the
spread. Therefore, ensure that the configured spread is no higher than 5:1.
Absolute pressure measuring limits from
gauge pressure series
Lower measuring limit
● Measuring cell with silicone oil filling
0 mbar a/kPa a/psi a
● Measuring cell with inert oil
For process temperature
30 mbar a/3 kPa a/0.44 psi a
-20 °C < ϑ ≤ 60 °C (-4 °F < ϑ
≤ +140 °F)
For process temperature
30 mbar a + 20 mbar a • (ϑ - 60 °C)/°C
60 °C < ϑ ≤ 100 °C (max.
3 kPa a + 2 kPa a • (ϑ - 60 °C)/°C
85 °C for measuring cell
0.44 psi a + 0.29 psi a • (ϑ - 140 °F)/°F
30 bar) (140 °F < ϑ ≤ 212 °F
(max. 185 °F for measuring
cell 435 psi))
Upper measuring limit
100% of max. range (for oxygen measurement: max. 100 bar/10 MPa/
1450 psi and 60 °C ambient temperature/medium temperature)
Lower range value
Between the measuring limits (continuously adjustable)
13.1.5
Absolute pressure with front-flush diaphragm
Absolute pressure with front-flush diaphragm
Measured variable
Absolute pressure
Measuring span (continuous-
Measuring span1)
Maximum permissible
Maximum test
ly adjustable) or measuring
operating pressure MAWP
pressure
range, max. operating pres-
(PS)
sure and max. test pressure
43 … 1300 mbar a
Refer to the information on the nameplate of the pressure
transmitter and the data on the mounting flange2)
4.3 ... 130 kPa a
17 … 525 inH2O a
166 … 5000 mbar a
16.6 ... 500 kPa a
2.41 … 72.5 psi a
1 … 30 bar a
0.1 ... 3 MPa a
14.5 … 435 psi a
Depending on the process connection, the measuring span may differ from these values
1) For devices with functional safety, the minimum permissible measuring span is limited by the
spread. Therefore, ensure that the configured spread is no higher than 5:1.
SITRANS P320/P420 with 4 to 20 mA/HART
203
Technical data
13.1 Input
2)
The MAWP value of the pressure transmitter can be lower than the PN value of the mounting
flange and vice versa. To determine the maximum permissible operating pressure and the
maximum permissible test pressure, use the lowest value as reference.
Absolute pressure measuring limits with front-flush diaphragm
Lower measuring limit
● Measuring cell with silicone oil filling
0 mbar a/kPa a/psi a
Upper measuring limit
100% of max. range
Lower range value
Between the measuring limits (continuously adjustable)
13.1.6
Absolute pressure from the differential pressure series
Absolute pressure input from the differential pressure series
Measured variable
Absolute pressure
Measuring span (continuous-
Measuring span1)
Maximum permissible
Max. permissible
ly adjustable) and maximum
operating pressure
test pressure
operating pressure (accord-
MAWP (PS)
ing to 2014/68/EU Pressure
8.3 … 250 mbar a
160 bar a
240 bar a
Equipment Directive)
0.83 ... 25 kPa a
16 MPa a
24 MPa a
3 … 100 inH2O a
2320 psi a
3480 psi a
43 … 1300 mbar a
160 bar a
240 bar a
4.3 ... 130 kPa a
16 MPa a
24 MPa a
17 … 525 inH2O a
2320 psi a
3480 psi a
166 … 5000 mbar a
160 bar a
240 bar a
16.6 ... 500 kPa a
16 MPa a
24 MPa a
2.41 … 72.5 psi a
2320 psi a
3480 psi a
1 … 30 bar a
160 bar a
240 bar a
0.1 ... 3 MPa a
16 MPa a
24 MPa a
14.5 … 435 psi a
2320 psi a
3480 psi a
5 … 100 bar a
160 bar a
240 bar a
0.5 ... 10 MPa a
16 MPa a
24 MPa a
76.9 … 1450 psi a
2320 psi a
3480 psi a
1) For devices with functional safety, the minimum permissible measuring span is limited by the
spread. Therefore, ensure that the configured spread is no higher than 5:1.
Absolute pressure measuring limits from dif-
ferential pressure series
Lower measuring limit
● Measuring cell with silicone oil filling
0 mbar a/kPa a/psi a
● Measuring cell with inert liquid
For process temperature -20 °C <
30 mbar a/3 kPa a/0.44 psi a
ϑ ≤ 60 °C (-4 °F < ϑ ≤ +140 °F)
SITRANS P320/P420 with 4 to 20 mA/HART
204
Technical data
13.1 Input
Absolute pressure measuring limits from dif-
ferential pressure series
For process temperature 60 °C < ϑ
30 mbar a + 20 mbar a • (ϑ - 60 °C)/°C
≤ 100 °C (max. 85 °C for measur-
3 kPa a + 2 kPa a • (ϑ - 60 °C)/°C
ing cell 30 bar) (140 °F < ϑ ≤ 212 °F
0.44 psi a + 0.29 psi a • (ϑ - 140 °F)/°F
(max. 185 °F for measuring cell
435 psi))
Upper measuring limit
100% of max. range (for oxygen measurement: max. 100 bar/10 MPa/
1450 psi and 60 °C ambient temperature/medium temperature)
Lower range value
Between the measuring limits (continuously adjustable)
SITRANS P320/P420 with 4 to 20 mA/HART
205
Technical data
13.1 Input
13.1.7
Differential pressure and flow
Differential pressure input and flow
Measured variable
Differential pressure and flow
Measuring span (continuous-
Measuring span1)
Maximum permissible
Max. permissible
ly adjustable) and maximum
operating pressure
test pressure
operating pressure (accord-
MAWP (PS)
ing to 2014/68/EU Pressure
1 ... 20 mbar
160 bar
240 bar
Equipment Directive)
0.1 ... 2 kPa
16 MPa
24 MPa
0.4015 … 8.031 inH2O
2320 psi
3480 psi
1 ... 60 mbar
160 bar
240 bar
0.1 ... 6 kPa
16 MPa
24 MPa
0.4015 … 24.09 inH2O
2320 psi
3480 psi
2.5 ... 250 mbar
160 bar
240 bar
0.2 ... 25 kPa
16 MPa
24 MPa
1.004 … 100.4 inH2O
2320 psi
3480 psi
6 ... 600 mbar
160 bar
240 bar
0.6 ... 60 kPa
16 MPa
24 MPa
2.409 … 240.9 inH2O
2320 psi
3480 psi
16 ... 1600 mbar
160 bar
240 bar
1.6 ... 160 kPa
16 MPa
24 MPa
6.424 … 642.4 inH2O
2320 psi
3480 psi
50 ... 5000 mbar
160 bar
240 bar
5 ... 500 kPa
16 MPa
24 MPa
20.08 … 2008 inH2O
2320 psi
3480 psi
0.3 … 30 bar
160 bar
240 bar
0.03 ... 3 MPa
16 MPa
24 MPa
4.35 … 435 psi
2320 psi
3480 psi
2.5 ... 250 mbar
420 bar
630 bar
0.25 ... 25 kPa
42 MPa
63 MPa
1.004 … 100.4 inH2O
6091 psi
9137 psi
6 ... 600 mbar
420 bar
630 bar
0.6 ... 60 kPa
42 MPa
63 MPa
2.409 … 240.9 inH2O
6091 psi
9137 psi
16 ... 1600 mbar
420 bar
630 bar
1.6 ... 160 kPa
42 MPa
63 MPa
6.424 … 642.4 inH2O
6091 psi
9137 psi
50 ... 5000 mbar
420 bar
630 bar
5 ... 500 kPa
42 MPa
63 MPa
20.08 … 2008 inH2O
6091 psi
9137 psi
0.3 … 30 bar
420 bar
630 bar
0.03 ... 3 MPa
42 MPa
63 MPa
4.35 … 435 psi
6091 psi
9137 psi
SITRANS P320/P420 with 4 to 20 mA/HART
206
Technical data
13.1 Input
1)
For devices with functional safety, the minimum permissible measuring span is limited by the
spread. Therefore, ensure that the configured spread is no higher than 5:1.
Differential pressure and flow measuring limits
Lower measuring limit
● Measuring cell
-100% of maximum measuring range or 30 mbar a /3 kPa a /0.44 psi a
with silicone oil
filling
● Measuring cell with inert oil
For process temperature -20 °C
-100% of maximum measuring range or 30 mbar a /3 kPa a /0.44 psi a
< ϑ ≤ 60 °C (-4 °F < ϑ ≤ +140 °F)
For process temperature 60 °C
-100% of maximum measuring range or 30 mbar a /3 kPa a /0.44 psi a
< ϑ ≤ 100 °C (max. 85 °C for
30 mbar a + 20 mbar a • (ϑ - 60 °C)/°C
measuring cell 30 bar with
3 kPa a + 2 kPa a • (ϑ - 60 °C)/°C
PN 420) (140 °F < ϑ ≤ 212 °F
(max. 185 °F for measuring cell
0.44 psi a + 0.29 psi a • (ϑ - 140 °F)/°F
435 psi))
● Measuring cell
For process temperature -10 °C
-100% of maximum measuring range or 100 mbar a /10 kPa a /
with FDA-
< ϑ ≤ 100 °C (-14 °F < ϑ
14.5 psi a.
compliant oil
≤ +212 °F)
Upper measuring
100% of max. range (for oxygen measurement: max. 100 bar/10 MPa/1450 psi and 60 °C ambient
limit
temperature/medium temperature)
Lower range value Between the measuring limits (continuously adjustable)
13.1.8
Level
Level input
Measured variable
Level
Measuring span (continuous-
Measuring span1)
Maximum permissible
Max. permissible
ly adjustable) and maximum
operating pressure
test pressure
operating pressure (accord-
MAWP (PS)
ing to 2014/68/EU Pressure
25 ... 250 mbar
See mounting flange
Equipment Directive)
2.5 ... 25 kPa
10 … 100 inH2O
25 ... 600 mbar
2.5 ... 60 kPa
10 … 240 inH2O
53 … 1600 mbar
5.3 ... 160 kPa
21 … 640 inH2O
166 … 5000 mbar
16.6 ... 500 kPa
2.41 … 72.5 psi
SITRANS P320/P420 with 4 to 20 mA/HART
207
Technical data
13.2 Measuring accuracy of SITRANS P320
1)
For devices with functional safety, the minimum permissible measuring span is limited by the
spread. Therefore, ensure that the configured spread is no higher than 5:1.
Level measuring limits
Lower measuring limit
Measuring cell with silicone oil
-100% of max. measuring range or 30 mbar a/3 kPa a/0.44 psi a depending
filling
on the mounting flange
Measuring cell with inert oil
-100% of max. measuring range or 30 mbar a/3 kPa a/0.44 psi a depending
on the mounting flange
Measuring cell with FDA-com-
-100% of maximum measuring range or 100 mbar a /10 kPa a /1.45 psi a
pliant oil
Upper measuring limit
100% of max. range
Lower range value
Between the measuring limits (continuously adjustable)
13.2
Measuring accuracy of SITRANS P320
13.2.1
Reference conditions
● According to EN 60770-1/IEC 61298-1
● Rising characteristic curve
● Lower range value 0 bar/kPa/psi
● Seal diaphragm stainless steel
● Measuring cell with silicone oil filling
● Room temperature 25 °C (77 °F)
13.2.2
Effect of auxiliary power supply
0.005% per 1 V (in percent per change in voltage)
13.2.3
Gauge pressure
Conformity error at limit point setting, including hysteresis and repeatability - gauge pressure
Measuring span ratio r (spread, Turn-Down)
r = max. measuring span/set measuring span and nominal
measuring range
● Linear characteristic curve
r ≤ 1.25
1.25 < r ≤ 30
250 mbar/25 kPa/3.6 psi
≤ 0.075%
≤ (0.008 • r + 0.055)%
● Linear characteristic curve
r ≤ 5
5 < r ≤ 100
SITRANS P320/P420 with 4 to 20 mA/HART
208
Technical data
13.2 Measuring accuracy of SITRANS P320
Conformity error at limit point setting, including hysteresis and repeatability - gauge pressure
1 bar/100 kPa/14.5 psi
≤ 0.065%
≤ (0.004 • r + 0.045)%
4 bar/400 kPa/58 psi
16 bar/1.6 MPa/232 psi
63 bar/6.3 MPa/914 psi
160 bar/16 MPa/2321 psi
● Linear characteristic
r ≤ 3
3 < r ≤ 100
curve
400 bar/40 MPa/5802 psi
≤ 0.075%
0.005 • r + 0.05
700 bar/70 MPa/10152 psi
Effect of ambient temperature - gauge pressure
In percent per 28 °C (50 °F)
250 mbar/25 kPa/3.6 psi
≤ (0.16 • r + 0.1)%
1 bar/100 kPa/14.5 psi
≤ (0.05 • r + 0.1)%
4 bar/400 kPa/58 psi
≤ (0.025 • r + 0.125)%
16 bar/1.6 MPa/232 psi
63 bar/6.3 MPa/914 psi
160 bar/16 MPa/2321 psi
400 bar/40 MPa/5802 psi
700 bar/70 MPa/10152 psi
≤ (0.08 • r + 0.16)%
Long-term stability at ±30 °C (±54 °F) - gauge pressure
250 mbar/25 kPa/3.6 psi
Per year ≤ (0.25 • r)%
1 bar/100 kPa/14.5 psi
In 5 years ≤ (0.25 • r)%
In 10 years ≤ (0.35 • r)%
4 bar/400 kPa/58 psi
In 5 years ≤ (0.125 • r)%
16 bar/1.6 MPa/232 psi
In 10 years ≤ (0.15 • r)%
63 bar/6.3 MPa/914 psi
160 bar/16 MPa/2321 psi
400 bar/40 MPa/5802 psi
700 bar/70 MPa/10152 psi
In 5 years ≤ (0.25 • r)%
In 10 years ≤ (0.35 • r)%
Step response time T63 (without electrical damping) - gauge pressure
Approx. 0.105 s
Effect of mounting position - gauge pressure
≤ 0.05 mbar/0.005 kPa/0.000725 psi per 10° incline
(correct the zero point with position error compensation)
SITRANS P320/P420 with 4 to 20 mA/HART
209
Technical data
13.2 Measuring accuracy of SITRANS P320
13.2.4
Gauge pressure from the differential pressure series
Conformity error at limit point setting, including hysteresis and repeatability - gauge pressure from the differential pressure
series
Measuring span ratio r (spread, Turn-Down)
r = max. measuring span/set measuring span and
nominal measuring range
● Linear characteristic curve
r ≤ 5
5 < r ≤ 20
20 mbar/2 kPa/8.031 inH2O
≤ 0.075%
≤ (0.005 • r + 0.05)%
● Linear characteristic curve
r ≤ 5
5 < r ≤ 60
60 mbar/6 kPa/24.09 inH2O
≤ 0.075%
≤ (0.005 • r + 0.05)%
● Linear characteristic curve
r ≤ 5
5 < r ≤ 100
250 mbar/25 kPa/3.6 psi
≤ 0.065%
≤ (0.004 • r + 0.045)%
600 mbar/60 kPa/240.9 inH2O
1600 mbar/160 kPa/642.4 inH2O
5000 mbar/500 kPa/2008 inH2O
30 bar/3 MPa/435 psi
● Linear characteristic curve
100 bar/10 MPa/1450.3 psi
r ≤ 10
10 < r ≤ 30
≤ 0.1%
≤ 0.2%
Effect of ambient temperature - gauge pressure from differential pressure series
In percent per 28 °C (50 °F)
20 mbar/2 kPa/8.031 inH2O
≤ (0.15 • r + 0.1)%
60 mbar/6 kPa/24.09 inH2O
≤ (0.075 • r + 0.1)%
250 mbar/25 kPa/3.6 psi
≤ (0.025 • r + 0.125)%
600 mbar/60 kPa/240.9 inH2O
1600 mbar/160 kPa/642.4 inH2O
5000 mbar/500 kPa/2008 inH2O
30 bar/3 MPa/435 psi
100 bar/10 MPa/1450.3 psi
≤ (0.08 • r + 0.16)
Long-term stability at ±30 °C (±54 °F) - gauge pressure from differential pressure series
20 mbar/2 kPa/8.031 inH2O
Per year ≤ (0.2 • r)%
60 mbar/6 kPa/24.09 inH2O
In 5 years ≤ (0.25 • r)%
250 mbar/25 kPa/3.6 psi
In 5 years ≤ (0.125 • r)%
600 mbar/60 kPa/240.9 inH2O
In 10 years ≤ (0.15 • r)%
1600 mbar/160 kPa/642.4 inH2O
5000 mbar/500 kPa/2008 inH2O
30 bar/3 MPa/435 psi
In 5 years ≤ (0.25 • r)%
In 10 years ≤ (0.35 • r)%
100 bar/10 MPa/1450.3 psi
In 5 years ≤ (0.25 • r)%
SITRANS P320/P420 with 4 to 20 mA/HART
210
Technical data
13.2 Measuring accuracy of SITRANS P320
Step response time T63 (without electrical damping) - gauge pressure from differential pressure series
20 mbar/2 kPa/8.031 inH2O
Approx. 0.160 s
60 mbar/6 kPa/24.09 inH2O
Approx. 0.150 s
250 mbar/25 kPa/3.6 psi
Approx. 0.135 s
600 mbar/60 kPa/240.9 inH2O
1600 mbar/160 kPa/642.4 inH2O
5000 mbar/500 kPa/2008 inH2O
30 bar/3 MPa/435 psi
100 bar/10 MPa/1450.3 psi
Approx. 0.145 s
Effect of mounting position - gauge pressure from differential pressure series
≤ 0.7 mbar/0.07 kPa/0.01015266 psi per 10° incline
(correct the zero point with position error compensation)
13.2.5
Absolute pressure from gauge and differential pressure series
Conformity error at limit point setting, including hysteresis and repeatability - absolute pressure from gauge and differential
pressure series
Measuring span ratio r (spread, Turn-Down)
r = max. measuring span/set measuring span and nominal
measuring range
● Linear characteristic curve
r ≤ 10
10 < r ≤ 30
All measuring cells
≤ 0.1%
≤ 0.2%
Effect of ambient temperature - absolute pressure from gauge and differential pressure series
In percent per 28 °C (50 °F)
250 mbar a/25 kPa a/3.6 psi a
≤ (0.15 • r + 0.1)
1300 mbar a/130 kPa a/18.8 psi a
≤ (0.08 • r + 0.16)
5 bar a/500 kPa a/72.5 psi a
30 bar a/3000 kPa a/435 psi a
100 bar a/10 MPa a/1450.3 psi a
160 bar a/16 MPa a/2321 psi a
400 bar a/40 MPa a/5802 psi a
700 bar a/70 MPa a/10152.6 psi a
Long-term stability at ±30 °C (±54 °F) - absolute pressure from gauge and differential pressure series
In 5 years ≤ (0.25 • r)%
SITRANS P320/P420 with 4 to 20 mA/HART
211
Technical data
13.2 Measuring accuracy of SITRANS P320
Step response time T63 (without electrical damping) - absolute pressure from gauge and differential pressure series
Gauge pressure series
All measuring cells
Approx. 0.105 s
Differential pressure series
250 mbar/25 kPa/3.6 psi
Approx. 0.195 s
1300 mbar a/130 kPa a/18.8 psi a
Approx. 0.145 s
5 bar a/500 kPa a/72.5 psi a
30 bar a/3000 kPa a/435 psi a
100 bar a/10 MPa a/1450.3 psi a
Effect of mounting position - absolute pressure from gauge and differential pressure series
In pressure per change of angle
● For absolute pressure (from the gauge pressure series): ≤ 0.05 mbar/0.005 kPa/
0.000725 psi per 10° incline
● For absolute pressure (from the differential pressure series): 0.7 mbar/0.07 kPa/
0.001015 psi per 10° incline
(zero-point correction is possible using the zero point adjustment)
13.2.6
Absolute pressure with front-flush diaphragm
Conformity error at limit point setting, including hysteresis and repeatability
Measuring span ratio r (spread, Turn-Down)
r = max. measuring span/set measuring span and nominal
measuring range
Linear characteristic curve
r ≤ 10
10 < r ≤ 30
All measuring cells
≤ 0.2%
≤ 0.4%
Effect of ambient temperature
In percent per 28 °C (50 °F)
All measuring cells
≤ (0.16 • r + 0.24)
Long-term stability at ±30 °C (±54 °F)
All measuring cells
In 5 years ≤ (0.25 • r)%
Step response time T63 (without electrical damping)
Approx. 0.105 s
SITRANS P320/P420 with 4 to 20 mA/HART
212
Technical data
13.2 Measuring accuracy of SITRANS P320
Effect of mounting position
In pressure per change of angle
0.04 kPa/0.4 mbar/0.006 psi per 10° incline
(zero-point correction is possible with position error compen-
sation)
13.2.7
Gauge pressure with front-flush diaphragm
Conformity error at limit point setting, including hysteresis and repeatability - gauge pressure with front-flush diaphragm
Measuring span ratio r (spread, Turn-Down)
r = max. measuring span/set measuring span and nominal
measuring range
● Linear characteristic curve
r ≤ 5
5 < r ≤ 100
1 bar/100 kPa/14.5 psi
≤ 0.075%
≤ (0.005 • r + 0.05)%
4 bar/400 kPa/58 psi
16 bar/1.6 MPa/232 psi
63 bar/6.3 MPa/914 psi
Effect of ambient temperature - gauge pressure with front-flush diaphragm
In percent per 28 °C (50 °F)
1 bar/100 kPa/14.5 psi
≤ (0.08 • r + 0.16)%
4 bar/400 kPa/58 psi
16 bar/1.6 MPa/232 psi
63 bar/6.3 MPa/914 psi
Long-term stability at ±30 °C (±54 °F) - gauge pressure with front-flush diaphragm
1 bar/100 kPa/14.5 psi
In 5 years ≤ (0.25 • r)%
4 bar/400 kPa/58 psi
16 bar/1.6 MPa/232 psi
In 5 years ≤ (0.125 • r)%
63 bar/6.3 MPa/914 psi
Step response time T63 (without electrical damping) - gauge pressure with front-flush diaphragm
Approx. 0.105 s
Effect of mounting position - gauge pressure with front-flush diaphragm
≤ 0.4 mbar/0.04 kPa/0.006 psi per 10° incline
(zero-point correction is possible with position error compen-
sation)
SITRANS P320/P420 with 4 to 20 mA/HART
213
Technical data
13.2 Measuring accuracy of SITRANS P320
13.2.8
Differential pressure and flow
Conformity error at limit point setting, including hysteresis and repeatability - differential pressure and flow
Measuring span ratio r (spread, Turn-Down)
r = max. measuring span/set measuring span and nomi-
nal measuring range
Linear characteristic curve
r ≤ 5
5 < r ≤ 20
20 mbar/2 kPa/0.29 psi
≤ 0.075%
≤ (0.005 • r + 0.05)%
Linear characteristic curve
r ≤ 5
5 < r ≤ 60
60 mbar/6 kPa/0.87 psi
≤ 0.075%
≤ (0.005 • r + 0.05)%
Linear characteristic curve
r ≤ 5
5 < r ≤ 100
250 mbar/25 kPa/3.63 psi
≤ 0.065%
≤ (0.004 • r + 0.045)%
600 mbar/60 kPa/8.70 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
30 bar/3 MPa/435.11 psi
Root extraction characteris-
r ≤ 5
5 < r ≤ 20
tic
Flow > 50%
20 mbar/2 kPa/0.29 psi
≤ 0.075%
≤ (0.005 • r + 0.05)%
Root extraction characteris-
r ≤ 5
5 < r ≤ 60
tic
Flow > 50%
60 mbar/6 kPa/0.87 psi
≤ 0.075%
≤ (0.005 • r + 0.05)%
Root extraction characteris-
r ≤ 5
5 < r ≤ 100
tic
Flow > 50%
250 mbar/25 kPa/3.63 psi
≤ 0.065%
≤ (0.004 • r + 0.045)%
600 mbar/60 kPa/8.70 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
30 bar/3 MPa/435.11 psi
Root extraction characteris-
r ≤ 5
5 < r ≤ 20
tic
Flow 25 ... 50%
20 mbar/2 kPa/0.29 psi
≤ 0.15%
≤ (0.01 • r + 0.1)%
Root extraction characteris-
r ≤ 5
5 < r ≤ 60
tic
Flow 25 ... 50%
60 mbar/6 kPa/0.87 psi
≤ 0.15%
≤ (0.01 • r + 0.1)%
Root extraction characteris-
r ≤ 5
5 < r ≤ 100
tic
SITRANS P320/P420 with 4 to 20 mA/HART
214
Technical data
13.2 Measuring accuracy of SITRANS P320
Conformity error at limit point setting, including hysteresis and repeatability - differential pressure and flow
Flow 25 ... 50%
250 mbar/25 kPa/3.63 psi
≤ 0.13%
≤ (0.008 • r + 0.09)%
600 mbar/60 kPa/8.70 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
30 bar/3 MPa/435.11 psi
Effect of ambient temperature - differential pressure and flow
In percent per 28 °C (50 °F)
20 mbar/2 kPa/0.29 psi
≤ (0.15 • r + 0.1)%
60 mbar/6 kPa/0.87 psi
≤ (0.075 • r + 0.1)%
250 mbar/25 kPa/3.63 psi
≤ (0.025 • r + 0.125)%
600 mbar/60 kPa/8.70 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
30 bar/3 MPa/435.11 psi
Effect of static pressure - differential pressure and flow
● On the lower range value
20 mbar/2 kPa/0.29 psi
≤ (0.3 • r) % per 70 bar (zero-point correction is
possible with position error compensation)
60 mbar/6 kPa/0.87 psi
≤ (0.1 • r)% per 70 bar (zero-point correction is
250 mbar/25 kPa/3.63 psi
possible with position error compensation)
600 mbar/60 kPa/8.70 psi
1600 mbar/160 kPa/23.21 psi
30 bar/3 MPa/435.11 psi
5 bar/500 kPa/72.52 psi
≤ (0.15 • r)% per 70 bar (zero-point correction is
possible with position error compensation)
● On the measuring span
20 mbar/2 kPa/0.29 psi
≤ 0.2% per 70 bar
60 mbar/6 kPa/0.87 psi
≤ 0.1% per 70 bar
250 mbar/25 kPa/3.63 psi
600 mbar/60 kPa/8.70 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
30 bar/3 MPa/435.11 psi
Long-term stability at ±30 °C (±54 °F) - differential pressure and flow
Static pressure max. 70 bar/7 MPa/1015 psi
20 mbar/2 kPa/0.29 psi
Per year ≤ (0.2 • r)%
60 mbar/6 kPa/0.87 psi
In 5 years ≤ (0.25 • r)%
SITRANS P320/P420 with 4 to 20 mA/HART
215
Technical data
13.2 Measuring accuracy of SITRANS P320
Long-term stability at ±30 °C (±54 °F) - differential pressure and flow
250 mbar/25 kPa/3.63 psi
In 5 years ≤ (0.125 • r)%
600 mbar/60 kPa/8.70 psi
In 10 years ≤ (0.15 • r)%
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
30 bar/3 MPa/435.11 psi
In 5 years ≤ (0.25 • r)%
In 10 years ≤ (0.35 • r)%
Step response time T63 (without electrical damping) - differential pressure and flow (PN 160)
20 mbar/2 kPa/0.29 psi
Approx. 0.160 s
60 mbar/6 kPa/0.87 psi
Approx. 0.150 s
250 mbar/25 kPa/3.63 ps
Approx. 0.135 s
600 mbar/60 kPa/8.70 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
30 bar/3 MPa/435.11 psi
Step response time T63 (without electrical damping) - differential pressure and flow (PN 420)
250 mbar/25 kPa/3.63 psi
Approx. 0.25 s
600 mbar/60 kPa/8.70 psi
Approx. 0.2 s
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
30 bar/3 MPa/435.11 psi
Effect of mounting position - differential pressure and flow
Effect of mounting position
In pressure per change of angle
≤ 0.7 mbar/0.07 kPa/0.028
inH2O per 10° incline
(zero-point correction is possible
with position error compensation)
SITRANS P320/P420 with 4 to 20 mA/HART
216
Technical data
13.2 Measuring accuracy of SITRANS P320
13.2.9
Level
Conformity error at limit point setting, including hysteresis and repeatability - level
Measuring span ratio r (spread,
r = max. measuring span/set measuring span and nominal measuring range
Turn-Down)
● Linear characteristic curve
r ≤ 5
5 < r ≤ 10
250 mbar/25 kPa/3.63 psi
≤ 0.125%
≤ (0.007 • r + 0.09) %
600 mbar/60 kPa/8.70 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
Effect of ambient temperature1) - level
In percent per 28 °C (50 °F)
250 mbar/25 kPa/3.63 psi
≤ (0.025 • r + 0.125)%
600 mbar/60 kPa/8.70 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
1) Data only applies to the basic unit. The error of the remote seal must be considered additively.
Effect of static pressure - level
● On the lower range value
250 mbar/25 kPa/3.63 psi
≤ (0.1 • r)% per 70 bar (zero-point correction is possible with position error
compensation)
600 mbar/60 kPa/8.70 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
≤ (0.15 • r)% per 70 bar (zero-point correction is possible with position error
compensation)
● On the measuring span
≤ (0.1 • r)% per 70 bar
Long-term stability at ±30 °C (±54 °F) - level
All measuring cells
In 5 years ≤ (0.25 • r)% static pressure max. 70 bar/7 MPa/
1015 psi
Effect of mounting position - level
Depends on the fill fluid in the
mounting flange
SITRANS P320/P420 with 4 to 20 mA/HART
217
Technical data
13.3 Measuring accuracy of SITRANS P420
13.3
Measuring accuracy of SITRANS P420
13.3.1
Reference conditions
● According to EN 60770-1/IEC 61298-1
● Rising characteristic curve
● Lower range value 0 bar/kPa/psi
● Seal diaphragm stainless steel
● Measuring cell with silicone oil filling
● Room temperature 25 °C (77 °F)
13.3.2
Effect of auxiliary power supply
0.005% per 1 V (in percent per change in voltage)
13.3.3
Gauge pressure
Conformity error at limit point setting, including hysteresis and repeatability - gauge pressure
Measuring span ratio r (spread, Turn-Down)
r = max. measuring span/set measuring span and nominal
measuring range
● Linear characteristic curve
r ≤ 1.25
1.25 < r ≤ 30
250 mbar/25 kPa/3.6 psi
≤ 0.065%
≤ (0.008 • r + 0.055)%
● Linear characteristic curve
r ≤ 5
5 < r ≤ 100
1 bar/100 kPa/14.5 psi
≤ 0.04%
≤ (0.004 • r + 0.045)%
4 bar/400 kPa/58 psi
16 bar/1.6 MPa/232 psi
63 bar/6.3 MPa/914 psi
160 bar/16 MPa/2321 psi
● Linear characteristic curve
r ≤ 5
5 < r ≤ 100
400 bar/40 MPa/5802 psi
≤ 0.075%
≤ (0.005 • r + 0.05)%
700 bar/70 MPa/10152 psi
Effect of ambient temperature - gauge pressure
In percent per 28 °C (50 °F)
250 mbar/25 kPa/3.6 psi
≤ (0.16 • r + 0.1)%
1 bar/100 kPa/14.5 psi
≤ (0.05 • r + 0.1)%
SITRANS P320/P420 with 4 to 20 mA/HART
218
Technical data
13.3 Measuring accuracy of SITRANS P420
Effect of ambient temperature - gauge pressure
4 bar/400 kPa/58 psi
≤ (0.025 • r + 0.125)%
16 bar/1.6 MPa/232 psi
63 bar/6.3 MPa/914 psi
160 bar/16 MPa/2321 psi
400 bar/40 MPa/5802 psi
700 bar/70 MPa/10152 psi
≤ (0.08 • r + 0.16)%
Long-term stability at ±30 °C (±54 °F) - gauge pressure
250 mbar/25 kPa/3.6 psi
Per year ≤ (0.25 • r)%
1 bar/100 kPa/14.5 psi
In 5 years ≤ (0.25 • r)%
In 10 years ≤ (0.35 • r)%
4 bar/400 kPa/58 psi
In 5 years ≤ (0.125 • r)%
16 bar/1.6 MPa/232 psi
In 10 years ≤ (0.15 • r)%
63 bar/6.3 MPa/914 psi
160 bar/16 MPa/2321 psi
400 bar/40 MPa/5802 psi
700 bar/70 MPa/10152 psi
In 5 years ≤ (0.25 • r)%
In 10 years ≤ (0.35 • r)%
Step response time T63 (without electrical damping) - gauge pressure
Approx. 0.105 s
Effect of mounting position - gauge pressure
≤ 0.05 mbar/0.005 kPa/0.000725 psi per 10° incline
(zero-point correction is possible with position error compen-
sation)
13.3.4
Gauge pressure from the differential pressure series
Conformity error at limit point setting, including hysteresis and repeatability - gauge pressure from differential pressure series
Measuring span ratio r (spread, Turn-Down)
r = max. measuring span/set measuring span and nomi-
nal measuring range
● Linear characteristic curve
r ≤ 5
5 < r ≤ 20
20 mbar/2 kPa/8.031 inH2O
≤ 0.075%
≤ (0.005 • r + 0.05)%
● Linear characteristic curve
r ≤ 5
5 < r ≤ 60
60 mbar/6 kPa/24.09 inH2O
≤ 0.075%
≤ (0.005 • r + 0.05)%
● Linear characteristic curve
r ≤ 5
5 < r ≤ 100
SITRANS P320/P420 with 4 to 20 mA/HART
219
Technical data
13.3 Measuring accuracy of SITRANS P420
Conformity error at limit point setting, including hysteresis and repeatability - gauge pressure from differential pressure series
250 mbar/25 kPa/3.6 psi
≤ 0.04%
≤ (0.004 • r + 0.045)%
600 mbar/60 kPa/240.9 inH2O
1600 mbar/160 kPa/642.4 inH2O
5000 mbar/500 kPa/2008 inH2O
30 bar/3 MPa/435 psi
● Linear characteristic
100 bar/10 MPa/1450.3 psi
r ≤ 10
10 < r ≤ 30
curve
≤ 0.1%
≤ 0.2%
Effect of ambient temperature - gauge pressure from differential pressure series
In percent per 28 °C (50 °F)
20 mbar/2 kPa/8.031 inH2O
≤ (0.15 • r + 0.1)%
60 mbar/6 kPa/24.09 inH2O
≤ (0.075 • r + 0.1)%
250 mbar/25 kPa/3.6 psi
≤ (0.025 • r + 0.0625)%
5000 mbar/500 kPa/2008 inH2O
600 mbar/60 kPa/240.9 inH2O
≤ (0.0125 • r + 0.0625)%
1600 mbar/160 kPa/642.4 inH2O
30 bar/3 MPa/435 psi
100 bar/10 MPa/1450.3 psi
≤ (0.08 • r + 0.16)%
Long-term stability at ±30 °C (±54 °F) - gauge pressure from differential pressure series
20 mbar/2 kPa/8.031 inH2O
Per year ≤ (0.2 • r)%
60 mbar/6 kPa/24.09 inH2O
In 5 years ≤ (0.25 • r)%
250 mbar/25 kPa/3.6 psi
In 5 years ≤ (0.125 • r)%
600 mbar/60 kPa/240.9 inH2O
In 10 years ≤ (0.15 • r)%
1600 mbar/160 kPa/642.4 inH2O
5000 mbar/500 kPa/2008 inH2O
30 bar/3 MPa/435 psi
In 5 years ≤ (0.25 • r)%
In 10 years ≤ (0.35 • r)%
100 bar/10 MPa/1450.3 psi
In 5 years ≤ (0.25 • r)%
Step response time T63 (without electrical damping) - gauge pressure from differential pressure series
20 mbar/2 kPa/8.031 inH2O
Approx. 0.160 s
60 mbar/6 kPa/24.09 inH2O
Approx. 0.150 s
250 mbar/25 kPa/3.6 psi
Approx. 0.135 s
600 mbar/60 kPa/240.9 inH2O
1600 mbar/160 kPa/642.4 inH2O
5000 mbar/500 kPa/2008 inH2O
30 bar/3 MPa/435 psi
100 bar/10 MPa/1450.3 psi
Approx. 0.145 s
SITRANS P320/P420 with 4 to 20 mA/HART
220
Technical data
13.3 Measuring accuracy of SITRANS P420
Effect of mounting position
≤ 0.7 mbar/0.07 kPa/0.01015266 psi per 10° incline
(zero-point correction is possible with position error compen-
sation)
13.3.5
Absolute pressure from gauge and differential pressure series
Conformity error at limit point setting, including hysteresis and repeatability - absolute pressure from gauge and differential
pressure series
Measuring span ratio r (spread, Turn-Down)
r = max. measuring span/set measuring span and nominal
measuring range
● Linear characteristic curve
r ≤ 10
10 < r ≤ 30
All measuring cells
≤ 0.1%
≤ 0.2%
Effect of ambient temperature - absolute pressure from gauge and differential pressure series
In percent per 28 °C (50 °F)
250 mbar a/25 kPa a/3.6 psi a
≤ (0.15 • r + 0.1)
1300 mbar a/130 kPa a/18.8 psi a
≤ (0.08 • r + 0.16)
5 bar a/500 kPa a/72.5 psi a
30 bar a/3000 kPa a/435 psi a
100 bar a/10 MPa a/1450.3 psi a
160 bar a/16 MPa a/2321 psi a
400 bar a/40 MPa a/5802 psi a
700 bar a/70 MPa a/10152.6 psi a
Long-term stability at ±30 °C (±54 °F) - absolute pressure from gauge and differential pressure series
In 5 years ≤ (0.25 • r)%
Step response time T63 (without electrical damping) - absolute pressure from gauge and differential pressure series
Gauge pressure series
All measuring cells
Approx. 0.105 s
Differential pressure series
250 mbar/25 kPa/3.6 psi
Approx. 0.195 s
1300 mbar a/130 kPa a/18.8 psi a
Approx. 0.145 s
5 bar a/500 kPa a/72.5 psi a
30 bar a/3000 kPa a/435 psi a
100 bar a/10 MPa a/1450.3 psi a
SITRANS P320/P420 with 4 to 20 mA/HART
221
Technical data
13.3 Measuring accuracy of SITRANS P420
Effect of mounting position - absolute pressure from gauge and differential pressure series
In pressure per change of angle
● For absolute pressure (from the gauge pressure series): ≤
0.05 mbar/0.005 kPa/0.000725 psi per 10° incline
● For absolute pressure (from the differential pressure
series): 0.7 mbar/0.07 kPa/0.001015 psi per 10° incline
(zero-point correction is possible with position error compen-
sation)
13.3.6
Absolute pressure with front-flush diaphragm
Conformity error at limit point setting, including hysteresis and repeatability
Measuring span ratio r (spread, Turn-Down)
r = max. measuring span/set measuring span and nominal
measuring range
Linear characteristic curve
r ≤ 10
10 < r ≤ 30
All measuring cells
≤ 0.2%
≤ 0.4%
Effect of ambient temperature
In percent per 28 °C (50 °F)
All measuring cells
≤ (0.16 • r + 0.24)
Long-term stability at ±30 °C (±54 °F)
All measuring cells
In 5 years ≤ (0.25 • r)%
Step response time T63 (without electrical damping)
Approx. 0.105 s
Effect of mounting position
In pressure per change of angle
0.04 kPa/0.4 mbar/0.006 psi per 10° incline
(zero-point correction is possible with position error compen-
sation)
SITRANS P320/P420 with 4 to 20 mA/HART
222
Technical data
13.3 Measuring accuracy of SITRANS P420
13.3.7
Gauge pressure with front-flush diaphragm
Conformity error at limit point setting, including hysteresis and repeatability - gauge pressure with front-flush diaphragm
Measuring span ratio r (spread, Turn-Down)
r = max. measuring span/set measuring span and nominal
measuring range
● Linear characteristic curve
r ≤ 5
5 < r ≤ 100
1 bar/100 kPa/14.5 psi
≤ 0.075%
≤ (0.005 • r + 0.05)%
4 bar/400 kPa/58 psi
16 bar/1.6 MPa/232 psi
63 bar/6.3 MPa/914 psi
Effect of ambient temperature - gauge pressure with front-flush diaphragm
In percent per 28 °C (50 °F)
1 bar/100 kPa/14.5 psi
≤ (0.08 • r + 0.16)%
4 bar/400 kPa/58 psi
16 bar/1.6 MPa/232 psi
63 bar/6.3 MPa/914 psi
Long-term stability at ±30 °C (±54 °F) - gauge pressure with front-flush diaphragm
1 bar/100 kPa/14.5 psi
In 5 years ≤ (0.25 • r)%
4 bar/400 kPa/58 psi
16 bar/1.6 MPa/232 psi
In 5 years ≤ (0.125 • r)%
63 bar/6.3 MPa/914 psi
Step response time T63 (without electrical damping) - gauge pressure with front-flush diaphragm
Approx. 0.105 s
Effect of mounting position - gauge pressure with front-flush diaphragm
≤ 0.4 mbar/0.04 kPa/0.006 psi per 10° incline
(zero-point correction is possible with position error compen-
sation)
13.3.8
Differential pressure and flow
Conformity error at limit point setting, including hysteresis and repeatability - differential pressure and flow
Measuring span ratio r (spread, Turn-Down)
r = max. measuring span/set measuring span and nomi-
nal measuring range
Linear characteristic curve
r ≤ 5
5 < r ≤ 20
20 mbar/2 kPa/0.29 psi
≤ 0.075%
≤ (0.005 • r + 0.05)%
SITRANS P320/P420 with 4 to 20 mA/HART
223
Technical data
13.3 Measuring accuracy of SITRANS P420
Conformity error at limit point setting, including hysteresis and repeatability - differential pressure and flow
Linear characteristic curve
r ≤ 5
5 < r ≤ 60
60 mbar/6 kPa/0.87 psi
≤ 0.075%
≤ (0.005 • r + 0.05)%
Linear characteristic curve
r ≤ 5
5 < r ≤ 100
250 mbar/25 kPa/3.63 psi (PN160)
≤ 0.04%
≤ (0.004 • r + 0.045)%
600 mbar/60 kPa/8.70 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
30 bar/3 MPa/435.11 psi
250 mbar/25 kPa/3.63 psi (PN420)
≤ 0.065%
600 mbar/60 kPa/8.70 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
30 bar/3 MPa/435.11 psi
Root extraction characteris-
r ≤ 5
5 < r ≤ 20
tic
Flow > 50%
20 mbar/2 kPa/0.29 psi
≤ 0.075%
≤ (0.005 • r + 0.05)%
Root extraction characteris-
r ≤ 5
5 < r ≤ 60
tic
Flow > 50%
60 mbar/6 kPa/0.87 psi
≤ 0.075%
≤ (0.005 • r + 0.05)%
Root extraction characteris-
r ≤ 5
5 < r ≤ 100
tic
Flow > 50%
250 mbar/25 kPa/3.63 psi
≤ 0.04%
≤ (0.004 • r + 0.045)%
600 mbar/60 kPa/8.70 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
30 bar/3 MPa/435.11 psi
Root extraction characteris-
r ≤ 5
5 < r ≤ 20
tic
Flow 25 ... 50%
20 mbar/2 kPa/0.29 psi
≤ 0.15%
≤ (0.01 • r + 0.1)%
Root extraction characteris-
r ≤ 5
5 < r ≤ 60
tic
Flow 25 ... 50%
60 mbar/6 kPa/0.87 psi
≤ 0.15%
≤ (0.01 • r + 0.1)%
Root extraction characteris-
r ≤ 5
5 < r ≤ 100
tic
SITRANS P320/P420 with 4 to 20 mA/HART
224
Technical data
13.3 Measuring accuracy of SITRANS P420
Conformity error at limit point setting, including hysteresis and repeatability - differential pressure and flow
Flow 25 ... 50%
250 mbar/25 kPa/3.63 psi
≤ 0.08%
≤ (0.008 • r + 0.09)%
600 mbar/60 kPa/8.70 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
30 bar/3 MPa/435.11 psi
Effect of ambient temperature - differential pressure and flow
In percent per 28 °C (50 °F)
20 mbar/2 kPa/0.29 psi
≤ (0.15 • r + 0.1)%
60 mbar/6 kPa/0.87 psi
≤ (0.075 • r + 0.1)%
250 mbar/25 kPa/3.63 psi
≤ (0.025 • r + 0.0625)%
600 mbar/60 kPa/8.70 psi
≤ (0.0125 • r+0.0625)%
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
≤ (0.025 • r + 0.0625)%
30 bar/3 MPa/435.11 psi
≤ (0.0125 • r+0.0625)%
Effect of static pressure - differential pressure and flow
● On the lower range value
20 mbar/2 kPa/0.29 psi
≤ (0.2 • r) % per 70 bar (zero-point correction is possible with
position error compensation)
60 mbar/6 kPa/0.87 psi
≤ (0.1 • r)% per 70 bar (zero-point correction is possible with
250 mbar/25 kPa/3.63 psi
position error compensation)
600 mbar/60 kPa/8.70 psi
1600 mbar/160 kPa/23.21 psi
30 bar/3 MPa/435.11 psi
5 bar/500 kPa/72.52 psi
≤ (0.15 • r)% per 70 bar (zero-point correction is possible with
position error compensation)
● On the measuring span
20 mbar/2 kPa/0.29 psi
≤ 0.2% per 70 bar
60 mbar/6 kPa/0.87 psi
≤ 0.1% per 70 bar
250 mbar/25 kPa/3.63 psi
600 mbar/60 kPa/8.70 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
30 bar/3 MPa/435.11 psi
Long-term stability at ±30 °C (±54 °F) - differential pressure and flow
Static pressure max. 70 bar/7 MPa/1015 psi
20 mbar/2 kPa/0.29 psi
Per year ≤ (0.2 • r)%
60 mbar/6 kPa/0.87 psi
In 5 years ≤ (0.25 • r)%
SITRANS P320/P420 with 4 to 20 mA/HART
225
Technical data
13.3 Measuring accuracy of SITRANS P420
Long-term stability at ±30 °C (±54 °F) - differential pressure and flow
250 mbar/25 kPa/3.63 psi
In 5 years ≤ (0.125 • r)%
600 mbar/60 kPa/8.70 psi
In 10 years ≤ (0.15 • r)%
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
30 bar/3 MPa/435.11 psi
In 5 years ≤ (0.25 • r)%
In 10 years ≤ (0.35 • r)%
Step response time T63 (without electrical damping) - differential pressure and flow (PN 160)
20 mbar/2 kPa/0.29 psi
Approx. 0.160 s
60 mbar/6 kPa/0.87 psi
Approx. 0.150 s
250 mbar/25 kPa/3.63 ps
Approx. 0.135 s
600 mbar/60 kPa/8.70 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
30 bar/3 MPa/435.11 psi
Step response time T63 (without electrical damping) - differential pressure and flow (PN 420)
250 mbar/25 kPa/3.63 psi
Approx. 0.25 s
600 mbar/60 kPa/8.70 psi
Approx. 0.2 s
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
30 bar/3 MPa/435.11 psi
Effect of mounting position - differential pressure and flow
Effect of mounting position
In pressure per change of angle
≤ 0.7 mbar/0.07 kPa/0.028
inH2O per 10° incline
(zero-point correction is possible
with position error compensation)
SITRANS P320/P420 with 4 to 20 mA/HART
226
Technical data
13.3 Measuring accuracy of SITRANS P420
13.3.9
Level
Conformity error at limit point setting, including hysteresis and repeatability - level
Measuring span ratio r (spread,
r = max. measuring span/set measuring span and nominal measuring range
Turn-Down)
● Linear characteristic curve
r ≤ 5
5 < r ≤ 10
250 mbar/25 kPa/3.63 psi
≤ 0.125%
≤ (0.007 • r + 0.09) %
600 mbar/60 kPa/8.70 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
Effect of ambient temperature1) - level
In percent per 28 °C (50 °F)
250 mbar/25 kPa/3.63 psi
≤ (0.025 • r + 0.0625)%
5 bar/500 kPa/72.52 psi
600 mbar/60 kPa/8.70 psi
≤ (0.125 • r + 0.0625)%
1600 mbar/160 kPa/23.21 psi
1) Data only applies to the basic unit. The error of the remote seal must be considered additively.
Effect of static pressure - level
● On the lower range value
250 mbar/25 kPa/3.63 psi
≤ (0.3 • r) % per 70 bar (zero-point correction is possible with position error
compensation)
600 mbar/60 kPa/8.70 psi
≤ (0.15 • r)% per 70 bar (zero-point correction is possible with position error
compensation)
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
● On the measuring span
≤ (0.1 • r)% per 70 bar
Long-term stability at ±30 °C (±54 °F) - level
All measuring cells
In 5 years ≤ (0.25 • r)% static pressure max. 70 bar/7 MPa/
1015 psi
Effect of mounting position - level
Depends on the fill fluid in the
mounting flange
SITRANS P320/P420 with 4 to 20 mA/HART
227
Technical data
13.5 Operating conditions
13.4
Output
Output
HART
Output signal
4 … 20 mA
● Low saturation limit (continuously
3.55 mA, set to 3.8 mA in the factory
adjustable)
● High saturation limit (continuously
22.8 mA, factory-set to 20.5 mA or optionally 22.0 mA
adjustable)
● Ripple (without HART communication)
ISS ≤ 0.5 % of the max. output current
Adjustable damping
0 … 100 s, continuously adjustable over remote operation
0 … 100 s, in steps of 0.1 s adjustable over display
● Current transmitter
3.55 … 22.8 mA
● Failure signal
3.55 … 22.8 mA
Load
Resistor R [Ω]
● Without HART communication
8+
9
5
P$
UH
Power supply in V
● With HART communication
HART communicator (Handheld)
R =230 … 1100 Ω
SIMATIC PDM
R =230 … 600 Ω
Characteristic curve
● Linearly increasing or linearly decreasing
● Linear increase or decrease or according to the square root (only for
differential pressure and flow)
Bus physics
-
Polarity-independent
-
13.5
Operating conditions
Operating conditions for gauge pressure and absolute pressure (from the gauge pressure series)
Ambient conditions
● Ambient temperature
Note
Observe the temperature class in hazardous areas.
Enclosure
-40 … +100 °C (-40 … +212 °F)
Measuring cell with sili-
-40 … +85 °C (-40 … +185 °F)
cone oil filling
Measuring cell with inert
-40 … +85 °C (-40 … +185 °F)
oil
Measuring cell with FDA-
-10 ...+85 °C (14 ... +185 °F)
compliant oil
Display
-20 … +80 °C (-4 … +185 °F)
SITRANS P320/P420 with 4 to 20 mA/HART
228
Technical data
13.5 Operating conditions
Operating conditions for gauge pressure and absolute pressure (from the gauge pressure series)
● Storage temperature
-50 … +85 °C (-58 … +185 °F)
(for FDA-compliant oil: -20 ... + 85 °C
(-4 ... +185 °F))
Climate class in accordance
4K4H
with IEC 60721-3-4
Degree of protection accord-
Enclosure with appropriate cable
IP66/Type 4X
ing to IEC/EN 60529/UL50-E
gland
IP68 (2 hours at 1.5 m)
Enclosure with mounted M12 device
IP66/Type 4X
plug and/or lightning protection1)
Enclosure with mounted HAN device
IP65
plug1)
Electromagnetic compatibili-
ty
Interference emission and
In accordance with EN 61326 and
interference immunity
NAMUR NE 21
Process medium conditions
● Process temperature
Cell
Pressure
Temperature range
Measuring cell with sili-
-40 … +100 °C (-40 … +212 °F)
cone oil filling
Measuring cell with inert
oil (gauge pressure)
250 mbar
-40 … +100 °C (-40 … +212 °F)
1 bar/100 kPa/14.5 psi
-40 … +100 °C (-40 … +212 °F)
4 bar/400 kPa/58 psi
-40 … +100 °C (-40 … +212 °F)
16 bar/1.6 MPa/232 psi
-40 … +100 °C (-40 … +212 °F)
63 bar/6.3 MPa/914 psi
-40 … +100 °C (-40 … +212 °F)
160 bar/16 MPa/2321 psi
-20 … +100 °C (-4 … +212 °F)
400 bar/40 MPa/5802 psi
-20 … +100 °C (-4 … +212 °F)
700 bar/70 MPa/10152 psi
-20 … +100 °C (-4 … +212 °F)
Measuring cell with inert
-20 … +100 °C (-4 … +212 °F)
oil (absolute pressure)
Measuring cell with FDA-
-10 ... +100 °C (14 ... +212 °F)
compliant oil
1)
Only for non-Ex devices, not approved for use in Ex areas (ATEX, IECEx, FM, CSA)
Operating conditions for gauge pressure and absolute pressure with
front-flush diaphragm
Ambient conditions
● Ambient temperature
Note
Observe the temperature class in hazardous areas.
SITRANS P320/P420 with 4 to 20 mA/HART
229
Technical data
13.5 Operating conditions
Operating conditions for gauge pressure and absolute pressure with
front-flush diaphragm
Enclosure
-40 … +100 °C (-40 … +212 °F)
Measuring cell with sili-
-40 … +85 °C (-40 … +185 °F)
cone oil filling
Measuring cell with inert
-40 … +85 °C (-40 … +185 °F)
oil
Measuring cell with FDA-
-10 … +85 °C (14 … 185 °F)
compliant oil
Display
-20 … +80 °C (-4 … +176 °F)
● Storage temperature
-50 … +85 °C (-58 … +185 °F)
(with FDA-compliant oil: -20 ... + 85
°C (-4 ... +185 °F))
Climate class in accordance
4K4H
with IEC 60721-3-4
Degree of protection accord-
Enclosure with appropriate cable
IP66/Type 4X
ing to IEC/EN 60529/UL50-E
gland
IP68 (2 hours at 1.5 m)
Enclosure with mounted M12 device
IP66/Type 4X
plug and/or lightning protection1)
Enclosure with mounted HAN device
IP65
plug1)
Electromagnetic compatibili-
ty
● Interference emission and
In accordance with EN 61326 and
interference immunity
NAMUR NE 21
Process medium conditions
Process temperature2)
● Measuring cell with
-40 … +150°C (-40 … +302 °F)
silicone oil filling
-40 … +200°C (-40 … +392 °F) with
cooling extension
● Measuring cell with inert oil
-20 … +100 °C (-4 … +212 °F)
● Measuring cell with FDA-
-10 … +150°C (14 … 302 °F)
compliant oil
-10 … +200°C (14 … 392 °F) with
cooling extension
1)
Only for non-Ex devices, not approved for use in Ex areas (ATEX, IECEx, FM, CSA)
2)
Observe the temperature limits in the process connection standards (e.g. DIN 32676 and DIN 11851) for the maximum
process temperature for flush-mounted process connections.
Operating conditions for gauge pressure and absolute pressure (from
the differential pressure series), differential pressure and flow
Installation conditions
● Measuring cells for
Dynamic stress according to AD 2000-S1 No. 1.4:
differential pressure with
● For MAWP (PS) = 420 bar: Maximum 1000 load changes
PN 420
● At 10% of MAWP (PS): Any number of load changes
Ambient conditions
● Ambient temperature
SITRANS P320/P420 with 4 to 20 mA/HART
230
Technical data
13.5 Operating conditions
Operating conditions for gauge pressure and absolute pressure (from
the differential pressure series), differential pressure and flow
Note
Observe the temperature class in hazardous areas.
Enclosure
-40 … +100 °C (-40 … +212 °F)
Measuring cell with sili-
-40 … +85 °C (-40 … +185 °F)
cone oil filling
● Measuring cell
-20 … +85 °C (-4 … +185 °F)
30 bar (435 psi),
● For flow: -20 … +85 °C (-4 …
PN 420
+185 °F)
Measuring cell with inert
-40 … +85 °C (-40 … +185 °F)
oil
Measuring cell with FDA-
-10 … +85 °C (14 … 185 °F)
compliant oil
Display
-20 … +80 °C (-4 … +185 °F)
● Storage temperature
-50 … +85 °C (-58 … +185 °F)
(with FDA-compliant oil: -20 ... + 85
°C (-4 ... +185 °F))
Climate class in accordance
4K4H
with IEC 60721-3-4
Degree of protection accord-
Enclosure with appropriate cable
IP66/Type 4X
ing to IEC/EN 60529/UL50-E
gland
IP68 (2 hours at 1.5 m)
Enclosure with mounted M12 device
IP66/Type 4X
plug and/or lightning protection1)
Enclosure with mounted HAN device
IP65
plug1)
Electromagnetic compatibili-
ty
Interference emission and
In accordance with EN 61326 and
interference immunity
NAMUR NE 21
Process medium conditions
● Process temperature
Measuring cell with sili-
-40 … +100 °C (-40 … +212 °F)
cone oil filling
● Measuring cell
-20 … +100°C (-4 … +212 °F)
30 bar (435 psi),
PN 420
Measuring cell with inert
-20 … +100 °C (-4 … +212 °F)
oil
● Measuring cell
-20 … +100 °C (-4 … +212 °F)
30 bar (435 psi),
PN 420
Measuring cell with FDA-
-10 ... +100°C (14 ...+212°F)
compliant oil
1)
Only for non-Ex devices, not approved for use in Ex areas (ATEX, IECEx, FM, CSA)
SITRANS P320/P420 with 4 to 20 mA/HART
231
Technical data
13.5 Operating conditions
Operating conditions for level
Installation conditions
● Installation instruction
Specified by the flange
Ambient conditions
● Ambient temperature
Note
Observe the allocation of the max. permissible operating temperature to the max. permissible
operating pressure of the relevant flange connection.
Enclosure
-40 … +100 °C (-40 … +212 °F)
Measuring cell with sili-
-40 … +85 °C (-40 … +185 °F)
cone oil filling
Display
-20 … +80 °C (-4 … +185 °F)
● Storage temperature
-50 … +85 °C (-58 … +185 °F)
Climate class in accordance
4K4H
with IEC 60721-3-4
Degree of protection accord-
Enclosure with appropriate cable
IP66/Type 4X
ing to IEC/EN 60529/UL50-E
gland
IP68 (2 hours at 1.5 m)
Enclosure with mounted M12 device IP66/Type 4X
plug and/or lightning protection1)
Enclosure with mounted HAN device IP65
plug1)
Electromagnetic compatibili-
ty
Interference emission and
In accordance with EN 61326 and
interference immunity
NAMUR NE 21
Process medium conditions
● Process temperature
Measuring cell with sili-
● Plus side: See mounting flange
cone oil filling
● Minus side: -40 … +100 °C
(-40 … +212 °F)
1)
Only for non-Ex devices, not approved for use in Ex areas (ATEX, IECEx, FM, CSA)
SITRANS P320/P420 with 4 to 20 mA/HART
232
Technical data
13.6 Vibration resistance
13.6
Vibration resistance
General operating conditions
Gauge pressure series2)
Differential pressure series1)
Aluminum and stainless steel enclosure
Aluminum and stainless steel enclosure
Vibrations (sine)
2 ... 9 Hz at 0.3 mm
IEC 60068-2-6
9 ... 200 Hz at 5 m/s²
1 octave/min
5 cycles/axis
Continuous shocks (half-sine)
70 m/s²
IEC 60068-2-27
30 ms
6 shocks/axis
Continuous shocks (half-sine)
250 m/s²
IEC 60068-2-27
6 ms
1000 shocks/axis
1) Without mounting bracket
2) With mounting bracket
Operating conditions according to KTA
Gauge pressure series2)
Differential pressure series2)
3503
Aluminum and stainless steel enclosure
Aluminum and stainless steel enclosure
Vibrations (sine)
9 ... 35 Hz at 10 m/s²
IEC 60068-2-6
1 octave/min
1 cycle/axis
Vibrations (sine)
5 ... 7 Hz at 20 mm
IEC 60068-2-6
9 ... 100 Hz at 20 m/s²
10 octave/min
1 cycle/axis
Continuous shocks (half-sine)
300 m/s²
IEC 60068-2-27
11 ms
6 shocks/axis
2) With mounting bracket
Operating conditions according to IEC
Gauge pressure series2)
Differential pressure series1)2)
61298-3 (2g normal)
Aluminum and stainless steel enclosure Aluminum and stainless steel enclosure
Vibrations (sine)
10 ... 58 Hz at 0.3 mm
IEC 60068-2-6
58 ... 1000 Hz at 20 m/s²
1 octave/min
20 cycles/axis
1) Without mounting bracket
2) With mounting bracket
SITRANS P320/P420 with 4 to 20 mA/HART
233
Technical data
13.7 Construction
Operating conditions according to IEC
Differential pressure series1)
61298-3 (5g enhanced)
Aluminum and stainless steel enclosure
Vibrations (sine)
10 ... 58 Hz at 0.7 mm
IEC 60068-2-6
58 ... 1000 Hz at 50 m/s²
1 octave/min
20 cycles/axis
1) Without mounting bracket
Operating conditions for marine (only in Gauge pressure series1)2)
Differential pressure series3)
combination with order option E):
DNV-GL (Det Norske Veritas/Germa-
2 ... 25 Hz at 3.2 mm
nischer Lloyd)
25 ... 100 Hz at 40 m/s²
Lloyd’s Register
0.5 octave/min
Bureau Veritas
1 frequency sweep/axis
ABS (American Bureau of Shipping)
Amplification factor (Q) < 2, 30 Hz/90 min
RINA (Registro Italiano Navale)
Amplification factor (Q) > 2, resonant frequency/90 min
CCS (China Classification Society)
1) Without bracket and aluminum enclosure
2) With mounting bracket, aluminum and stainless steel enclosure
3) Without mounting bracket, aluminum and stainless steel enclosure
13.7
Construction
Construction for gauge pressure and absolute pressure (from the gauge pressure series)
Weight
Approx. 1.8 kg (3.9 lb) with aluminum enclosure
Approx. 3.8 kg (8.3 lb) with stainless steel enclosure
Material
● Wetted parts materials
Process connection
Stainless steel, material no. 1.4404/316L or Alloy C22, material no. 2.4602
Oval flange
Stainless steel, mat. no. 1.4404/316L
Seal diaphragm
Stainless steel, material no. 1.4404/316L or Alloy C276, material no. 2.4819
● Non-wetted parts materials
Electronics housing
● Low-copper die-cast aluminum GD-AlSi 12 or stainless steel precision casting, mat.
no. 1.4409/ CF-3M
● Standard: Powder coating with polyurethane
Option: 2 coats: Coat 1: epoxy-based; coat 2: Polyurethane
● Stainless steel nameplate (1.4404/316L)
Mounting bracket
Steel, galvanized, stainless steel 1.4301/304, stainless steel 1.4404/316L
SITRANS P320/P420 with 4 to 20 mA/HART
234
Technical data
13.7 Construction
Construction for gauge pressure and absolute pressure (from the gauge pressure series)
Process connection
● Connection pin G1/2A in accordance with DIN EN 837-1
● Female thread 1/2-14 NPT
● Oval flange (PN 160 (MAWP 2320 psi g)) with fastening screw thread:
-
7/16-20 UNF in accordance with EN 61518
– M10 in accordance with DIN 19213
● Oval flange (PN 420 (MAWP 2320 psi g)) with fastening screw thread:
-
7/16-20 UNF in accordance with EN 61518
– M12 in accordance with DIN 19213
● Male thread M20 x 1.5 and 1/2-14 NPT
Electrical connection
Cable inlet using the following screwed joints:
● M20 x 1.5
½-14 NPT
● Han 7D/Han 8D connector1)
● M12 connector
1)
Han 8D is identical to Han 8U.
Construction for gauge pressure, with flush mounted diaphragm
Weight (pressure transmitter without
Approx. 1.8 kg (3.9 lb) with aluminum enclosure
mounting flange)
Approx. 3.8 kg (8.3 lb) with stainless steel enclosure
Material
● Wetted parts materials
Process connection
Stainless steel, mat. no. 1.4404/316L
Seal diaphragm
Stainless steel, material no. 1.4404/316L or Alloy C276, material no. 2.4819
● Non-wetted parts materials
Electronics housing
● Low-copper die-cast aluminum GD-AlSi 12 or stainless steel precision casting,
mat. no. 1.4409/CF-3M
● Standard: Powder coating with polyurethane
D20 option: 2 coats: Coat 1: epoxy-based; coat 2: Polyurethane
● Stainless steel nameplate (1.4404/316L)
Mounting bracket
Steel, galvanized, stainless steel 1.4301/304, stainless steel 1.4404/316L
Process connection
● Flanges as per EN and ASME
● F&B and Pharma flange
● BioConnect/BioControl
● PMC style
Electrical connection
Cable inlet using the following screwed joints:
● M20x1.5
½-14 NPTM
● Han 7D/Han 8D connector1)
● M12 connector
1)
Han 8D is identical to Han 8U.
SITRANS P320/P420 with 4 to 20 mA/HART
235
Technical data
13.7 Construction
Construction for gauge pressure and absolute pressure (from the differential pressure series), differential pressure and flow
rate
Weight
Approx. 3.9 kg (8.5 lb) with aluminum enclosure
Approx. 5.9 kg (13 lb) with stainless steel enclosure
Material
● Wetted parts materials
Seal diaphragm
Stainless steel, mat. no. 1.4404/316L, Alloy C276, mat. no. 2.4819, Monel 400, mat.
no. 2.4360, tantalum or gold
Pressure caps and vents
Stainless steel, mat. no. 1.4408 to PN 160, mat. no. 1.4571/316Ti for PN 420, Al-
loy C22, 2.4602 or Monel 400, mat. no. 2.4360
O-ring
FKM (Viton) or optionally: PTFE, FEP, FEPM and NBR
● Non-wetted parts materials
Electronics housing
● Low-copper die-cast aluminum GD-AlSi 12 or stainless steel precision casting,
mat. no. 1.4409/CF-3M
● Standard: Powder coating with polyurethane
D20 option: 2 coats: Coat 1: epoxy-based; coat 2: Polyurethane
● Stainless steel nameplate (1.4404/316L)
Pressure cap screws
Stainless steel ISO 3506-1 A4-70
Mounting bracket
Steel, galvanized, stainless steel 1.4301/304, stainless steel 1.4404/316L
Process connection
1/4-18 NPT female thread and flange connection with 7/16-20 UNF fastening screw
thread in accordance with EN 61518 or M10 fastening screw thread in accordance
with DIN 19213 (M12 for PN 420 (MAWP 6092 psi))
Electrical connection
Screw terminals
Cable inlet using the following screwed joints:
● M20 x 1.5
½-14 NPT
● Han 7D/Han 8D connector1)
● M12 connector
1)
Han 8D is identical to Han 8U.
Construction for level
Weight
● In accordance with EN (pressure
Approx. 11 … 13 kg (24.2 … 28.7 lb) with aluminum enclosure
transmitter with mounting flange,
Approx. 13 ... 15 kg (28.7 ... 33 lb) with stainless steel enclosure
without tube)
● In accordance with ASME
Approx. 11 … 18 kg (24.2 … 39.7 lb) with aluminum enclosure
(pressure transmitter with
Approx. 13 ... 20 kg (28.7 ... 44 lb) with stainless steel enclosure
mounting flange, without tube)
Material
● Wetted parts materials
Plus side
SITRANS P320/P420 with 4 to 20 mA/HART
236
Technical data
13.7 Construction
Construction for level
● Seal diaphragm on the
Stainless steel, mat. no. 1.4404/316L, Monel 400, mat. no. 2.4360, Alloy B2, mat. no.
mounting flange
2.4617, Alloy C276, mat. no. 2.4819, Alloy C22, mat. no. 2.4602, tantalum, PTFE
● Sealing surface
Smooth as per EN 1092-1, form B1 or ASME B16.5 RF 125 … 250 AA for stainless
steel 316L, EN 2092-1 form B2 or ASME B16.5 RFSF for the remaining materials
Sealing material in the pressure
caps
● For standard applications
FKM (Viton)
● For underpressure
Copper
applications on the mounting
flange
Minus side
● Seal diaphragm
Stainless steel, mat. no. 1.4404/316L
● Pressure caps locking screws
Stainless steel, mat. no. 1.4408
● Locking screw
Stainless steel ISO 3506-1 A4-70
● O-ring
FKM (FKM (Viton))
● Non-wetted parts materials
Electronics housing
● Low-copper die-cast aluminum GD-AlSi 12 or stainless steel precision casting,
mat. no. 1.4409/CF-3M
● Standard: Powder coating with polyurethane
D20 option: 2 coats: Coat 1: epoxy-based; coat 2: Polyurethane
● Stainless steel nameplate (1.4404/316L)
Pressure cap screws
Stainless steel ISO 3506-1 A4-70
Measuring cell filling
Silicone oil
● Mounting flange fill fluid
Silicon oil or a different design
Process connection
● Plus side
Flange as per EN and ASME
● Minus side
1/4-18 NPT female thread and flange connection with M10 fastening screw thread in
accordance with DIN 19213 (M12 for PN 420 (MAWP 6092 psi)) or 7/16-20 UNF in
accordance with EN 61518
Electrical connection
Screw terminals
Cable inlet using the following screwed joints:
● M20 x 1.5
½-14 NPT
● Han 7D/Han 8D connector1)
● M12 connector
1)
Han 8D is identical to Han 8U.
SITRANS P320/P420 with 4 to 20 mA/HART
237
Technical data
13.9 Display, keys and auxiliary power
13.8
Torques
Torques
Connecting terminals
● Connecting terminals in the connection compartment
1.5 Nm (1.1 ft lb)
● External ground terminal on enclosure
Cable glands/blanking plugs
● Screw-in torque for plastic gland in all enclosures
4 Nm (3 ft lb)
● Screw-in torque for metal/stainless steel glands in
6 Nm (4.4 ft lb)
aluminum/stainless steel enclosure
● Screw-in torque for NPT adapter made of metal/stainless
15 Nm (11.1 ft lb)
steel in aluminum/stainless steel enclosure
● Tightening torque for union nut made of plastic
2.5 Nm (1.8 ft lb)
● Tightening torque for union nut made of metal/stainless
4 Nm (3 ft lb)
steel
Screws for mounting bracket (option)
● Tightening torque for thread M8 or 5/16-24 UNF
18 Nm (13.2 ft lb)
● Tightening torque for thread M10 or 7/16-20 UNF
36 Nm (26.5 ft lb)
Retaining screws for rotation of the enclosure
● Tightening torque for aluminum enclosure
3.8 Nm (2.8 ft lb)
● Tightening torque for stainless steel enclosure
3.5 Nm (2.5 ft lb)
13.9
Display, keys and auxiliary power
Display and buttons
Buttons
4 buttons for operation directly on the device
Display
● With or without integrated display (optional)
● Cover with glass pane (option)
Auxiliary power UH
HART
Terminal voltage on pressure transmitter
● DC 10.5 V … 45 V
● In the case of intrinsically safe operation 10.5 V … 30 V DC
Auxiliary power
-
Separate supply voltage
-
SITRANS P320/P420 with 4 to 20 mA/HART
238
Technical data
13.10 Certificates and approvals
13.10
Certificates and approvals
Explosion protection in accordance with ATEX
BVS 18 ATEX E049X
Intrinsic safety "i"
Designation
II 1/2 G Ex ia/ib IIC T4/T6 Ga/Gb
Permissible ambient temperature
-40 … +80 °C (-40 … +176 °F) Temperature class T4
-40 … +55 °C (-40 … +158 °F) Temperature class T6
Permissible temperature of medium
-40 … +100 °C (-40 … +212 °F) temperature class T4
-40 … +70 °C (-40 … +158 °F) temperature class T6
Connection
To a certified intrinsically safe circuit with the max. values:
Ui = 30 V, Ii = 101 mA, Pi = 760 mW
Ui = 29 V, Ii = 110 mA, Pi = 800 mW
Effective inner capacitance
Ci = 3.29 nF
Effective inner inductance
Li = 0.24 µH
Flameproof enclosure encapsulation "d"
Designation
II 1/2G Ex ia/db IIC T4/T6 Ga/Gb
Permissible ambient temperature
-40 … +80 °C (-40 … +176 °F) temperature class T4
-40 … +70 °C (-40 … +158 °F) temperature class T6
Permissible temperature of medium
-40 … +100 °C (-40 … +212 °F) temperature class T4
-40 … +70 °C (-40 … +158 °F) temperature class T6
Connection
To a circuit with the operating values:
UH = 10.5 … 45 V DC, 4 ... 20 mA
Dust explosion protection for zones 21, 22
Designation
II 2D Ex tb IIIC T120 °C Db
II 3D Ex tc IIIC T120 °C Dc
Permissible ambient temperature
-40 ... +80 °C (-40 ... +176 °F)
Permissible temperature of medium
-40 … +100 °C (-40 … +212 °F)
Max. surface temperature
120°C (248°F)
Connection
To a circuit with the operating values:
UH = 10.5 … 45 V DC, 4 ... 20 mA
Dust explosion protection for Zone 20, 21, 22
Designation
II 1D Ex ia IIIC T120 °C Da
II 2D Ex ib IIIC T120 °C Db
II 3D Ex ic IIIC T120 °C Dc
Permissible ambient temperature
-40 ... +80 °C (-40 ... +176 °F)
Permissible temperature of medium
-40 … +100 °C (-40 … +212 °F)
Connection
To a certified intrinsically safe circuit with the max. values:
Ui = 30 V, Ii = 101 mA, Pi = 760 mW
Ui = 29 V, Ii = 110 mA, Pi = 800 mW
Effective inner capacitance
Ci = 3.29 nF
Effective inner inductance
Li = 0.24 µH
SITRANS P320/P420 with 4 to 20 mA/HART
239

 

 

 

 

 

 

 