TROUBLE SHOOTING MANUAL
MICROPROCESSOR BASED
LOCOMOTIVE CONTROL SYSTEM
MEP 660
FOR DIESEL ELECTRIC LOCOMOTIVES
As Per
RDSO Specification No. MP.0.24.00.26 Rev. 0.3 November 2005
P- 4 / 5 B, I.D.A NACHARAM
HYDERABAD - 500 076
Ph. No. 040- 2717 3990
Fax. 040 2717 4908
Email: marketing@medhaindia.com
URL: www.medhaindia.com
CONTENTS
DESCRIPTION
PAGE
1.0 INTRODUCTION
1 - 3
2.0 HIGH PRIORITY FAULT MESSAGES
4-116
3.0 MEDIUM PRIORITY FAULT MESSAGES
117-178
4.0 LOW PRIORITY FAULT MESSAGES
179-260
5.0 ONLY ERROR LOG MESSAGES
261-279
6.0 Annexure-1
280-281
7.0 Annesure-2
282
8.0 Annesure-3
283-284
9.0 Annesure-4
285
10.0 Revision sheet
286
1.0
INTRODUCTION
The Microprocessor Based Locomotive Control system MEP 660 continuously monitors
operating levels of various parameters like currents, voltages, temperatures, pressures,
RPMs etc. and status of all Auxiliary and main contacts of Contactors. The MEP 660
identifies any abnormal working conditions of any equipment that can indicate a fault in
that equipment. Various faults that are identified are given in the Fault Manual document
No. IM 10 issued by M/S Medha Servo Drives. On identification of any such fault, an
appropriate control action is taken instantly to avoid damage to traction equipments. A
fault message, along with any restriction applied due to the fault, is displayed on the
display unit for guiding the driver. The fault is recorded in the error log along with date
and time stamp. Eight data packs of various locomotive parameters are recorded from 5
seconds prior to the occurrence of fault to three seconds after the occurrence of fault @
one data pack every second. These data packs help the maintenance staff later for
analysis of how the fault has developed and also helps analyse complicated faults.
The classification of these faults and their reset procedure are given in Annexure - 1 for
easy reference
This trouble-shooting manual provides information like restrictions imposed by the fault,
probable causes that can cause the fault and the remedial actions to isolate the fault. The
isolation procedures are written for each and every fault message Identified and listed in
the above Fault Message Manual. No troubleshooting guide is required for the fault
recovery messages that are listed in the Fault Message Manual.
There are 19 cards / modules in the MEP 660 control unit. These modules are plug in
type and inserted in the corresponding slots. Through out this manual the slots are
assumed as 1 to 19, from left to right. The card type No. is labeled both on the card and
MEP-660 control unit to avoid wrong insertion of card. A list of cards and their location of
slots are given as Annexure-2
In this manual an attempt is made to explain step by step procedure to isolate the fault
both in locomotive and as well as MEP 660 components. The trouble-shooting manual has
been discussed anticipating that the user has got basic concept on the locomotive,
through knowledge on MEP 660 components and their functionality. It is recommended
that the user should read the system manual document No. 08 and schematics of MEP
660 document No. ED1000 before this document is used.
In the step by step procedure of fault isolation, the user has been asked to perform
Manual testing of inputs and outputs through display unit wherever necessary to find the
status of digital inputs/outputs and proper functioning of out put devices. The procedure
for Manual testing of inputs and outputs are described in the System Manual document
No. IM 08.
Similar way there are three Digital out cards available from slot 14 to 16. The list of
output devices that are connected to each card is given as Annexure - 3 for easy
reference.
There are 5 digital input cards in the MEP 660 control unit from slot 9 to slot 13. A set of
16 inputs are connected to each card through ear marked cables having unique ID nos.
(like ID:xx). The digital input cards MDIP16 are provided with Green and Yellow LEDs on
the front fascia of the card to know the status of the digital inputs. There are 16 green
LEDs on the bottom portion and 16 Yellow LEDs on the top portion of the front fascia. A
number side to the LED identifies these LEDs. The logic between these Green and Yellow
1
LEDs is that both LEDs of same number should toggle their status either ON or OFF
simultaneously. The matrix of these LEDs is given as Annexure-4 for reference
indicating which LED represents to what digital input. These LEDs are addressed by their
Numbers printed on the front fascia by side of the LED and corresponding slot on the
base in which the card is available.
The various digital inputs and digital outputs with their connections between locomotive
and the control unit having their corresponding cable IDs and pin numbers are given as
Annexure-5. This data is extracted from the Electrical schemnatics for MEP 660 system.
Doc. No. ED-1000.
The menu system and the display parameters are extensively referred in this manual to
identify the fault. Various menu and submenu options available and the displayed
parametes in each group are given as Annexure-6 for easy reference to navigate
through Display menu.
2
Precautions to be followed while troubleshooting:
Where ever locomotive has been asked to move or open first notch with GF
ON, extreme care should be taken that brakes are applied physically on the
wheels and brake system is working normal as per Rail Road instructions.
Wherever user has been asked to replace the card or cable, Switch off all
breakers, replace the card/cable and switch ON the breakers and then continue
the test. Removal of card or cable with supply can damage the respective card /
module.
Use proper tools like spanners / nut drivers etc to remove / replace defective
components. Do not try with un-sized tools.
While reconnecting wires / cables ensure proper cable tags are available and
they are connected correctly to the correct terminals. If cable tags are missing,
disconnect cables / wires checkup continuity, re-tag the wires and connect.
Wrong connection of any wire / cable can lead into further complicated trouble.
3
1.0
HIGH PRIORITY FAULTS
PARAMETER
DESCRIPTION
FAULT CODE
1001
FAULT MESSAGE
Low Water Level.
RESTRICTIONS
Engine Shutdown
ALARM BELL
Continuous ON
RESET LEVEL
LOW, MANUAL.
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when fault is cleared and 20 seconds itime is lapsed.
RECOVERY
PROBABLE
1.
LWS operated due to low water level.
CAUSES
2.
Faulty micro switch, bellow, float. Etc. in the LWS unit.
3.
Any open ciduit in LWS wiring from LWS to MEP660.
FAULT
1.
Check Water level. If water is less add water. Reset the fault.
ISOLATION
2.
If water is full, Check operation of the LWS by operating the LWS
cock.
The number 4 green and yellow LEDs on MDIP-16 card in slot 11
indicate the status of LWS feed back signal.
Both LEDs glow with LWS normal position (full water) and both
LEDs are OFF with LWS operated (low water)
A.
If both LEDS are not ON with LWS normal position (full water),
a) Check Voltage at wire No. TO1 on backside TB. Observe for
any disconnected wires. If so reconnect.
b) If voltage at wire No. TO1 is zero
1) Check voltage at wire No. 51 at backside TB. Observe for
any disconnected wires at the terminal. If so reconnect.
2) If voltage is >65V.
i. Either LWS wiring or LWS faulty
Check wiring continuity of wire 51 from backside
TB to LWS.
Check wiring continuity of wire No. TO1 from LWS
to backside TB.
Check for any disconnected wires at LWS.
If wire continuity is good, LWS micro switch is
defective. Replace and check.
c) If the Voltage at back side TB on wire No. TO1 is > 65V
1) Check the wiring continuity of wire No. TO1 from
backside TB to MEP-660 by removing the coupler (DI32-
DI47) - (Pin. E). If no continuity replace the cable.
B. If only Green LED is glowing, and yellow LED is not glowing, it
indicates that the LWS feed back input is available upto digital
input card and the DI card in slot 11 is defective. Replace the
card.
4
PARAMETER
DESCRIPTION
FAULT CODE
1002
FAULT MESSAGE
Engine Over Speed.
RESTRICTIONS
Engine Shutdown
ALARM BELL
30 Seconds
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when engine is not running and Master Handle is kept in
RECOVERY
IDLE position for 10 secconds.
PROBABLE
1. Faulty wiring from tacho generator to MEP-660
CAUSES
2. Faulty Tacho generator
3. Faulty governor / sticky racks
FAULT
1. Reset the fault. Ensure that there are no sticky racks or fuel
ISOLATION
injection pumps. If OSTA is tripped, reset it. Crank the engine.
2. Check the notch wise engine RPM.
A. If the RPM is not correct
a) Check up with the governor and set the notch wise engine
RPMs with in limits.
B. If the displayed RPM is correct
a) Check up with tacho generator wiring from tacho generator
terminal board to backside TB to MEP-660 for any open
circuit or loose connections.
b) Check up tacho generator frequency (engine RPM) with
conventional RPM meter as used in conventional WDM3A
locomotives.
c) If notch wise readings are not stable and hevy fluctaution is
noticed, check for tacho generator and replace.
5
PARAMETER
DESCRIPTION
FAULT CODE
1003
FAULT MESSAGE
Exciter Drive Short Circuit Fault.
RESTRICTIONS
Motoring and Dynamic Brake Prohibited
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
No auto recovery.
RECOVERY
PROBABLE
1. There may be a wiring fault with FCP (EFR1 to EFR4)
CAUSES
2. PWM output card is defectie.
3. The current sensor is giving faulty output.
FAULT
1. Check foe any disconnected wires and shorting to other terminals at
ISOLATION
FCP terminal board. If any found, check and reconnect the wires.
2. Connect DC ammeter 0-10Amps to wire terminals 61F (+) and 61FF
(-) at EXPR interlocks.
3. Pack the EXPR interlock 61F and 61FF with insulating sheet.
4. Switch on breakers. From the display menu, Select Display mode to
Excitation Display to view exciter field current EXFI.
A. If current in the meter is equal to the displayed current of EXFI,
then the current sensor is good. PWM output card is defective.
Replace the card.
B. If current in the meter is less than the displayed current of EXFI,
then the current sensor is faulty. Replace the current sensor.
However this will have an accompanied message or
‘Exciter
field current sensor EXFI Faulty’ (Fault code 1176).
6
PARAMETER
DESCRIPTION
FAULT CODE
1004
FAULT MESSAGE
LLOB trip. Reset Plunger.
RESTRICTIONS
Cranking Prohibited
ALARM BELL
Continuous ON
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Autometic when the fault is cleared and 20 seconds of time is lapsed.
RECOVERY
PROBABLE
1. Low Lube Oil Button might have tripped in the Woodward governor.
CAUSES
Or
2. The feedback input wire OPSFB is getting wrong supply.
FAULT
1. Check the Low Lube Oil Button position on the Woodward governor.
ISOLATION
2. If tripped (projecting outside),
A. Press the button inside to reset.
B. Reset the Fault manually and crank the engine.
3. If LLOB is not in tripped position
A. Pull the knob outside and reset once again.
B. Check the OPS (LLOB) feed back signal level with Number 5
Green and Yellow LEDs on Digital Input card MDIP-16 in 11th
slot.
With LLOB in normal position, both LEDs are OFF.
With LLOB in tripped position, both LEDs are ON.
C. If both LEDs are ON with LLOB in normal position
a) Check voltage at wire No. 1B at the back side TB.
b) If voltage is > 65V
c) Disconnect the wires 1B and identify which wire is getting
supply.
d) If the wire is from governor amphonal plug, then the micro
switch in the Governor is shorted. Replace the micro switch.
e) If the wire is from loco side, there may be a wrong feed back
from indication panel side. Check up and isolate the supply.
Note: Most probably this fault is accompanied with a Fault message
‘LLOB Trip. Reset Plunger’ (Fault code 1005). Driver might have reset
the fault on the display with out reseting the LLOB on the Governor.
7
PARAMETER
DESCRIPTION
FAULT CODE
1005
FAULT MESSAGE
LLOB Trip. Reset Plunger.
RESTRICTIONS
Cranking Prohibited
ALARM BELL
Continuous ON
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Autometic when the fault is cleared and 20 seconds of time is lapsed.
RECOVERY
PROBABLE
1. Low Lube Oil Button might have tripped in the Woodward governor.
CAUSES
Or
2. The feedback input wire OPSFB is getting wrong supply.
FAULT
1. Check the Low Lube Oil Button position on the Woodward governor.
ISOLATION
2. If tripped (Knob projecting outside),
A. Press the button inside to reset.
B. Reset the Fault manually and crank he engine.
3. If LLOB is not in tripped position
A. Pull the knob outside and reset once again.
B. Check the OPS (LLOB) feed back signal level with Number 5
Green and Yellow LEDs on Digital Input card MDIP 16 in 11th
slot.
With LLOB in normal position, both LEDs are OFF.
With LLOB in tripped position, both LEDs are ON.
C. If both LEDs are ON with LLOB in normal position
a) Check voltage at wire No. 1B at the back side TB.
b) If voltage is > 65V
c) Disconnect the wires 1B and identify which wire is getting
supply.
d) If the wire is from governor amphonal plug, then the micro
switch in the Governor is shorted. Replace the micro switch.
e) If the wire is from loco side, there may be a wrong feed back
from indication panel side. Check up and isolate the supply.
Note: Most probably this fault is logged due to LLOB tripping while
notching up or notching down or sudden easing of throttle
after working in higher notches.
Imp. : If the fault is repeatedly logging and engine shutting
down, the shutting down pressures of lube oil and the
timings need to be recalibrated on the governor.
8
PARAMETER
DESCRIPTION
FAULT CODE
1006
FAULT MESSAGE
HOT ENGINE. Can’t Power Up
RESTRICTIONS
Motoring and Dynamic Brake are Prohibited.
Engine speed restricted to IDLE.
ALARM BELL
Continuous ON
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Autometic when the engine temperature is less than 900 C.
RECOVERY
PROBABLE
1. Engine water temperature is high.
CAUSES
FAULT
1. Allow the engine to cool till temperature is reduced below 900C.
ISOLATION
9
PARAMETER
DESCRIPTION
FAULT CODE
1007
FAULT MESSAGE
Power Circuit Ground Fault.
RESTRICTIONS
Motoring and Dynamic Brake Prohibited.
Engine speed restricted to Idle.
ALARM BELL
Continuous ON
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Autometic when the traction alternator neutral to ground leakage
RECOVERY
current value is reduced below the set limit and Master Handle is
brought to IDLE.
PROBABLE
1. The fault may be transient or permanent.
CAUSES
2. The Fault is automatically recovered after 15 seconds once the
throttle is brought to IDLE.
3. Driver can work further with out any trouble.
4. If the fault is recoring for more than 3 times in one hour, it
indicates fault is persisting and needs attention.
5. The fault is logged due to
A. Moisture in Traction Motors.
B. Flash over in Traction Motors
C. Cracked insulators on traction Traction Alternators / Traction
Motors / Power Rectifier / Dynamic brake grids / BKT / REV /
power contactors.
D. Any external metal parts touching to power terminals.
E. Any power circuit cables are rubbing to body and insulation is
damaged.
FAULT
If the fault is recurring:
ISOLATION
1. Set the display mode to ‘Mixed’ through Display Menu setup.
2. Apply Loco motive brakes and ensure locomotive brakes are
physically applied.
3. Set the locomotive operation to motoring mode and notch to 1.
4. Observe the traction alternator leakage current (TANGI) on the
display.
5. If the leakage cauurent ismore than set (0.4 Amps) value, then
there is a real ground.
A. Inspect traction alternator power circuit cables for any rubbing
to loco body. If so isolate the cables.
B. Inspect traction motor cables for any rubbing to locobody. If so
isolate the cables.
C. Check for any cracked insualators in the equipements as
mentioned above.
D. Check for any flash over / burnt marks in the power rectifier and
connected cables.
10
PARAMETER
DESCRIPTION
FAULT CODE
1008
FAULT MESSAGE
Control Circuit Ground Fault.
RESTRICTIONS
Cranking prohibited.
ALARM BELL
Continuous ON
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when the control circuit negative to ground leakage current
RECOVERY
value is reduced below the set limit and 15 seconds lapsed with Master
Handle in IDLE. Automatic Fault reset is permitted for 3 times in an
hour and after that manually reset is required.
PROBABLE
1. Any control circuit wiring is grounded.
CAUSES
2. Any equipements like dust blower motors, sander coils, lighting
circuit etc. connected in control circuits are having low / zero
insulation resistance value.
FAULT
1. Identify the control circuit having low/zero Insulation Resistance
ISOLATION
(IR) value.
2. Isoalte the low insulation either replacing the equipement or by
insulating the grounded wires.
Note: This fault is logged during cranking only.
11
PARAMETER
DESCRIPTION
FAULT CODE
1009
FAULT MESSAGE
Locked Axle on Wheel Number 1
RESTRICTIONS
Motoring and Dynamic Brake Prohibited.
ALARM BELL
As long as Loco moves and for 30 Seconds minimum.
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
No auto recovery.
RECOVERY
PROBABLE
1. There may be a physical locked axle.
CAUSES
2. Traction Motor speed sensor is faulty.
3. The speed signal gear assembly worked out from the Traction Motor
Armature shaft.
FAULT
1. If there is physically locked axle, act according to Rail Road rules
ISOLATION
and regulations.
2. If the axle is not locked physically,
A. Reset the fault manually. Set the display mode to ‘Wheel Slip
Display Mode’ under Display Menu. Open the notch to 1 in
motoring and slowly release the brakes.
B. Observe the individual Traction Motor speeds and currents on
the display.
C. If the currents of all Traction Motor are with in limits, and speed
of Traction Motor No.1 is zero / less, MEP-660 is not getting
proper speed signal from Traction Motor No.1.
D. Stop the locomotive and
a) Check for any cable disconnection in the No.1 Traction Motor
Armature speed sensor circuit. Replace / reconnect the cable.
b) Check for any dislocation of the speed sensor on the end
shield of Traction Motor 1. Reconnect the sensor properly.
c) Remove the end shield of Traction motor No.1 and check for
dislocation of sensor gear on the shaft. If so replace the Tr.
Motor / refit the sensor gear properly.
12
PARAMETER
DESCRIPTION
FAULT CODE
1010
FAULT MESSAGE
Locked Axle on Wheel Number 2
RESTRICTIONS
Motoring and Dynamic Brake Prohibited.
ALARM BELL
As long as Loco moves and for 30 Seconds minimum.
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
No auto recovery.
RECOVERY
PROBABLE
1. There may be a physical locked axle.
CAUSES
2. Traction Motor speed sensor is faulty.
3. The speed signal gear assembly worked out from the Traction Motor
Armature shaft.
FAULT
1. If there is physically locked axle, act according to Rail Road rules
ISOLATION
and regulations.
2. If the axle is not locked physically,
A. Reset the fault manually. Set the display mode to ‘Wheel Slip
Display Mode’ under Display Menu. Open the notch to 1 in
motoring and slowly release the brakes.
B. Observe the individual Traction Motor speeds and currents on
the display.
C. If the currents of all Traction Motor are with in limits, and speed
of Traction Motor No.2 is zero / less, MEP-660 is not getting
proper speed signal from Traction Motor No.2.
D. Stop the locomotive and
a) Check for any cable disconnection in the No.2 Traction Motor
Armature speed sensor circuit. Replace / reconnect the cable.
b) Check for any dislocation of the speed sensor on the end
shield of Traction Motor 2. Reconnect the sensor properly.
c) Remove the end shield of Traction motor No.2 and check for
dislocation of sensor gear on the shaft. If so replace the Tr.
Motor / refit the sensor gear properly.
13
PARAMETER
DESCRIPTION
FAULT CODE
1011
FAULT MESSAGE
Locked Axle on Wheel Number 3
RESTRICTIONS
Motoring and Dynamic Brake Prohibited.
ALARM BELL
As long as Loco moves and for 30 Seconds minimum.
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
No auto recovery.
RECOVERY
PROBABLE
1. There may be a physical locked axle.
CAUSES
2. Traction Motor speed sensor is faulty.
3. The speed signal gear assembly worked out from the Traction Motor
Armature shaft.
FAULT
1. If there is physically locked axle, act according to Rail Road rules
ISOLATION
and regulations.
2. If the axle is not locked physically,
A. Reset the fault manually. Set the display mode to ‘Wheel Slip
Display Mode’ under Display Menu. Open the notch to 1 in
motoring and slowly release the brakes.
B. Observe the individual Traction Motor speeds and currents on
the display.
C. If the currents of all Traction Motor are with in limits, and speed
of Traction Motor No.3 is zero / less, MEP-660 is not getting
proper speed signal from Traction Motor No.3
D. Stop the locomotive and
a) Check for any cable disconnection in the No.3 Traction Motor
Armature speed sensor circuit. Replace / reconnect the cable.
b) Check for any dislocation of the speed sensor on the end
shield of Traction Motor 3. Reconnect the sensor properly.
c) Remove the end shield of Traction motor No.3 and check for
dislocation of sensor gear on the shaft. If so replace the Tr.
Motor / refit the sensor gear properly.
14
PARAMETER
DESCRIPTION
FAULT CODE
1012
FAULT MESSAGE
Locked Axle on Wheel Number 4
RESTRICTIONS
Motoring and Dynamic Brake Prohibited.
ALARM BELL
As long as Loco moves and for 30 Seconds minimum.
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
No auto recovery.
RECOVERY
PROBABLE
1. There may be a physical locked axle.
CAUSES
2. Traction Motor speed sensor is faulty.
3. The speed signal gear assembly worked out from the Traction
Motor Armature shaft.
FAULT
1. If there is physically locked axle, act according to Rail Road rules
ISOLATION
and regulations.
2. If the axle is not locked physically,
A. Reset the fault manually. Set the display mode to ‘Wheel Slip
Display Mode’ under Display Menu. Open the notch to 1 in
motoring and slowly release the brakes.
B. Observe the individual Traction Motor speeds and currents on
the display.
C. If the currents of all Traction Motor are with in limits, and speed
of Traction Motor No.4 is zero / less, MEP-660 is not getting
proper speed signal from Traction Motor No.4.
D. Stop the locomotive and
a) Check for any cable disconnection in the No.4 Traction Motor
Armature speed sensor circuit. Replace / reconnect the cable.
b) Check for any dislocation of the speed sensor on the end
shield of Traction Motor 4. Reconnect the sensor properly.
c) Remove the end shield of Traction motor No.4 and check for
dislocation of sensor gear on the shaft. If so replace the Tr.
Motor / refit the sensor gear properly.
15
PARAMETER
DESCRIPTION
FAULT CODE
1013
FAULT MESSAGE
Locked Axle on Wheel Number 5
RESTRICTIONS
Motoring and Dynamic Brake Prohibited.
ALARM BELL
As long as Loco moves and for 30 Seconds minimum.
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
No auto recovery.
RECOVERY
PROBABLE
1. There may be a physical locked axle.
CAUSES
2. Traction Motor speed sensor is faulty.
3. The speed signal gear assembly worked out from the Traction Motor
Armature shaft.
FAULT
1. If there is physically locked axle, act according to Rail Road rules
ISOLATION
and regulations.
2. If the axle is not locked physically,
A. Reset the fault manually. Set the display mode to ‘Wheel Slip
Display Mode’ under Display Menu. Open the notch to 1 in
motoring and slowly release the brakes.
B. Observe the individual Traction Motor speeds and currents on
the display.
C. If the currents of all Traction Motor are with in limits, and speed
of Traction Motor No.5 is zero / less, MEP-660 is not getting
proper speed signal from Traction Motor No.5.
D. Stop the locomotive and
a) Check for any cable disconnection in the No.5 Traction Motor
Armature speed sensor circuit. Replace / reconnect the cable.
b) Check for any dislocation of the speed sensor on the end
shield of Traction Motor 5. Reconnect the sensor properly.
c) Remove the end shield of Traction motor No.5 and check for
dislocation of sensor gear on the shaft. If so replace the Tr.
Motor / refit the sensor gear properly.
16
PARAMETER
DESCRIPTION
FAULT CODE
1014
FAULT MESSAGE
Locked Axle on Wheel Number 6
RESTRICTIONS
Motoring and Dynamic Brake Prohibited.
ALARM BELL
As long as Loco moves and for 30 Seconds minimum.
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
No auto recovery.
RECOVERY
PROBABLE
1. There may be a physical locked axle.
CAUSES
2. Traction Motor speed sensor is faulty.
3. The speed signal gear assembly worked out from the Traction Motor
Armature shaft.
FAULT
1. If there is physically locked axle, act according to Rail Road rules
ISOLATION
and regulations.
2. If the axle is not locked physically,
A. Reset the fault manually. Set the display mode to ‘Wheel Slip
Display Mode’ under Display Menu. Open the notch to 1 in
motoring and slowly release the brakes.
B. Observe the individual Traction Motor speeds and currents on
the display.
C. If the currents of all Traction Motor are with in limits, and speed
of Traction Motor No.6 is zero / less, MEP-660 is not getting
proper speed signal from Traction Motor No.6.
D. Stop the locomotive and
a) Check for any cable disconnection in the No.6 Traction Motor
Armature speed sensor circuit. Replace / reconnect the cable.
b) Check for any dislocation of the speed sensor on the end
shield of Traction Motor 6. Reconnect the sensor properly.
c) Remove the end shield of Traction motor No.6 and check for
dislocation of sensor gear on the shaft. If so replace the Tr.
Motor / refit the sensor gear properly.
17
PARAMETER
DESCRIPTION
FAULT CODE
1015
FAULT MESSAGE
Loco over speed. Move Master Controller Handle to IDLE
RESTRICTIONS
Motoring Prohibited.
ALARM BELL
30 Seconds.
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Autometic when loco speed is below the set limit and Master Handle is
RECOVERY
brought to IDLE.
PROBABLE
Locomotive speed is high.
CAUSES
FAULT
Reduce the notch and work to maintain the locomotive speed with in
ISOLATION
the set limit.
18
PARAMETER
DESCRIPTION
FAULT CODE
1016
FAULT MESSAGE
Alternator Field Circuit Open FAULT
RESTRICTIONS
Nil
ALARM BELL
30 Seconds.
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Autometic when Traction Alternator Field circuit is closed.
RECOVERY
PROBABLE
1.
Internal fault with Exciter.
CAUSES
2.
Disconnected cable at Exciter terminals.
3.
Disconnected cables at the Terminal board.
4.
Poor contact of GF contactor main tips / the main tips may not be
closing due to mechanical obstruction in the contactor assembly.
5.
Bad contact between Traction Alternator brushes and slip rings.
6.
Tr. Alternator field showing high resistance / Open circuited.
FAULT
1.
Set the Display mode to ‘Excitation’ through Display menu.
ISOLATION
2.
Apply locomotive brakes. Keep Reverser Hnadle in neutral position.
Switch ON both the GF switches and open notch to 1.
3.
Observe Exciter Field current (EXFI) and Exciter PWM output
(EXPWM). Exciter Field current should be around 2.4 Amps and
Exciter PWM output should be around 4000.
4.
Measure Exciter output Voltage on Exciter terminals LA and LAA.
A. If the Exciter output Voltage is less than 10 Volts then
a) Exciter is defective. Replace the Exciter.
B. If Exciter Voltage is more than the minimum value, then check
the Voltage on terminals 61L and 44 at the backside TB.
C. If the voltage is zero, then
a) The cables 61L or / and cable 44 are having high resistance
or open circuited. Identify and repalce the cable.
D. If the Voltage is equal to Exciter Voltage, then check the voltage
on terminals 44 at backside TB and 61L at GF contactor.
E. If the voltage is zero, then
a) The cable 61L from backside TB to GF contactor is having
high resistance or open circuited. Check and replace the
cable.
F. If the Voltage is equal to the Exciter Voltage, then check the
voltage on the terminals 44 at backside TB and 61K at GF
contactor. (Ensure that the GF contactor is in picked up
condition and AFR connectons are removed.)
G. With GF contactor closed and the Voltage is zero, then
a) GF contactor main tips are not closing properly. Remove the
archute and exmine for any mechanical obstruction / foreign
materials inside the contactor. Remove and clean the
contactors. If the contactor itself is defective, replace the
contactors.
H. If the Voltage is equal to Exciter Voltage, then check the Voltage
on terminals 61K and 44 at backside TB.
I. If the Voltage is zero, then
a) The cable 61K from GF contactor to backside TB is having
high resistance or open circuited. Check and replace the
19
cable.
J. If the Voltage is equal to the Exciter Voltage, then check the
Voltage on the Traction Alternator brush arms.
Extreme care should be taken while measuring the Voltage at
the Traction Alternator slip rings. It is highly recommended to
shut down the engine and connect measuring leads at the brush
arms. After connecting the leads to meter, set up the
locomotive as per the Sl. No. 1 to 3.
K. If the Voltage is zero, then
a) The cables AF1 and AF2 connecting Traction Alternator brush
arms and back side TB are having high resistance / open
circuit. Check and replace the cables.
L. If the Voltage is equal to Exciter Voltage, then
a) The problem is inside the Traction Alternator. Check the
following and fix up the problem
1) Check up the brush arms and brushes for any open
circuit / burnt sysmptoms.
2) Check up for any discoloration of slip rings that can
cause bad contact between brushes and slip rings.
3) Check up any burnt / fused slip ring connections.
4) Check for any open circuit in the Traction Alternator Field
circuit.
5. If every thing is nrmal, measure the Traction Alternator Field
current with a clip on DC ammeter clipped to any one of the
Traction Alternator Field cables.
6. If the meter indicates current and the value of EXAI on the display
is less / zero, then
A. The communication cable between the current sensor EXAI and
MEP-660 is bad. Check the continuity of the cable and if
necessary replace the cable.
B. If the cable is good, then the sensor is bad. Replace the sensor.
7. Return the throttle to IDLE.
20
PARAMETER
DESCRIPTION
FAULT CODE
1017
FAULT MESSAGE
Exciter Field Circuit Open / Short Fault.
RESTRICTIONS
Nil
ALARM BELL
30 Seconds.
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Autometic when Exciter Filed Current found normal.
RECOVERY
PROBABLE
1.
Defective wiring (Open circuited at Ex. Gen. TB or back side TB.)
CAUSES
2.
Defective Current Sensor.
3.
Bad interlocks of EXPR. (61F-61FF, 61G-61GA)
4.
Defective Ex. Gen. (Field is internally open circuited.)
5.
Defective MPWM2 card.
FAULT
1.
Set the display mode to ‘Excitation’ under ‘Display Mode’ menu.
ISOLATION
2.
Move the master handle to Notch 1, by applying brakes.
3.
If EPWM is more than 0 and EXFI is zero,
4.
Check voltage between wire 61F (at EXPR 2 interlock) and
locomotive 4-wire.
A. If Voltage is zero, check 71-wire loop coming to FCP. If it is
open, identify and replace.
B. If the voltage is 72V, check 4-wire loop coming to FCP from the
locomotive 4-wire.
C. If voltage is still 0, replace the FCP.
D. If voltage is greater than 30V.
5.
Check voltage between wire 61FF (at EXPR 2 interlock) and
locomotive 4-wire.
A. If the voltage between wire 61FF at FCP and locomotive 4-wire
is 0, check the EXPR 2 interlock.
B. If the voltage between wire 61FF at FCP and locomotive 4-wire
is greater than 30V, check the current sensor proper polarity.
Identify and replace the sensor.
6.
Check voltage between wir LSS (E) at Exciter field winding and
locomotive 4-wire.
A. If Voltage is 0, check the Exciter field winding resistance with a
multimeter. If it is open circuited replace the Exciter Gen.
B. If Voltage is greater than 30V, check the EXPR 3 interlock
condition.
7.
If still EXFI is showing zero, MPWM2 card might be defective.
Replace the card check.
21
PARAMETER
DESCRIPTION
FAULT CODE
1018
FAULT MESSAGE
GF Stuck Open. Run Auto/Manual Test
Can’t Power up: Electrical Control Problem
RESTRICTIONS
Nil
ALARM BELL
30 Seconds.
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Autometic when GF contactorfound closed.
RECOVERY
PROBABLE
1.
Defective GF contactor.
CAUSES
2.
Wiring fault from MEP-660 to GF contactor coil.
3.
Positive supply to GF contactor operating coil is missing.
FAULT
1.
Set the Display to ‘Manual Tests for Ouputs’ mode through Test
ISOLATION
Mode Menu and satisfy the initial conditions required to run manual
test as prompted on the display unit.
2.
Press 13 + ‘Enter Key’+1 to energise GF contactor.
3.
If GF contactor energises, then
A. Check up for proper closing of main contact tips and Auxilary
contacts.
B. The status of GF Aux. Contact 1 can be checked through 0
number Green and Yellow LEDs on digital input card MDIP-16 in
slot 11.
C. The status of GF Aux. Contact 2 can be checked through 1
numbered Green and Yellow LEDs on Digital Input card MDIP-16
in slot No. 12.
D. All the 4 LEDs should glow.
4.
Press ‘0’ key to deenegise the GF contactor.
A. All the 4 LEDs in both the digital input cards should be OFF.
B. If LEDs are not as per the sequence and remains always OFF,
then
a) Check voltage on wire No. 51 at the GF contactor auxiliary
contacts 1 and 2 with respect to wire No. 4
b) If the voltage is zero, then
1) Wiring loop of wire No. 51 is open circuited. Identify the
open circuit and ensure supply at the terminal 51 on Aux.
Contact of GF contactor is available.
c) If Voltage is greater than 65V, then
1) Check voltage at the wire terminals FCD and FCE on
Auxiliary contacts of GF contactor.
2) If Voltage is zero, then the Aux. Contacts of GF
contactors are bad. Check, clean and adjust the auxiliary
contacts. If necessary replace them.
3) If voltage is greater than 65V, then wiring between GF
contactor and MEP-660 is open circuited. Identy and
replace the cable.
C. If the GF contactor is not energizing as per the test sequence,
then
a) Connect Voltmeter across the operating coil of the GF
contactor and switch ON GF contactor by pressing 1 key.
b) If the Voltage is more than 65V, then
22
1) The GF contactor-operating coil is open circuited
internally or there may be a physical obstruction in the
contactor operation. Check and replace the GF contactor
if necessary.
c) If the voltage is zero, then
d) Check the voltage on coil terminal wire No. 13 and 4.
1) If Voltage is zero, then wire loop 13 connected to GF
operating coil is open circuited. Identify and replace.
2) If the voltage is more than 65V, then negative feed is not
coming to GF contactor oerating coil.
3) This may be due to cable fault or digtal ouput card
defective.
4) Check the cable continuity from MEP-660 to GF contactor
coil. If necessary replace the cable.
5) If continuity is available, replace the digital ouput card.
And check the operations of GF contactor.
23
PARAMETER
DESCRIPTION
FAULT CODE
1019
FAULT MESSAGE
CEB Breaker OFF.
RESTRICTIONS
No restrictions, only indication.
ALARM BELL
Continuous ON
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when CEB breaker is switched ON.
RECOVERY
PROBABLE
1. Crank Case Exahauster Motor is not getting supply due to CCEB
CAUSES
tripped or switched OFF.
2. Crankcase Exhauster Breaker Feed Back (CEB FB) status is low as
sensed by MEP-660.
FAULT
1. If Breaker is in tripped/OFF position, reset/switch ON the breaker.
ISOLATION
2. The high level status of the Crankcase Exhauster Breaker Feed Back
is indicated by 7 Numbered Green and Yellow LEDs on digital input
card MDIP-16 in slot No. 13.
3. With CEB in ON position, CCEM fail indication LEDs on both control
desks should be OFF. Both 7 numbered Green and Yellow LEDs on
the Digital Input card in slot 13 should be ON.
A. If the indications LEDs on both the control desks are ON, then
the breaker is defective and the CCEM is not working. Replace
the breaker.
B. If 7 numbered Green LED is OFF on digital input card in slot 13,
then wiring from CEB breaker to MEP-660 open circuited. Check
and replace wiring.
C. If 7-numberED Green LED is ON and 7-numbered Yellow LED is
OFF, the digital input card in slot 13 is defective. Replace and
check.
24
PARAMETER
DESCRIPTION
FAULT CODE
1020
FAULT MESSAGE
Rectifier Diodes HOT.
RESTRICTIONS
Engine RPM and Power Limited to 4th Notch.
ALARM BELL
30 Sec.
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when thermostate switch in the power rectifier closes.
RECOVERY
PROBABLE
1. The thermostate switch in the power rectifier unit is showing open
CAUSES
circuit due to blower might have failed resulting in high temperature
or the thermostate contact itself is open circuited permanently.
Note: Probably this fault message will be logged in locomotives
equipped with self-cooled rectifiers and having thermal protection for
the diodes.
FAULT
The thermostate switch is a normally closed interlock. 8 numbered
ISOLATION
Green and Yellow LEDs on the digital input card MDIP-16 in slot 12
indicate the status of this interlock ‘RECT HOT’. Both Green and Yellow
LEDs should be ON in normal working condition of the loco. Reset the
message and check the status of both the LEDs
1.
If both Green and Yellow LEDs are not ON, then
A.
The power rectifier blower might have failed and the diodes
might have heated up. Check up proper working of rectifier
blower. If necessary replace the blower.
If blower had failed, please ensure that no diodes/fuses
are burnt out inside rectifier unit before releasing the
locomotive.
B.
If the rectifier is cool and blower is working normal, then check
voltage at the rectifier terminal board on wire terminal No.
DLK1.
a) If the voltage is zero, check voltage on wire terminal 51.
1) If the voltage is zero, then 51-wire loop from CP/TB to
rectifier TB is open circuited. Check and replace.
2) If the voltage is > 65V, the thermostae switch is
defective or internal wiring is burnt. Check up with
rectifier and attend.
C.
If the voltage is > 65V, check voltage at terminal DLK1 on
backside TB.
a) If the voltage is zero, then the wire loop DLK1 from backside
TB to Rectifier TB is open circuited. Check and replace.
D.
If the voltage is > 65V and
a) The 8 numbered Green LED on the Digital Input card in slot
12 is not ON, then the wire loop from backside TB to MEP-
660 is open circuited. Check and replace.
b) Green LED is ON and 8 numbered Yellow LED on the digital
input card in slot 12 is OFF, then the digital card is defective.
Check and replace.
25
PARAMETER
DESCRIPTION
FAULT CODE
1021
FAULT MESSAGE
Rectifier Blower Failed or RBB Breaker OFF.
RESTRICTIONS
Engine RPM and Power Limited to 4th Notch.
ALARM BELL
30 Sec.
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Autometic when Rectifier blower Breaker is switched ON.
RECOVERY
PROBABLE
1. The Rectifier Blower Breaker is in switched OFF / tripped position.
CAUSES
Note: Probably this fault message will be logged in locomotives
equipped with self-cooled rectifiers and having thermal protection for
the diodes.
FAULT
1. If the Rectifier Blower Breaker is in switched OFF / Tripped position,
ISOLATION
switch ON / reset the breaker. 9 numbered Green and Yellow LEDs
on the digital input card in slot 12 indicate the status of the Rctifier
Blower Breaker. With RBB in ON position, Both LEDs should be ON.
2. If the Green LED is not ON, then
A. Check supply at wire terminals 50AA and 4 on the backside TB.
B. If the voltage is zero, then the breaker is defective or wire 55A
between RRB to backside TB is open circuited. Check up and
replace.
C. If voltage is > 65V, then rectifier blower should work. If rectifier
blower is not working, check up the voltage at same wire
terminals on rectifier TB.
a) If voltage is zero, then the wire 55A or 4 wire between
backside TB and Rectifier TB is open circuited. Check and
replace.
b) If Voltage is > 65 V, then check up with blower / Rectifier
wiring.
D. If the 9 numbered Green LED is OFF, then the wire No. RBBFB
from backside TB and MEP-660 is open circuited. Check up and
replace the wires.
E. If the Green LED and 9 numbered Yellow LED on Digital input
card in slot 12 is OFF, then digital input card is defective. Check
and replace.
26
PARAMETER
DESCRIPTION
FAULT CODE
1022
FAULT MESSAGE
Wrong Command: TL6 & TL17/TL23 High.
Can’t Change Mode
RESTRICTIONS
Motoring and Dynamic Brake Prohibited
ALARM BELL
30 Sec.
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Autometic when master handle is brought to IDLE.
RECOVERY
PROBABLE
Most probably this fault is an intermittent fault logged. The fault might
CAUSES
have recovered by the time it is tried to find out the reason. However if
the fault is continuously logging, it may be due to
1. Non-working control stand might not be in IDLE position.
2. Wrong interlocking of any one of the master controllers.
3. Locomotive is being controlled from two locomotives
simultaneously.
4. Wrong feed back of train line wires through MU cables.
5. Any wiring fault causing simultaneous energisation TL6 along with
TL17 or TL23 while operating Master Handle.
FAULT
If the fault is cleared check the operation of the master controller
ISOLATION
interlocks as follows:
1. Shut down the engine. Set the display mode to “Manual Test for
Inputs” under test menu. When prompted for input number Enter
07 + Enter Key to view the status of the Train Line wire TL6 on the
display.
2. Set the control stand to motoring mode. Operate the Master Handle
between IDLE to 1st notch two to three times. Observe the status of
the TL6 on the display. The staus of TL6 should toggle as per the
master handle position. Bring back the master handle to IDLE.
3. Press
‘down arrow’ key + 09 + ‘Enter’ key to check the status of
the train line wire TL17.
4. Set the Master Handle to Dynamic Brake set up position. Operate
the Master Handle between IDLE to OFF positions two to three
times. Observe the status of Train Line wire TL17 while moving the
Master Handle and ensure it is as per Master Handle position.
5. Press ‘down arrow’ key +10 + ‘Enter’ key to check the status of the
train line wire TL23.
6. Move the Master Handle between OFF position to Dynamic brake
position for two to three times and observe the status of TL23 wire.
It should follow the Master Handle movement.
7. Repeat the steps from 2 to 7 on the other control stand. This
ensures proper operation of the Master Handle interlocks.
If the fault is not cleared and continuously logging:
1. Remove the MU jumper cables to isolate wrong feed through MU
jumper cables.
2. If the fault is not rectified, keep both Master Handles in IDLE
position.
3. Check voltage on Train Line Wires TL6, TL17 and TL23 at the
27
backside TB.
4. If voltage is available on any of the above wires, Disconnect the
bunch wires and identify which lead is getting wrong supply and
rectify.
5. If no voltages are found on the above wires,
A. Operate Master Handle to Motoring position (Notch 1) on control
stand 1. Check voltages on TL17 and TL23.
a) If voltage is >35V on any of the two wires, then repeat the
step 4.
B. Operate the Master Handle to OFF position (Dynamic Brake set
up). Check Voltage on TL6.
a) If Voltage is >35V on TL6, then repeat step 4.
C. Operate the Master Handle to Dy. Brake position. Check Voltage
on TL6.
a) If voltage is > 35V on TL6, then repeat step 4.
D. Move the Master Handle to IDLE position.
E. Rpeat checks from A to D on control stand 2.
28
PARAMETER
DESCRIPTION
FAULT CODE
1023
FAULT MESSAGE
BKT Stuck in Braking. Run Auto/Manual Test.
Can’t Motor: Electrical Control Problem
RESTRICTIONS
Motoring Prohibited
ALARM BELL
30 Sec.
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Autometic when BKT stuck is cleared
RECOVERY
PROBABLE
1.
Control Air pressure is less or zero.
CAUSES
2.
Foreign particles fallen in Paul assembly.
3.
BKT motoring side magnet valve is defective.
4.
Air leaking from the Air cylinder gasket.
5.
Air hose connection to magnet valve given up.
FAULT
1.
Check control air pressure in the nose compartment. It should be
ISOLATION
5kg/Cm.2.
A. If it is less adjust the pressure.
B. If it is zero, check and attend air brake system.
2.
Operate BKT manually with ‘L’ rod.
A. If BKT is not operating manually, then
a) Inspect Paul assembly for any foreign particles inside the
Rack and pinion teeth. Check and attend.
b) Inspect other operatig mechanism for any disorders or
broken iolite bushes etc. Replace wherever necessary.
c) Check for any main contacts welding. Inspect and replace if
necessary.
3.
If BKT is operating manually, and control air pressure is 5 Kg/Cm2
operate the BKT through magnetvalves by pressing manual levers /
armature plates on both Motoring and Braking side magnetvalves.
A. If BKT is not operating, then
a) Check which magnet valve is defective and replace.
b) Check for any air leakages through air engine gaskets and
replace the gaskets.
c) Check for any damged piston buckets and replace.
4.
If BKT is operating through magnetvalves, set up the display mode
to “Manual Tests for outputs” under Test Mode menu by pressing
the following keys.
5.
‘Menu’ + 3 + (Pass code) + 3 + ‘Enter’ + 09 + ‘Enter’ + 1 to
operate magnet valve of BKT motoring side.
6.
If the BKT is not operated to motoring side, then
A. Check the voltage at the operating coil of BKT motoring side
magnet valve.
B. If the Voltage is > 65V, then the operating coil is open circuited
internally. Replace amgnet valve.
C. If the Voltage is zero, check the voltage between wire terminal 6
on the BKT motoring magnet valve and 4 wire.
D. If the voltage is zero, 6 wire loop coming to BKT motoring side
magnet valve is open circuited. Check and replace.
E. If voltage is > 65V, then positive supply is available but
negative supply through MEP-660 is missing.
29
a) Check up wire continuity of BKTM wire between BKT
motoring side magnet valve coil and backside TB. Replace if
open circuited.
b) Check up wire continuity of BKTMCL from backside TB and
MEP-660. Replace if open circuited.
7. If BKT is operated to motoring side, press the following keys in the
same sequence on the display unit to operate BKT to braking side.
0 + ‘Down Arrow’ + 10 + ‘Enter’ + 1.
8. BKT should move to Braking side. Press 0 + ‘Menu’ +’Menu’ + 5
keys to turn the display to normal mode. Reset the fault and release
the loco.
30
PARAMETER
DESCRIPTION
FAULT CODE
1024
FAULT MESSAGE
BKT-M Aux Contact ckt. Open. Run Auto/Manual Test.
Can’t Motor: Electrical Control Problem.
RESTRICTIONS
Motoring Prohibited
ALARM BELL
30 Sec.
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Autometic when BKT-M Aux. Contact circuit closes.
RECOVERY
PROBABLE
1. Wiring faulty causing low status level of BKT-M feed back.
CAUSES
2. BKT Interlock
FAULT
13 & 14 numbered Green LEDs on the digital input card MDIP-16 in slot
ISOLATION
10 indicate the status of BKT position in the following pattern.
BKT position
Green LED - 13
Green LED - 14
BKT in Motoring Position
ON
OFF
BKT in Dynamic Brake Position
OFF
ON
1.
Check BKT Aux. Contactacts for any dislocation of contacts /
disconnected wires. In any found rectify or replace the Aux.
Contacts if necessary. Ensure proper closing of Aux. Contacts both
in motoring and dynamic brake position. Reset the message.
2.
Ensure control air pressure is 5 Kg/Cm2. Set the display mode to
“Manual Tests for outputs” under Test Mode menu by pressing the
following keys in the same sequence.
‘Menu’ + 3 + (Pass code) + 3
+ ‘Enter’ + 09 + ‘Enter’ + 1 to operate magnet valve of BKT
motoring side.
3.
BKT is operated to motoring side. Ensure the aux. Contacts are
operated and closing properly. Check the status of Green LEDs on
the Digital Input card in slot 10.
4.
If Green LED-13 is not ON, then
A. Check the supply between wire terminal 51 at the common
terminal of the Auxiliary contacts of BKT and wire 4.
a) If the voltage is zero, then wire 51-loop open circuited.
Check and replace.
b) If voltage is > 65 V, then check the voltage between Aux.
Contact BKTM and 4.
c) If voltage is zero, then the Aux. Contact is bad. Check and
clean. If necessary replace.
d) If the Voltage is > 65V, then check the voltage between wire
terminals BKTM and 4 at the backside TB.
e) If voltage is zero, then the wire BKTB between Aux. Contact
and backside TB is open circuited. Check and replace.
f) If the voltage is more than 65V, then the wire BKTMFB
bwteeen backside TB and MEP-660 open circuited. Check
and replace.
5.
Press the keys listed with in brakets on the display unit in the same
sequence (0 + ‘Menu’ +’Menu’ + 5). The display returns to normal
mode. Reset the fault and release the loco.
31
PARAMETER
DESCRIPTION
FAULT CODE
1025
FAULT MESSAGE
Alternator Output Voltage High FAULT
RESTRICTIONS
Motoring and Dynamic Brake Prohibited
ALARM BELL
30 Sec.
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Autometic when Traction Alternator Voltage is reduced below 100V and
RECOVERY
Master Handle is brought to IDLE. Auto recovery is permitted for 3
times in one hour. There after Manual reset is required.
PROBABLE
1.
Momentarily the Traction Alternator Voltage might have shooted up
CAUSES
2.
Some wiring short circuit has occurred in FCP and Exciter field
circuit.
FAULT
1.
Connect a DC voltameter 0 to 1000V range between GA11 and GA2.
ISOLATION
2.
Crank the engine and ensure loco brakes are applied.
3.
Press the following keys on the display unit in the same sequence to
set the display mode to “Load Box Test” under Test mode menu.
‘Menu’ + 3 + (pass code) + 1 + 1 +’Enter’.
4.
Move the master Hnadle to notch 1 with both GF switches are ON.
5.
Observe the Traction Alternator Voltage displayed on the display
unit under TA Volts.
6.
Compare this reading with the voltage reading on the external
voltmeter.
7.
If the Voltage on the display is abnormally higher than the
voltmeter reading, then
A. The voltage sensor is faulty. Check up the cable connections on
the Tr. Alternator Voltage sensor TAV. If necessary replace.
8.
If both the voltages are same and are abnormally high as compared
to 1st notch no load voltage, then move the Master Handle to IDLE.
A. Check wiring connections at FCP1 (EFR1, 2, 3 and 4). Check for
any disconnected / short-circuited / over heated wire terminals
at the FCP1. Check and rectify.
B. Check wiring connections at wire terminals 61G and 61GA on
the backside TB for any disconnected / short-circuited / over
heated terminals. Check and rectify.
9.
If both the voltages are equal and with in limits, then the fault is a
transient.
32
PARAMETER
DESCRIPTION
FAULT CODE
1026
FAULT MESSAGE
Alternator Output Current High FAULT in DB
RESTRICTIONS
Motoring and Dynamic Brake Prohibited
ALARM BELL
30 Sec.
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Autometic when Traction Alternator current is reduced below 100A and
RECOVERY
Master Handle is brought to IDLE. Auto fault recovery is permitted for 3
times in one hour. There after Manual reset is required.
PROBABLE
1. Defective FCP
CAUSES
2. Any foreign materials in between REV or BKT contacts cuasing high
current to flow
3. Defective current sensor
FAULT
1. Check for any disconnected / over heated wires at the FCP. Identify
ISOLATION
and reconnect the wires.
2. Check BKT and REV contacts. Remove any foreign materials if
avialble.
3. Apply loco brakes and ensure that the brakes are physically applied.
Take all precausions required to move a locomotive.
4. Set up the locomotive to motoring and move the master handle to
notch 1.
5. If the current indicated on the display is with in limits of 1st notch
current, then the fault is transient.
6. If the current indicated on the display is abnormally high with out
any jerk, then the current sensor is faulty. Check and replace the
Traction alternator current sensor.
7. If the current idicated is abnormally high with heavy jerk, PWM
output card is defect.
8. Replace the card and check once again.
33
PARAMETER
DESCRIPTION
FAULT CODE
1027
FAULT MESSAGE
Alternator Field Over Current fault.
RESTRICTIONS
Motoring and Dynamic Brake Prohibited
ALARM BELL
30 Sec.
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Traction Alternator field current is reduced below 20A
RECOVERY
and Master Handle is brought to IDLE. Auto fault recovery is permitted
for 3 times in one hour. There after Manual reset is required.
PROBABLE
1. Defective FCP
CAUSES
2. Defective Exciter
3. Exciter field drive circuit defect
FAULT
1. Check for any disconnected / over heated wires at the FCP. Identify
ISOLATION
and reconnect the wires.
2. Check for any short circuit between armature and field circuit due
to either internally or externally like terminals touching to
inspection cover. If found rectify and remove short circuit.
3. Apply loco brakes and ensure that the brakes are physically
applied. Take all precausions required to move a locomotive.
4. Set the display mode to excitation mode.
5. Set up the locomotive to motoring and move the master handle to
notch 1.
6. Observe the exciter field current and exciter armature current on
the display unit. If both the values are with in the limits, then the
fault is transient.
34
PARAMETER
DESCRIPTION
FAULT CODE
1028
FAULT MESSAGE
Exciter Field Over Current Fault.
RESTRICTIONS
Motoring and Dynamic Brake Prohibited
ALARM BELL
30 Sec.
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Autometic when exciter field current is reduced below 0.5A and Master
RECOVERY
Handle is brought to IDLE. Auto fault recovery is permitted for 3 times
in one hour. There after Manual reset is required.
PROBABLE
1. Defective / Wrong connection at FCP
CAUSES
2. Defective Exciter (Field internally shorted)
3. Any one-diode short circuit in the rectifier making the system to
pump more current in the exciter field.
4. One of the alternator phase is not generating any voltage.
5. Defective EXFI current sensor
6. Defective MAIP8_EP card.
FAULT
1. Check for any disconnected / over heated wires at the FCP. Identify
ISOLATION
and reconnect the wires correctly.
2. Check for any short circuit between exciter terminals either
internally or externally like terminals touching to inspection cover.
If found rectify and remove short circuit.
3. Check backside Terminal board for any disconnected exciter field
wires and touching to nearby positive wires. Identify and isolate
them.
4. Check and ensure that there are no short-circuited diodes in the
rectifier.
5. Measure the Exciter field current with an ammeter and compare
with the displayed EXFI value.
6. If the displayed EXFI value is greater than the actual current:
A. EXFI current sensor might be defective.
B. MAIP8_EP card might be defective.
35
PARAMETER
DESCRIPTION
FAULT CODE
1029
FAULT MESSAGE
Cranking Contactor CK Stuck Closed.
RESTRICTIONS
Motoring Prohibited. Dynamic Brake Prohibited.
ALARM BELL
Continuous
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be
generated again.
FAULT RECOVERY
Automatic on releasing of stuck condition as sensed through
Auxiliary contacts of CK1/CK2/CK3.
PROBABLE
1.
CK1/CK2/CK3 contactor main tips are welded.
CAUSES
2.
Defective wiring.
(Wiring from these auxiliary interlocks
disconnected)
3.
Defective MDIP16 card.
FAULT ISOLATION
1.
Check the status of CK1/CK2/CK3 feed back LEDs on the
MDIP_16 card in slot 10 and green LEDs numbered 0,1,2.
2.
Which ever the LED is not glowing, corresponding cranking
contactor is welded or interlock is bad.
3.
LED 0 for CK1, LED 1 for CK2 and LED 2 for CK3. on MDIP16
card in slot 10.
4.
Check for any weld condition of the contactors. Release the
main tips with a wooden stick.
5.
If there is no welding of contactors, check and clean the
concerned N/C interlocks of that particular contactor.
6.
If interlock is good, check the voltage between CK#FB and
locomotive 4 wire.
7.
If the Voltage is more than 65V,
A. Check the slackness of the connector of cable ID: AU at
control unit. If slack press the connector towards the control
unit and tighten the connector.
B. If connector is tight and still the green LED is not glowing
a) MDIP16 card might be defective.
36
PARAMETER
DESCRIPTION
FAULT CODE
1030
FAULT MESSAGE
SLBR / SLBC Contactor Stuck Closed.
RESTRICTIONS
Motoring Prohibited Dynamic Brake Prohibited
ALARM BELL
30 Seconds
RESET LEVEL
Low, Manual
FAULT RECOVERY
Autometic. When stuck condition is released as sensed through
auxiliary contacts of SLBC1, SLBC2, SLBC3 and SLBC4.
Manual fault clearing through keyboard on the display unit. (If the
fault condition is present when cleared manually, the fault will be
generated again.
PROBABLE
1. Defective SLBR relay. (Permanently ON)
CAUSES
2. Defective MLSD16 card (slot 15)
3. Welded SLBC1/SLBC2/SLBC3/SLBC4
4. Defective wiring. (SLBC FB wire is getting +ve supply)
5. Defective MDIP16 card (Slot 13)
FAULT ISOLATION
1. Check the status of SLBR relay.
2. If SLBR is in pick up condition:
A. Check the supply voltage at SLBR coil. If voltage is more than
65V, then MLSD16 card in slot 15 is defective. Replace the
card.
B. If the voltage is zero, then the relay is defective. Replace the
relay.
3. If SLBR is in drop out conditio, check status of SLBC contactors.
4. If any SLBC contactor is in pick up position, check the supply at
the magnet valve coil.
A. If the voltage is more than 65V, the SLBR relay is defective or
SLBC wire is getting supply.
B. Replace the SLBR relay or identify the wrong supply to SLBC
contactor.
5. If no SLBC contactors are in pick up condition, check for the
welded interlocks of SLBC auxiliary contacts. If found replace the
Aux. Contacts.
6. If no aux. Contacts of SLBC is welded, check the supply between
SLBC FB wire and wire 4 of locomotive.
A. If voltage is more than 65V, then SLBC FB wire is getting wrong
supply. Identify wrong wiring and rectify.
B. If the voltage is zero, then MDIP16 card in slot No. 13 is
defective. Replace the card.
37
PARAMETER
DESCRIPTION
FAULT CODE
1031
FAULT MESSAGE
Wheel Number 1 Continuously Sliding
RESTRICTIONS
No restrictions. Warning only.
ALARM BELL
As long as Loco moves and for 30 Seconds minimum.
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic on arresting of wheel slide as sensed through TM speed
RECOVERY
sensor.
PROBABLE
1. Brake binding on No.1 wheel resulting in low speed.
CAUSES
2. Defective Speed sensor on TM 1
FAULT
1. If any brake binding is found, clear it as early as possible.
ISOLATION
2. Check for tightness of the speed sensor coupler of TM No.1 and
ensure coupler is tight.
3. Speed sensor gear in the TM No.1 is slack or freely rotating in the
end cup. If found replace the TM.
PARAMETER
DESCRIPTION
FAULT CODE
1032
FAULT MESSAGE
Wheel Number 2 Continuously Sliding
RESTRICTIONS
No restrictions. Warning only.
ALARM BELL
As long as Loco moves and for 30 Seconds minimum.
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic on arresting of wheel slide as sensed through TM speed
RECOVERY
sensor.
PROBABLE
1. Brake binding on No.2 wheel resulting in low speed.
CAUSES
2. Defective Speed sensor on TM 2
FAULT
1. If any brake binding is found, clear it as early as possible.
ISOLATION
2. Check for tightness of the speed sensor coupler of TM No.2 and
ensure coupler is tight.
3. Speed sensor gear in the TM No.2 is slack or freely rotating in the
end cup. If found replace the TM.
38
PARAMETER
DESCRIPTION
FAULT CODE
1033
FAULT MESSAGE
Wheel Number 3 Continuously Sliding
RESTRICTIONS
No restrictions. Warning only.
ALARM BELL
As long as Loco moves and for 30 Seconds minimum.
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic on arresting of wheel slide as sensed through TM speed
RECOVERY
sensor.
PROBABLE
1. Brake binding on No.3 wheel resulting in low speed.
CAUSES
2. Defective Speed sensor on TM 3
FAULT
1. If any brake binding is found, clear it as early as possible.
ISOLATION
2. Check for tightness of the speed sensor coupler of TM No.3 and
ensure coupler is tight.
3. Speed sensor gear in the TM No.3 is slack or freely rotating in the
end cup. If found replace the TM.
PARAMETER
DESCRIPTION
FAULT CODE
1034
FAULT MESSAGE
Wheel Number 4 Continuously Sliding
RESTRICTIONS
No restrictions. Warning only.
ALARM BELL
As long as Loco moves and for 30 Seconds minimum.
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic on arresting of wheel slide as sensed through TM speed
RECOVERY
sensor.
PROBABLE
1. Brake binding on No.4 wheel resulting in low speed.
CAUSES
2. Defective Speed sensor on TM 4
FAULT
1. If any brake binding is found, clear it as early as possible.
ISOLATION
2. Check for tightness of the speed sensor coupler of TM No.4 and
ensure coupler is tight.
3. Speed sensor gear in the TM No.4 is slack or freely rotating in the
end cup. If found replace the TM.
39
PARAMETER
DESCRIPTION
FAULT CODE
1035
FAULT MESSAGE
Wheel Number 5 Continuously Sliding
RESTRICTIONS
No restrictions. Warning only.
ALARM BELL
As long as Loco moves and for 30 Seconds minimum.
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic on arresting of wheel slide as sensed through TM speed
RECOVERY
sensor.
PROBABLE
1. Brake binding on No.5 wheel resulting in low speed.
CAUSES
2. Defective Speed sensor on TM 5
FAULT
1. If any brake binding is found, clear it as early as possible.
ISOLATION
2. Check for tightness of the speed sensor coupler of TM No.5 and
ensure coupler is tight.
3. Speed sensor gear in the TM No.5 is slack or freely rotating in the
end cup. If found replace the TM.
PARAMETER
DESCRIPTION
FAULT CODE
1036
FAULT MESSAGE
Wheel Number 6 Continuously Sliding
RESTRICTIONS
No restrictions. Warning only.
ALARM BELL
As long as Loco moves and for 30 Seconds minimum.
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic on arresting of wheel slide as sensed through TM speed
RECOVERY
sensor.
PROBABLE
1. Brake binding on No.6 wheel resulting in low speed.
CAUSES
2. Defective Speed sensor on TM 6.
FAULT
1. If any brake binding is found, clear it as early as possible.
ISOLATION
2. Check for tightness of the speed sensor coupler of TM No.6 and
ensure coupler is tight.
3. Speed sensor gear in the TM No.6 is slack or freely rotating in the
end cup. If found replace the TM.
40
PARAMETER
DESCRIPTION
FAULT CODE
1037
FAULT MESSAGE
Traction Motor 1 High Current While Motoring.
RESTRICTIONS
Tr. Motor No.1 is cutout and Dynamic brake is Prohibited.
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Traction Motor current is reduced and Master
RECOVERY
Controller Handle is brought to Idle. Automatic Fault Reset is permitted
for maximum 3 times in an hour, after which manual clearing is
required.
PROBABLE
1. Tr. Motor / car body cables grounded / short-circuited.
CAUSES
2. No.1 wheel might be locked physically or brakes are jammed.
3. Foreign materials fallen in between BKT/REV contacts.
FAULT
1. Set the locomotive operation to motoring. Take necessary
ISOLATION
precautions to move the locomotive.
2. Set the display mode to wheel slip.
3. Open 1st notch and observe the traction motor currents. If all the
traction motor currents are equal, there could be momentary short
circuit in the traction motor / car body cables while on run.
A. Check up the traction motor cables for any damage of insulation
or pressed cables.
4. If the current in traction motor No.1 is showing high,
A. Check for free movement of axle 1 with out any brake binding.
If necessary attend and make the wheel movement free.
B. Observe for any foreign materials in between BKT and REV
contacts. If found, remove them and attend to BKT/REV
contacts.
5. If the wheel is rotating freely and BKT / REV contacts are free from
foreign materials and still traction motor current is showing high as
compared to other motors, the TM1AI sensor might be defective.
Replace the sensor and check up.
41
PARAMETER
DESCRIPTION
FAULT CODE
1038
FAULT MESSAGE
Traction Motor 2 High Current While Motoring.
RESTRICTIONS
Tr. Motor No.2 is cutout and Dynamic brake is Prohibited.
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Traction Motor current is reduced and Master
RECOVERY
Controller Handle is brought to Idle. Automatic Fault Reset is permitted
for maximum 3 times in an hour, after which manual clearing is
required.
PROBABLE
1. Tr. Motor / car body cables grounded / short-circuited.
CAUSES
2. No.2 wheel might be locked physically or brakes are jammed.
3. Foreign materials fallen in between BKT/REV contacts.
FAULT
1. Set the locomotive operation to motoring. Take necessary
ISOLATION
precautions to move the locomotive.
2. Set the display mode to wheel slip.
3. Open 1st notch and observe the traction motor currents. If all the
traction motor currents are equal, there could be momentary short
circuit in the traction motor / car body cables while on run.
A. Check up the traction motor cables for any damage of insulation
or pressed cables.
4. If the current in traction motor No.2 is showing high,
A. Check for free movement of axle 2 with out any brake binding.
If necessary attend and make the wheel movement free.
B. Observe for any foreign materials in between BKT and REV
contacts. If found, remove them and attend to BKT/REV
contacts.
5. If the wheel is rotating freely and BKT / REV contacts are free from
foreign materials and still traction motor current is showing high as
compared to other motors, the TM2AI sensor might be defective.
Replace the sensor and check up.
42
PARAMETER
DESCRIPTION
FAULT CODE
1039
FAULT MESSAGE
Traction Motor 3 High Current While Motoring.
RESTRICTIONS
Tr. Motor No.3 is cutout and Dynamic brake is Prohibited.
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Traction Motor current is reduced and Master
RECOVERY
Controller Handle is brought to Idle. Automatic Fault Reset is permitted
for maximum 3 times in an hour, after which manual clearing is
required.
PROBABLE
1. Tr. Motor / car body cables grounded / short-circuited.
CAUSES
2. No.1 wheel might be locked physically or brakes are jammed.
3. Foreign materials fallen in between BKT/REV contacts.
FAULT
1. Set the locomotive operation to motoring. Take necessary
ISOLATION
precautions to move the locomotive.
2. Set the display mode to wheel slip.
3. Open 1st notch and observe the traction motor currents. If all the
traction motor currents are equal, there could be momentary short
circuit in the traction motor / car body cables while on run.
A. Check up the traction motor cables for any damage of insulation
or pressed cables.
4. If the current in traction motor No.3 is showing high,
A. Check for free movement of axle 3 with out any brake binding.
If necessary attend and make the wheel movement free.
B. Observe for any foreign materials in between BKT and REV
contacts. If found, remove them and attend to BKT/REV
contacts.
5. If the wheel is rotating freely and BKT / REV contacts are free from
foreign materials and still traction motor current is showing high as
compared to other motors, the TM3AI sensor might be defective.
Replace the sensor and check up.
43
PARAMETER
DESCRIPTION
FAULT CODE
1040
FAULT MESSAGE
Traction Motor 4 High Current While Motoring.
RESTRICTIONS
Tr. Motor No.4 is cutout and Dynamic brake is Prohibited.
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Traction Motor current is reduced and Master
RECOVERY
Controller Handle is brought to Idle. Automatic Fault Reset is permitted
for maximum 3 times in an hour, after which manual clearing is
required.
PROBABLE
1. Tr. Motor / car body cables grounded / short-circuited.
CAUSES
2. No.4 wheel might be locked physically or brakes are jammed.
3. Foreign materials fallen in between BKT/REV contacts.
FAULT
1. Set the locomotive operation to motoring. Take necessary
ISOLATION
precautions to move the locomotive.
2. Set the display mode to wheel slip.
3. Open 1st notch and observe the traction motor currents. If all the
traction motor currents are equal, there could be momentary short
circuit in the traction motor / car body cables while on run.
A. Check up the traction motor cables for any damage of insulation
or pressed cables.
4. If the current in traction motor No.4 is showing high,
A. Check for free movement of axle 4 with out any brake binding.
If necessary attend and make the wheel movement free.
B. Observe for any foreign materials in between BKT and REV
contacts. If found, remove them and attend to BKT/REV
contacts.
5. If the wheel is rotating freely and BKT / REV contacts are free from
foreign materials and still traction motor current is showing high as
compared to other motors, the TM4AI sensor might be defective.
Replace the sensor and check up.
44
PARAMETER
DESCRIPTION
FAULT CODE
1041
FAULT MESSAGE
Traction Motor 5 High Current While Motoring.
RESTRICTIONS
Tr. Motor No.5 is cutout and Dynamic brake is Prohibited.
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Traction Motor current is reduced and Master
RECOVERY
Controller Handle is brought to Idle. Automatic Fault Reset is permitted
for maximum 3 times in an hour, after which manual clearing is
required.
PROBABLE
1. Tr. Motor / car body cables grounded / short-circuited.
CAUSES
2. No.5 wheel might be locked physically or brakes are jammed.
3. Foreign materials fallen in between BKT/REV contacts.
FAULT
1. Set the locomotive operation to motoring. Take necessary
ISOLATION
precautions to move the locomotive.
2. Set the display mode to wheel slip.
3. Open 1st notch and observe the traction motor currents. If all the
traction motor currents are equal, there could be momentary short
circuit in the traction motor / car body cables while on run.
A. Check up the traction motor cables for any damage of insulation
or pressed cables.
4. If the current in traction motor No.5 is showing high,
A. Check for free movement of axle 5 with out any brake binding.
If necessary attend and make the wheel movement free.
B. Observe for any foreign materials in between BKT and REV
contacts. If found, remove them and attend to BKT/REV
contacts.
5. If the wheel is rotating freely and BKT / REV contacts are free from
foreign materials and still traction motor current is showing high as
compared to other motors, the TM5AI sensor might be defective.
Replace the sensor and check up.
45
PARAMETER
DESCRIPTION
FAULT CODE
1042
FAULT MESSAGE
Traction Motor 6 High Current While Motoring.
RESTRICTIONS
Tr. Motor No.6 is cutout and Dynamic brake is Prohibited.
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Traction Motor current is reduced and Master
RECOVERY
Controller Handle is brought to Idle. Automatic Fault Reset is permitted
for maximum 3 times in an hour, after which manual clearing is
required.
PROBABLE
1. Tr. Motor / car body cables grounded / short-circuited.
CAUSES
2. No.6 wheel might be locked physically or brakes are jammed.
3. Foreign materials fallen in between BKT/REV contacts.
FAULT
1. Set the locomotive operation to motoring. Take necessary
ISOLATION
precautions to move the locomotive.
2. Set the display mode to wheel slip.
3. Open 1st notch and observe the traction motor currents. If all the
traction motor currents are equal, there could be momentary short
circuit in the traction motor / car body cables while on run.
A. Check up the traction motor cables for any damage of insulation
or pressed cables.
4. If the current in traction motor No.6 is showing high,
A. Check for free movement of axle 6 with out any brake binding.
If necessary attend and make the wheel movement free.
B. Observe for any foreign materials in between BKT and REV
contacts. If found, remove them and attend to BKT/REV
contacts.
5. If the wheel is rotating freely and BKT / REV contacts are free from
foreign materials and still traction motor current is showing high as
compared to other motors, the TM6AI sensor might be defective.
Replace the sensor and check up.
46
PARAMETER
DESCRIPTION
FAULT CODE
1043
FAULT MESSAGE
Traction Motor 1 High Current While in Dynamic Brake.
RESTRICTIONS
Dynamic brake is Prohibited.
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Traction Motor current is reduced and Master
RECOVERY
Controller Handle is brought to Idle. Automatic Fault Reset is permitted
for maximum 3 times in an hour, after which manual clearing is
required.
PROBABLE
1. Short circuited / burnt grids between R1 and R4 (TM1 and TM4
CAUSES
Armatures)
2. Wrong connection of Dynamic brake grids.
3. SLBC4 power contactor tips got welded. (In case of self load box
feature equipped locos)
4. Welded / burnt contacts of BKT.
FAULT
1. Check for any wrong connections at the Dynamic brake grids and
ISOLATION
as well at BKT. Identify and reconnect the cables correctly.
2. Check for welded tips of SLBC4 power contactor. If welded separate
them and clean the tips.
3. Check the BKT contacts thoroughly for any burnt / welded contacts
or foreign material on the contacts. If necessary attend / replace
BKT.
4. Check for any short circuit between R1 and R4 cables from BKT to
Grids.
5. Remove the Grids which are connected between R1 and R4 cables
and check for any burnt / short circuited grid panels. If found
replace the damaged grids.
47
PARAMETER
DESCRIPTION
FAULT CODE
1044
FAULT MESSAGE
Traction Motor 2 High Current While in Dynamic Brake.
RESTRICTIONS
Dynamic brake is Prohibited.
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Traction Motor current is reduced and Master
RECOVERY
Controller Handle is brought to Idle. Automatic Fault Reset is permitted
for maximum 3 times in an hour, after which manual clearing is
required.
PROBABLE
1. Short circuited / burnt grids between R21 and R24 (TM2 and TM5
CAUSES
Armatures)
2. Wrong connection of Dynamic brake grids.
3. Welded / burnt contacts of BKT.
FAULT
1. Check for any wrong connections at the Dynamic brake grids and
ISOLATION
as well at BKT. Identify and reconnect the cables correctly.
2. Check the BKT contacts thoroughly for any burnt / welded contacts
or foreign material on the contacts. If necessary attend / replace
BKT.
3. Check for any short circuit between R21 and R24 cables from BKT
to Grids.
4. Remove the Grids which are connected between R21 and R24
cables and check for any burnt / short circuited grid panels. If found
replace the damaged grids.
48
PARAMETER
DESCRIPTION
FAULT CODE
1045
FAULT MESSAGE
Traction Motor 3 High Current While in Dynamic Brake.
RESTRICTIONS
Dynamic brake is Prohibited.
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Traction Motor current is reduced and Master
RECOVERY
Controller Handle is brought to Idle. Automatic Fault Reset is permitted
for maximum 3 times in an hour, after which manual clearing is
required.
PROBABLE
1. Short circuited / burnt grids between R11 and R14 (TM3 and TM6
CAUSES
Armatures)
2. Wrong connection of Dynamic brake grids.
3. Welded / burnt contacts of BKT.
FAULT
1. Check for any wrong connections at the Dynamic brake grids and
ISOLATION
as well at BKT. Identify and reconnect the cables correctly.
2. Check the BKT contacts thoroughly for any burnt / welded contacts
or foreign material on the contacts. If necessary attend / replace
BKT.
3. Check for any short circuit between R11 and R14 cables from BKT
to Grids.
4. Remove the Grids which are connected between R11 and R14
cables and check for any burnt / short circuited grid panels. If found
replace the damaged grids.
49
PARAMETER
DESCRIPTION
FAULT CODE
1046
FAULT MESSAGE
Traction Motor 4 High Current While in Dynamic Brake.
RESTRICTIONS
Dynamic brake is Prohibited.
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Traction Motor current is reduced and Master
RECOVERY
Controller Handle is brought to Idle. Automatic Fault Reset is permitted
for maximum 3 times in an hour, after which manual clearing is
required.
PROBABLE
1. Short circuited / burnt grids between R1 and R4 (TM1 and TM4
CAUSES
Armatures)
2. Wrong connection of Dynamic brake grids.
3. SLBC4 power contactor tips got welded. (In case of self load box
feature equipped locos)
4. Welded / burnt contacts of BKT.
FAULT
1. Check for any wrong connections at the Dynamic brake grids and
ISOLATION
as well at BKT. Identify and reconnect the cables correctly.
2. Check for welded tips of SLBC4 power contactor. If welded separate
them and clean the tips.
3. Check the BKT contacts thoroughly for any burnt / welded contacts
or foreign material on the contacts. If necessary attend / replace
BKT.
4. Check for any short circuit between R1 and R4 cables from BKT to
Grids.
5. Remove the Grids which are connected between R1 and R4 cables
and check for any burnt / short circuited grid panels. If found
replace the damaged grids.
50
PARAMETER
DESCRIPTION
FAULT CODE
1047
FAULT MESSAGE
Traction Motor 5 High Current While in Dynamic Brake.
RESTRICTIONS
Dynamic brake is Prohibited.
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Traction Motor current is reduced and Master
RECOVERY
Controller Handle is brought to Idle. Automatic Fault Reset is permitted
for maximum 3 times in an hour, after which manual clearing is
required.
PROBABLE
1. Short circuited / burnt grids between R21 and R24 (TM2 and TM5
CAUSES
Armatures)
2. Wrong connection of Dynamic brake grids.
3. Welded / burnt contacts of BKT.
FAULT
1. Check for any wrong connections at the Dynamic brake grids and
ISOLATION
as well at BKT. Identify and reconnect the cables correctly.
2. Check the BKT contacts thoroughly for any burnt / welded contacts
or foreign material on the contacts. If necessary attend / replace
BKT.
3. Check for any short circuit between R21 and R24 cables from BKT
to Grids.
4. Remove the Grids which are connected between R21 and R24
cables and check for any burnt / short circuited grid panels. If found
replace the damaged grids.
51
PARAMETER
DESCRIPTION
FAULT CODE
1048
FAULT MESSAGE
Traction Motor 6 High Current While in Dynamic Brake.
RESTRICTIONS
Dynamic brake is Prohibited.
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Traction Motor current is reduced and Master
RECOVERY
Controller Handle is brought to Idle. Automatic Fault Reset is permitted
for maximum 3 times in an hour, after which manual clearing is
required.
PROBABLE
1. Short circuited / burnt grids between R11 and R14 (TM3 and TM6
CAUSES
Armatures)
2. Wrong connection of Dynamic brake grids.
3. Welded / burnt contacts of BKT.
FAULT
1. Check for any wrong connections at the Dynamic brake grids and
ISOLATION
as well at BKT. Identify and reconnect the cables correctly.
2. Check the BKT contacts thoroughly for any burnt / welded contacts
or foreign material on the contacts. If necessary attend / replace
BKT.
3. Check for any short circuit between R11 and R14 cables from BKT
to Grids.
4. Remove the Grids which are connected between R11 and R14
cables and check for any burnt / short circuited grid panels. If found
replace the damaged grids.
52
PARAMETER
DESCRIPTION
FAULT CODE
1049
FAULT MESSAGE
High Current in Cutout Traction Motor 1. Can’t Load: Power Circuit
Problem
RESTRICTIONS
Motoring and Dynamic brake are Prohibited.
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Traction Motor current is reduced and Master
RECOVERY
Controller Handle is brought to Idle. Automatic Fault Reset is permitted
for maximum 3 times in an hour, after which manual clearing is
required.
PROBABLE
1. P2 power contactor stuck closed and there is no feed back signal
CAUSES
from P2 power contactor.
2. S1 power contactor stuck closed and there is no feed back signal
from S1 power contactor.
3. Wrongly connected power cables.
4. Defective digital output card.
FAULT
1. Check for welded contact tips of P2 and S1 power contactors. If
ISOLATION
welded tips are found:
A. Separate the tips and clean them.
B. Operate the power contactor manually and verify the status of
corresponding LEDs on the respective digital input card.
2. If no welded tips are found and the contactors are in good
condition, check up thoroughly the power cable connections for any
wrong connection.
3. Switch on all the breakers. If power contactors P2 or S1 are directly
picking up, then the digital output card MLSD16 in slot No. 14 is
defective. Replace the card.
53
PARAMETER
DESCRIPTION
FAULT CODE
1050
FAULT MESSAGE
High Current in Cutout Traction Motor 2. Can’t Load: Power Circuit
Problem
RESTRICTIONS
Motoring and Dynamic brake are Prohibited.
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Traction Motor current is reduced and Master
RECOVERY
Controller Handle is brought to Idle. Automatic Fault Reset is permitted
for maximum 3 times in an hour, after which manual clearing is
required.
PROBABLE
1. P32 power contactor stuck closed and there is no feed back signal
CAUSES
from P32 power contactor.
2. S31 power contactor tuck closed and there is no feed back signal
from S31 power contactor.
3. Wrongly connected power cables.
4. Defective digital output card.
FAULT
1. Check for welded contact tips of P32 and S31 power contactors. If
ISOLATION
welded tips are found:
A. Separate the tips and clean them.
B. Operate the power contactor manually and verify the status of
corresponding LEDs on the respective digital input card.
2. If no welded tips are found and the contactors are in good
condition, check up thoroughly the power cable connections for any
wrong connection.
3. Switch on all the breakers. If power contactors P32 or S31 are
directly picking up, then the digital output card is defective. Replace
the card.
54
PARAMETER
DESCRIPTION
FAULT CODE
1051
FAULT MESSAGE
High Current in Cutout Traction Motor 3. Can’t Load: Power Circuit
Problem
RESTRICTIONS
Motoring and Dynamic brake are Prohibited.
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Traction Motor current is reduced and Master
RECOVERY
Controller Handle is brought to Idle. Automatic Fault Reset is permitted
for maximum 3 times in an hour, after which manual clearing is
required.
PROBABLE
1. P22 power contactor stuck closed and there is no feed back signal
CAUSES
from P22 power contactor.
2. S21 power contactor tuck closed and there is no feed back signal
from S21 power contactor.
3. Wrongly connected power cables.
4. Defective digital output card.
FAULT
1. Check for welded contact tips of P22 and S21 power contactors. If
ISOLATION
welded tips are found:
A. Separate the tips and clean them.
B. Operate the power contactor manually and verify the status of
corresponding LEDs on the respective digital input card.
2. If no welded tips are found and the contactors are in good
condition, check up thoroughly the power cable connections for any
wrong connection.
3. Switch on all the breakers. If power contactors P22 or S21 are
directly picking up, then the digital output card is defective. Replace
the card.
55
PARAMETER
DESCRIPTION
FAULT CODE
1052
FAULT MESSAGE
High Current in Cutout Traction Motor 4. Can’t Load: Power Circuit
Problem
RESTRICTIONS
Motoring and Dynamic brake are Prohibited.
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Traction Motor current is reduced and Master
RECOVERY
Controller Handle is brought to Idle. Automatic Fault Reset is permitted
for maximum 3 times in an hour, after which manual clearing is
required.
PROBABLE
1. P1 power contactor stuck closed and there is no feed back signal
CAUSES
from P1 power contactor.
2. S1 power contactor tuck closed and there is no feed back signal
from S1 power contactor.
3. Wrongly connected power cables.
4. Defective digital output card.
FAULT
1. Check for welded contact tips of P1 and S1 power contactors. If
ISOLATION
welded tips are found:
A. Separate the tips and clean them.
B. Operate the power contactor manually and verify the status of
corresponding LEDs on the respective digital input card.
2. If no welded tips are found and the contactors are in good
condition, check up thoroughly the power cable connections for any
wrong connection.
3. Switch on all the breakers. If power contactors P1 or S1 are directly
picking up, then the digital output card is defective. Replace the
card.
56
PARAMETER
DESCRIPTION
FAULT CODE
1053
FAULT MESSAGE
High Current in Cutout Traction Motor 5. Can’t Load: Power Circuit
Problem
RESTRICTIONS
Motoring and Dynamic brake are Prohibited.
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Traction Motor current is reduced and Master
RECOVERY
Controller Handle is brought to Idle. Automatic Fault Reset is permitted
for maximum 3 times in an hour, after which manual clearing is
required.
PROBABLE
1. P31 power contactor stuck closed and there is no feed back signal
CAUSES
from P31 power contactor.
2. S31 power contactor tuck closed and there is no feed back signal
from S31 power contactor.
3. Wrongly connected power cables.
4. Defective digital output card.
FAULT
1. Check for welded contact tips of P31 and S31 power contactors. If
ISOLATION
welded tips are found:
A. Separate the tips and clean them.
B. Operate the power contactor manually and verify the status of
corresponding LEDs on the respective digital input card.
2. If no welded tips are found and the contactors are in good
condition, check up thoroughly the power cable connections for any
wrong connection.
3. Switch on all the breakers. If power contactors P31 or S31 are
directly picking up, then the digital output card is defective. Replace
the card.
57
PARAMETER
DESCRIPTION
FAULT CODE
1054
FAULT MESSAGE
High Current in Cutout Traction Motor 6. Can’t Load: Power Circuit
Problem
RESTRICTIONS
Motoring and Dynamic brake are Prohibited.
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Traction Motor current is reduced and Master
RECOVERY
Controller Handle is brought to Idle. Automatic Fault Reset is permitted
for maximum 3 times in an hour, after which manual clearing is
required.
PROBABLE
1. P21 power contactor stuck closed and there is no feed back signal
CAUSES
from P21 power contactor.
2. S21 power contactor tuck closed and there is no feed back signal
from S21 power contactor.
3. Wrongly connected power cables.
4. Defective digital output card.
FAULT
1. Check for welded contact tips of P21 and S21 power contactors. If
ISOLATION
welded tips are found:
A. Separate the tips and clean them.
B. Operate the power contactor manually and verify the status of
corresponding LEDs on the respective digital input card.
2. If no welded tips are found and the contactors are in good
condition, check up thoroughly the power cable connections for any
wrong connection.
3. Switch on all the breakers. If power contactors P21 or S21 are
directly picking up, then the digital output card is defective. Replace
the card.
58
PARAMETER
DESCRIPTION
FAULT CODE
1055
FAULT MESSAGE
Traction Motor 1 Ckt. Open.
RESTRICTIONS
Traction Motor 1 Cutout and Dynamic Brake Prohibited
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Master Controller Handle is brought to Idle. Automatic
RECOVERY
Fault Reset is permitted for maximum 3 times in an hour, after which
manual clearing is required.
PROBABLE
1. Defective power contactor P2. Power contactor picking up but main
CAUSES
contact tips are not closing.
2. Foreign materials (Insulation) in REV contacts.
3. Foreign materials (Insulation) in BKT contacts.
4. Tr. Motor cables burnt or disconnected
5. Tr. Motor open circuited internally.
FAULT
1. Ease the throttle and Switch OFF GF switch. Remove the archute of
ISOLATION
P2 power contactor.
2. Operate the power contactor either through display unit by
selecting the manual test for outputs or by manually operating
power contactor. Check and ensure the main tips are closing
correctly and there is no obstruction in between.
3. Manually operate BKT to braking side and REV to non-working side.
Check up thoroughly any foreign materials are fallen in between
contacts of BKT and REV like insulating tape etc. (Especially BKT 9th
contact. REV No.1 contact.)
4. Check up under truck cable joints of Tr. Motor 1 for any burnt /
disconnected cables. If found replace / attend the cables. Remake
the joints.
5. Disconnect the TM cables and check for continuity of field and
armature. If any open circuit is found, replace the motor.
59
PARAMETER
DESCRIPTION
FAULT CODE
1056
FAULT MESSAGE
Traction Motor 2 Ckt. Open.
RESTRICTIONS
Traction Motor 2 Cutout and Dynamic Brake Prohibited
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Master Controller Handle is brought to Idle. Automatic
RECOVERY
Fault Reset is permitted for maximum 3 times in an hour, after which
manual clearing is required.
PROBABLE
1. Defective power contactor P32. Power contactor picking up but main
CAUSES
contact tips are not closing.
2. Foreign materials (Insulation) in REV contacts.
3. Foreign materials (Insulation) in BKT contacts.
4. Tr. Motor cables burnt or disconnected
5. Tr. Motor open circuited internally.
FAULT
1. Ease the throttle and Switch OFF GF switch. Remove the archute of
ISOLATION
P32 power contactor.
2. Operate the power contactor either through display unit by
selecting the manual test for outputs or by manually operating
power contactor. Check and ensure the main tips are closing
correctly and there is no obstruction in between.
3. Manually operate BKT to braking side and REV to non-working side.
Check up thoroughly any foreign materials are fallen in between
contacts of BKT and REV like insulating tape etc. (Especially BKT 7th
contact. REV No.2 contact.)
4. Check up under truck cable joints of Tr. Motor 2 for any burnt /
disconnected cables. If found replace / attend the cables. Remake
the joints.
5. Disconnect the TM cables and check for continuity of field and
armature. If any open circuit is found, replace the motor.
60
PARAMETER
DESCRIPTION
FAULT CODE
1057
FAULT MESSAGE
Traction Motor 3 Ckt. Open.
RESTRICTIONS
Traction Motor 3 Cutout and Dynamic Brake Prohibited
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Master Controller Handle is brought to Idle. Automatic
RECOVERY
Fault Reset is permitted for maximum 3 times in an hour, after which
manual clearing is required.
PROBABLE
1. Defective power contactor P22. Power contactor picking up but main
CAUSES
contact tips are not closing.
2. Foreign materials (Insulation) in REV contacts.
3. Foreign materials (Insulation) in BKT contacts.
4. Tr. Motor cables burnt or disconnected
5. Tr. Motor open circuited internally.
FAULT
1. Ease the throttle and Switch OFF GF switch. Remove the archute of
ISOLATION
P22 power contactor.
2. Operate the power contactor either through display unit by
selecting the manual test for outputs or by manually operating
power contactor. Check and ensure the main tips are closing
correctly and there is no obstruction in between.
3. Manually operate BKT to braking side and REV to non-working side.
Check up thoroughly any foreign materials are fallen in between
contacts of BKT and REV like insulating tape etc. (Especially BKT 6th
contact. REV No.3 contact.)
4. Check up under truck cable joints of Tr. Motor 3 for any burnt /
disconnected cables. If found replace / attend the cables. Remake
the joints.
5. Disconnect the TM cables and check for continuity of field and
armature. If any open circuit is found, replace the motor.
61
PARAMETER
DESCRIPTION
FAULT CODE
1058
FAULT MESSAGE
Traction Motor 4 Ckt. Open.
RESTRICTIONS
Traction Motor 4 Cutout and Dynamic Brake Prohibited
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Master Controller Handle is brought to Idle. Automatic
RECOVERY
Fault Reset is permitted for maximum 3 times in an hour, after which
manual clearing is required.
PROBABLE
1. Defective power contactor P1. Power contactor picking up but main
CAUSES
contact tips are not closing.
2. Foreign materials (Insulation) in REV contacts.
3. Foreign materials (Insulation) in BKT contacts.
4. Tr. Motor cables burnt or disconnected
5. Tr. Motor open circuited internally.
FAULT
1. Ease the throttle and Switch OFF GF switch. Remove the archute of
ISOLATION
P1 power contactor.
2. Operate the power contactor either through display unit by
selecting the manual test for outputs or by manually operating
power contactor. Check and ensure the main tips are closing
correctly and there is no obstruction in between.
3. Manually operate BKT to braking side and REV to non-working side.
Check up thoroughly any foreign materials are fallen in between
contacts of BKT and REV like insulating tape etc. (Especially BKT 4th
contact. REV No.4 contact.)
4. Check up under truck cable joints of Tr. Motor 4 for any burnt /
disconnected cables. If found replace / attend the cables. Remake
the joints.
5. Disconnect the TM cables and check for continuity of field and
armature. If any open circuit is found, replace the motor.
62
PARAMETER
DESCRIPTION
FAULT CODE
1059
FAULT MESSAGE
Traction Motor 5 Ckt. Open.
RESTRICTIONS
Traction Motor 5 Cutout and Dynamic Brake Prohibited
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Master Controller Handle is brought to Idle. Automatic
RECOVERY
Fault Reset is permitted for maximum 3 times in an hour, after which
manual clearing is required.
PROBABLE
1. Defective power contactor P31. Power contactor picking up but main
CAUSES
contact tips are not closing.
2. Foreign materials (Insulation) in REV contacts.
3. Foreign materials (Insulation) in BKT contacts.
4. Tr. Motor cables burnt or disconnected
5. Tr. Motor open circuited internally.
FAULT
1. Ease the throttle and Switch OFF GF switch. Remove the archute of
ISOLATION
P31 power contactor.
2. Operate the power contactor either through display unit by
selecting the manual test for outputs or by manually operating
power contactor. Check and ensure the main tips are closing
correctly and there is no obstruction in between.
3. Manually operate BKT to braking side and REV to non-working side.
Check up thoroughly any foreign materials are fallen in between
contacts of BKT and REV like insulating tape etc. (Especially BKT 2nd
contact. REV No.5 contact.)
4. Check up under truck cable joints of Tr. Motor 5 for any burnt /
disconnected cables. If found replace / attend the cables. Remake
the joints.
5. Disconnect the TM cables and check for continuity of field and
armature. If any open circuit is found, replace the motor.
63
PARAMETER
DESCRIPTION
FAULT CODE
1060
FAULT MESSAGE
Traction Motor 6 Ckt. Open.
RESTRICTIONS
Traction Motor 6 Cutout and Dynamic Brake Prohibited
ALARM BELL
30 Seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when Master Controller Handle is brought to Idle. Automatic
RECOVERY
Fault Reset is permitted for maximum 3 times in an hour, after which
manual clearing is required.
PROBABLE
1. Defective power contactor P21. Power contactor picking up but main
CAUSES
contact tips are not closing.
2. Foreign materials (Insulation) in REV contacts.
3. Foreign materials (Insulation) in BKT contacts.
4. Tr. Motor cables burnt or disconnected
5. Tr. Motor open circuited internally.
FAULT
1. Ease the throttle and Switch OFF GF switch. Remove the archute of
ISOLATION
P21 power contactor.
2. Operate the power contactor either through display unit by
selecting the manual test for outputs or by manually operating
power contactor. Check and ensure the main tips are closing
correctly and there is no obstruction in between.
3. Manually operate BKT to braking side and REV to non-working side.
Check up thoroughly any foreign materials are fallen in between
contacts of BKT and REV like insulating tape etc. (Especially BKT 1st
contact. REV No.6 contact.)
4. Check up under truck cable joints of Tr. Motor 6 for any burnt /
disconnected cables. If found replace / attend the cables. Remake
the joints.
5. Disconnect the TM cables and check for continuity of field and
armature. If any open circuit is found, replace the motor.
64
PARAMETER
DESCRIPTION
FAULT CODE
1061
FAULT MESSAGE
Battery Voltage LOW
Warning: Loco may STALL
RESTRICTIONS
Nil
ALARM BELL
Continuously ON
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when the battery voltage is more than 62V for 5 seconds.
RECOVERY
PROBABLE
This is a warning message indicating Batteries are getting discharged.
CAUSES
Normally this message is followed by
Fault message ‘Aux. Gen. output open circuited.’ Fault code 1145 or
Fault message ‘Aux. Gen Field circuit open / shorted’ Fault code 1146
FAULT
1. If none of the above faults are logged, prior to this fault message:
ISOLATION
A. Change the display mode to ‘Auxiliary’
B. Measure Voltage with a voltmeter at the BATV battery voltage
sensor (wire No. 51 and 4) and voltage at AGAV Voltage sensor
(wire No. 49 and 44D).
C. If the measured voltages are tallying with the displayed
parameters and really battery voltage is low and battery-
charging current is zero, Then RCD is open circuited. Replace
RCD.
D. If the measured battery voltage is higher than displayed voltage
the voltage sensor or its wiring is defect. Check and identify.
2. If the ‘Aux. Gen. output open circuited.’ Fault message is also
logged trouble shoot to find open circuit in the Aux. Gen. output
circuit. Refer Fault code 1145.
3. If Aux. Gen. Field Circuit open / Shorted’ message is also logged
trouble shoot to find open circuit in the Auxiliary Generator field
circuit. Refer fault log No. 1146. ‘Aux. Gen. Field Circuit Open or
Short’.
65
PARAMETER
DESCRIPTION
FAULT CODE
1062
FAULT MESSAGE
Battery Voltage HIGH Fault
RESTRICTIONS
Battery charging prohibited.
ALARM BELL
Continuously ON
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when the battery voltage is less than the set limit by 2 Volts
RECOVERY
for 15 seconds.
PROBABLE
1. The battery charging voltage is more than the set voltage.
CAUSES
Normally this message is followed by ‘Aux.Gen. Voltage High’. Fault
code 1141.
FAULT
1. Switch off AGFB. And reset the fault.
ISOLATION
2. Change the display mode to ‘Auxiliaries’ under display menu option.
3. Measure battery voltage with a voltmeter. If the measured value is
equal to the displayed BATV value and is less than 69V, then the
fault is transient.
4. If the displayed value is more than the measured value, the voltage
sensor is bad. Replace the sensor.
5. Switch ON AGFB and observe the AGAV on the display. If AGAV is
72 Volts, then the fault is transient.
6. If AGAV is more than 72Volts, trouble shoot for Aux. Gen.Voltage
High. Refer fault code No. 1141. ‘Aux. Gen. Output Voltage High
FAULT’
66
PARAMETER
DESCRIPTION
FAULT CODE
1063
FAULT MESSAGE
Aux. Gen. Field drive short circuit fault.
RESTRICTIONS
Battery charging prohibited. Warning: Battery life limited. Loco may
stall.
ALARM BELL
30 sec.
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
No auto recovery.
RECOVERY
PROBABLE
1. Defective MPWM2 card.
CAUSES
2. Defective wiring.
3. Defective AGFI current sensor
FAULT
1. Switch OFF all breakers. Connect DC ammeter 0-10Amps to wire
ISOLATION
terminals AGC (+) and AGF (-) at AGPR interlocks.
2. Switch ON MB1, MB2, MFPB1, MFPB2, FPB and MPCB breakers.
3. Change the display mode to ‘Auxiliary’ under ‘Display’ option
available in main menu.
4. Check the Auxiliary Field current AGFI.
5. If current in the meter is equal to the displayed current of AGFI,
A. PWM output card is defective. Replace the card.
B. There may be a short externally from AGC to locomotive 4 wire.
6. If current in the meter is zero and AGFI indicating some value then
the current sensor is faulty. Replace the current sensor.
7. If both the currents are zero,
A. There could be an external short between Auxiliary Generator
field LSS and locomotive 4 wire. Identify and remove the short
circuit.
B. There could be an internal short between LSS and LAA in side
the machine.
67
PARAMETER
DESCRIPTION
FAULT CODE
1064
FAULT MESSAGE
Low Lube Oil Pressure
RESTRICTIONS
Engine Shutdown.
ALARM BELL
30 sec.
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when engine is shutdown. Automatic Fault Reset is
RECOVERY
permitted for maximum 5 times in an hour, after which manual
clearing is required.
PROBABLE
This message will only be logged when ‘Low LOP shut down enabled’
CAUSES
flag is enabled. By default this flag is disabled as Governor is taking
care of low lube oil pressure.
This message will be logged if engine is shut down due to low lube oil
pressure as sensed by LOP pressure sensor available in MEP-system.
1. Lube Oil Pressure is really dipped below the set limit.
2. Pressure sensor might be defective.
3. MIAI card might be defective.
FAULT
1. Check the real conditions at which the engine is shut down. If realy
ISOLATION
there is a dip in LOP, identify the root cause for LOP dipping.
2. Check the difference of pressures between LOP guage / diplay
reading on Governor. If there is a difference between the MCBG
display / LOP gauge:
A. Connect a calibrated gauge at the pressure inlet of LOP sensor
by providing a ‘T’ joint. Crank the engine. Compare the
readings.
B. If there is a difference between display and the calibrated
gauge:
a. Replace the sensor and verify the readings.
b. If still difference of reading is available, change the MIAI
card and check the readings.
C. If the difference is permisable, check the pipelines and clean the
pipes.
68
PARAMETER
DESCRIPTION
FAULT CODE
1068
FAULT MESSAGE
REV Stuck in Reverse. Run Auto/Manual Test
RESTRICTIONS
Forward Motoring and Forward Dynamic Brake Prohibited
ALARM BELL
30 seconds
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when the RVFFB and RVRFB feed back signals become
RECOVERY
normal.
PROBABLE
1.
Control air pressure is < 2Kg./Sq.Cm.
CAUSES
2.
The REV is physically got stuck due to mechanical obstruction.
3.
Defective wiring of REV feed back signals RVFFB and RVRFB
4.
Defective digital input card.
5.
REV forward direction magnet valve defective.
6.
REV forward direction magnet valve is not getting electrical supply.
7.
Defective digital output card.
FAULT
1.
Check and adjust the control air pressure to 5 Kg./Sq.Cm.
ISOLATION
2.
Manually operate the Reverser by pressing the forward and reverse
magnet valves alternatively to ensure free operation of the
contacts.
A. Ensure that change over contacts and auxiliary contacts are
changing their position freely.
B. If the operation of the REV is sluggish / not operating, attend /
replace the reverser.
C. Check the status of the corresponding feed back LEDs (14 & 15)
on the digital input card in slot 10. Both Green and Yellow LEDs
should toggle their status with respect to REV operation.
D. If the status is not syncronysing to REV operation:
a) Adjust the feedback auxiliary contacts to get correct logic.
b) If both Green LEDs (14 & 15) are not glowing, check the
incoming supply at the common terminal of the Aux. Contacts.
(wire No. 51) with respect to locomotive 4 wire.
c) If the supply is zero, check the continuity of 51wire loop. If
necessary change the wiring.
d) If supply is more than 65V, check the supply at out going
terminals (wire nos. RVFFB and RVRFB).
e) If supply is more than 65V on the corresponding terminal with
respective REV position
1) Check the slackness of the connector of cable ID: AU. If
slack tighten the connector.
2) Check the wire continuity of wires from REV feed back
auxiliary contacts to MEP-660. (Cable ID: AU, Pins - R &
S). If necessary replace the cable.
f) If only Green LEDs (14 & 15) are toggling their status and
corresponding Yellow LEDs are not toggling, then Digital input
card in slot 10 is defective. Replace the card.
3.
Manually set the REV in Reverse direction.
4.
Set the display mode to ‘Manual Test for outputs’ under Test Mode
menu.
5.
Enter 11 and press ‘Enter’ key to test reverser forward.
6.
Press 1 to energise the REV forward side magnet valve.
69
7. The REV should operate to forward direction. The Green LED 14 on
the digital input card MDIP16 in slot 10 should glow.
8. If REV is not operating to forward direction, Check supply at the
REV forward side magnet valve coil.
9. If supply is more than 65 volts, then magnet valve is defective.
Replace the magnet valve.
10. If supply is zero, check the supply at the magnet valve coil terminal
(wire no. 8) with respect to locomotive 4 wire.
11. If the voltage is zero, check continuity of 8-wire loop coming to
magnet valve.
12. If voltage is more than 65V, Check the voltage between locomotive
wire 13 and wire RVFCL at the magnet valve coil
13. If the voltage is zero,
A. Check the slackness of the connector of the cable ID: AY at
MEP-660. If slack tighten the connector.
B. Check the continuity of wire RVFCL from the magnet valve coil
to the connector of cable ID: AY Pin No.M. If necessary replace
the cable.
C. The digital output card might be defective. Change the card and
check up once again.
14. Press 0 to de-energise the magnet valve and press menu key to
exit.
70
PARAMETER
DESCRIPTION
FAULT CODE
1069
FAULT MESSAGE
REV-F Aux. Contact ckt. Open. Run Auto/manual Test.
RESTRICTIONS
Forward Motoring and Forward Dynamic Brake Prohibited
ALARM BELL
30 seconds
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when the REV-F Auxiliary contact circuit is closed.
RECOVERY
PROBABLE
1. Bad contact of REV-F auxiliary contact.
CAUSES
2. Disconnected wires at auxiliary contacts / open circuited wiring.
3. Defective digital input card.
FAULT
1. Ensure Reverser is in forward direction. If not operate manually.
ISOLATION
2. Check the status of the Green LED 14 on the digital input card in
slot 10.
3. If the Green LED is not glowing:
A. Auxiliary contact is bad. Clean/adjust the contact and check.
B. Check supply voltage at incoming terminal (wire No. 51) with
respect to locomotive 4 wire.
C. If supply is zero, check the continuity of 51-wire loop.
A. If the supply voltage is more than 65V, check supply between
wire no. RVFFB and locomotive 4 wire.
D. If the supply voltage is more than 65V,
a) Check the slackness of the connector of the cable ID: AU at
MEP660. If slack tighten the connector.
b) Check the continuity of the wire REFFB, from the reverser
aux. Contact to connector of cable ID: AU, Pin - R. If
necessary replace the cable.
4. If green LED 14 is glowing but the corresponding yellow LED is not
glowing, then the digital input card is defective. Replace the card
and check up.
71
PARAMETER
DESCRIPTION
FAULT CODE
1070
FAULT MESSAGE
REV Stuck in Forward. Run Auto/Manual Test
RESTRICTIONS
Reverse Motoring and Reverse Dynamic Brake Prohibited
ALARM BELL
30 seconds
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when the RVFFB and RVRFB feed back signals become
RECOVERY
normal.
PROBABLE
1.
Control air pressure is < 2Kg./Sq.Cm.
CAUSES
2.
The REV is physically got stuck due to mechanical obstruction.
3.
Defective wiring of REV feed back signals RVFFB and RVRFB
4.
Defective digital input card.
5.
REV reverse direction magnet valve defective.
6.
REV reverse direction magnet valve is not getting electrical supply.
7.
Defective digital output card.
FAULT
1.
Check and adjust the control air pressure to 5 Kg./Sq.Cm.
ISOLATION
2.
Manually operate the Reverser by pressing the forward and reverse
magnet valves alternatively to ensure free operation of the
contacts.
A. Ensure that change over contacts and auxiliary contacts are
changing their position freely.
B. If the operation of the REV is sluggish / not operating, attend /
replace the reverser.
C. Check the status of the corresponding feed back LEDs (14 & 15)
on the digital input card in slot 10. Both Green and Yellow LEDs
should toggle their status with respect to REV operation.
3.
If the status is not syncronysing to REV operation:
A. Adjust the feedback auxiliary contacts to get correct logic.
4.
If both Green LEDs (14 & 15) are not glowing, check the voltage
between wire 51 at the Aux. Contact of reverser and locomotive 4
wire.
A. If the supply is zero, check the continuity of 51wire loop. If
necessary change the wiring.
5.
If supply is more than 65V, check the supply at out going terminals
(wire nos. RVFFB and RVRFB by changing the REV position).
A. If supply is more than 65V on the corresponding terminal with
respective REV position, check the wire continuity of wires from
REV feed back auxiliary contacts to MEP-660. (Cable ID:AU, Pins
- R & S). If necessary replace the cable.
B. If only Green LEDs (14 & 15) are toggling their status and
corresponding Yellow LEDs are not toggling, then Digital input
card in slot 10 is defective. Replace the card.
6.
Manually set the REV in Forward direction.
7.
Set the display mode to ‘Manual Test for outputs’ under Test Mode
menu.
8.
To test REV reverse side operation, enter 12 and press ‘Enter’ key.
9.
Press 1 to energise the REV reverse side magnet valve.
10. The REV should operate to reverse direction.
11. If REV is not operating to reverse direction, check supply at the
REV reverse side magnet valve coil.
72
A. If supply is more than 60 volts, then magnet valve is defective.
Replace the magnet valve.
12. If supply is zero, check the supply at the magnet valve coil terminal
(wire no. 0) with respect to locomotive 4 wire.
A. If the voltage is zero, check continuity of 0 wire loop connected
to magnet valve.
13. If voltage is more than 65V, check the voltage between locomotive
wire No. 13 (TB) and wire RVRCL at magnet valve coil.
A. If the voltage is zero,
a) Check the slackness of the connector of the cable ID: AY. If
slack tighten the connector.
b) Check the wire continuity of RVRCL from the magnet valve to
connector of cable ID: AY pin - N. If necessary replace the
cable.
c) The digital output card might be defective. Change the card
and check up once again.
14. Press 0 to de-energise the magnet valve and press menu key to
exit.
73
PARAMETER
DESCRIPTION
FAULT CODE
1071
FAULT MESSAGE
REV-R Aux. Contact ckt. Open. Run Auto/manual Test.
RESTRICTIONS
Reverse Motoring and Reverse Dynamic Brake Prohibited
ALARM BELL
30 seconds
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when the REV-R Auxiliary contact circuit is closed.
RECOVERY
PROBABLE
1. Bad contact of REV-R auxiliary contact.
CAUSES
2. Disconnected wires at auxiliary contacts / open circuited wiring.
3. Defective digital input card.
FAULT
1. Ensure Reverser is in reverse direction. If not operate manually.
ISOLATION
2. Check the status of the Green LED 15 on the digital input card in
slot 10.
3. If the Green LED is not glowing:
A. Auxiliary contact is bad. Clean/adjust the contact and check.
B. Check supply voltage at incoming terminal (wire No. 51) with
respect to locomotive 4 wire.
C. If supply is zero, check the continuity of 51-wire loop.
B. If the supply voltage is more than 65V, check supply between
wire no. RVRFB and locomotive 4 wire.
D. If the supply voltage is more than 65V,
a) Check the slackness of the connector of the cable ID: AU at
MEP660. If slack tighten the connector.
b) Check the continuity of the wire RVRFB, from the reverser
aux. Contact to connector of cable ID: AU, Pin - S. If
necessary replace the cable.
4. If green LED 15 is glowing but the corresponding yellow LED is not
glowing, then the digital input card is defective. Replace the card
and check up.
74
PARAMETER
DESCRIPTION
FAULT CODE
1072
FAULT MESSAGE
Wrong Command: TL23 High & TL17 Low. Can’t Brake
RESTRICTIONS
Dynamic Brake Prohibited
ALARM BELL
30 seconds
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when the TL23 and TL17 are found both High.
RECOVERY
PROBABLE
1. This fault generally logs while the locomotive is set to dynamic
CAUSES
brake mode or while changing from dynamic brake to motoring.
2. Wrong wiring.
3. Jumper cable defective while working MU consist.
FAULT
1. Most probably this fault is a transient fault and recovers
ISOLATION
automatically when dynamic brake is applied in correct sequence.
2. Set the locomotive to dynamic brake mode. If the fault is not
logging, then the fault is transient.
3. If the fault is logging frequently, check the following.
4. Proper sequence of master controller interlocks which are
energizing wire No. 23 and wire no. 17.
5. Wire No. 17 should get energized in OFF position.
6. Wire No. 23 should get energized in Big. D position.
7. Check up whether wire No. 23 is getting any wrong feed due to
wrong connections or defective MU cable.
75
PARAMETER
DESCRIPTION
FAULT CODE
1073
FAULT MESSAGE
Fire Alarm ON. Check Loco and MU Locos for fire and extinguish fire.
RESTRICTIONS
Engine Shutdown.
ALARM BELL
30 sec.
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when engine is shut down and fire alert signal is OFF.
RECOVERY
PROBABLE
1. MEP detected fire alert signal from Fire Alert System and shut down
CAUSES
the engine.
2. MDIP16 card in slot No. 13 might be defective.
3. Defective wiring.
4. Deective MU cable.
FAULT
This message can log when any fire accident occurred either in leading
ISOLATION
loco or trailing loco.
Ensure that there is no fire accident in any loco before trouble shooting
the fault.
1. Check the status of green LED 6 on MDIP 16 card in slot No. 13. If
LED is glowing:
A. Check the voltage between wire TL 11 and 4. If voltage is more
than 65V.
a. Then the fire alerter system is ON. Check the Fire alerter
system and reset. If already system is reset then wire TL 11
is getting a wrong supply. Identify and rectify the problem.
B. If voltage is zero, Fire alerter system is not activated and
message is logged then the MDIP16 card in slot 13 might be
defective.
C. Replace the MDIP16 card and verify.
Note: Malfunction / wrong detection of fire by the fire alerter system
can cause logging of the above fault.
76
PARAMETER
DESCRIPTION
FAULT CODE
1074
FAULT MESSAGE
Field Shunting Relay FSR or FS Contactor FS2X Stuck Closed.
RESTRICTIONS
Motoring always with field shunting. Motoring in parallel prohibited.
ALARM BELL
30 seconds
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when the stuck closed relay/contactor is detected as open.
RECOVERY
PROBABLE
1. Welded FS contactors.
CAUSES
2. Defective FSR Relay
3. Defective wiring.
4. Defective output card.
FAULT
1. Check the status of Green LED 10 and yellow LED 10 on the digital
ISOLATION
input card in slot 12.
2. If both the LEDs are glowing, check the status of FSR relay.
A. If FSR is energized,
a) Check the condition of FSR relay for any dislocated springs. If
necessary change the relay.
b) The digital output card in slot 15 might be defective. Replace
the card.
3. If FSR is in de-energised position, check FS contactors for any
welded contact tips. If found welded contactors, separate the tips
and clean them. The LEDs should be OFF.
4. If still LEDs are glowing, FSFB wire is getting wrongly supply due to
wrong wiring / shorted wiring. Identify and rectify.
5. If both the LEDs are not glowing but the fault is logged, check
operation of FS contactors for proper operation. Delayed dropout of
any FS contactor can log this fault and later on it is recovered.
Note: This Error message will be generated only if either “Series Field Shunting” or
“Parallel Field Shunting” ENABLED flags are set (√).
77
PARAMETER
DESCRIPTION
FAULT CODE
1075
FAULT MESSAGE
Field Shunting Relay FSR circuit open.
RESTRICTIONS
Motoring with field shunting and Motoring in parallel prohibited.
ALARM BELL
30 seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when the master handle is brought to IDLE. Automatic reset
RECOVERY
is permitted for 3 times after which manual reset is required.
PROBABLE
1.
Defective FSR relay.
CAUSES
2.
Defective digital output card
3.
Defective wiring of FS contactor feed back.
4.
Defective digital input card.
FAULT
1.
Set the display mode to ‘Manual Test for outputs’ under Test Mode
ISOLATION
menu.
2.
Enter 24 and press ‘Enter’ key to test the FSR operation.
3.
Press ‘1’ key to switch on FSR relay.
4.
FSR relay should pickup and along with that FS contactors also
should pick up.
5.
If FSR relay not picking up check Voltage across FSR relay coil with
a voltmeter.
A. If voltage is more than 65V, then the Relay is defective. Replace
the relay.
6.
If voltage is zero, check voltage at FSR coil terminal (Wire No. 13)
with respect to locomotive 4 wire with a voltmeter.
A. If voltage is zero, check the continuity of 13-wire loop
connected to FSR relay. Check and replaced the open circuited
wires.
7.
If Voltage is more than 65V, check the voltage between Locomotive
13 wire and wire FSRCL at FSR relay coil terminal.
A. If the voltage is zero:
a) Check slackness of connector of cable ID: AZ at MEP660
control unit. If slack tighten the connector.
b) Check continuity of FSRCL wire from FSR coil terminal to MEP-
660 (Cable ID: AZ, Pin-J). If necessary replace the cable.
c) If continuity is available, the digital output card 2 in slot No.
15 is defective. Replace the card and recheck.
8.
If FSR relay is picking up and FS contactors are not picking up:
A. Bad interlock of FSR relay. Replace the FSR relay.
B. There is no 13-wire supply at FSR relay interlocks. Check up
continuity of 13-wire loop. Replace any open circuited wires.
9.
If FS contactors are picking up:
10. Check the status of Green LED 10 on the Digital input card in slot
No. 12. The LED should glow.
11. If the Green LED 10 is not glowing, check voltage at incoming wire
51 at FS contactor auxiliary contacts with respective to locomotive 4
wire.
A. If the voltage is zero, check continuity of 51-wire loop. Replace
any open circuited wires/ wrong connections.
12. If voltage is more than 65V, Check the voltage at FS contactor
auxiliary contact (wire No. FSFB) with respective locomotive 4 wire.
78
A. If the Voltage is more than 65V, check continuity of wire FSFB
from FS 26 contactor Auxiliary contact to MEP-660. (Cable ID:
AW, Pin-L). If necessary replace the cable.
13. If the Green LED is glowing and corresponding yellow LED is not
glowing, the digital input card in slot 12 is defective.
14. Replace the card and check once again.
Note: This Error message will be generated only if either “Series Field Shunting” or
“Parallel Field Shunting” ENABLED flags are set (√).
79
PARAMETER
DESCRIPTION
FAULT CODE
1076
FAULT MESSAGE
Loose Contact in S1 circuit. Run Auto/Manual Test
Power Limited: Power Circuit Problem
RESTRICTIONS
TM1 and TM4 are cut out in 2S-3P mode only. Dynamic brake
prohibited.
ALARM BELL
30 seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
--
RECOVERY
PROBABLE
1. Fluttering of power contactor due to improper air supply.
CAUSES
2. Power contactor itself defective.
3. Loose connections in the wiring.
FAULT
1. Ensure control air pressure is 5kg. /Sq.Cm. Adjust if necessary.
ISOLATION
2. Check for air leakages in the pneumatic pipeline connected to
power contactor. If necessary replace the pneumatic pipe.
3. Manually operate the power contactor by pressing the armature
plate.
4. Check for air leakages from the magnet valve and power contactor
cylinder. There should not be any leakages.
5. The contactor should pick up with out any sluggish operation. If
found sluggish, replace power contactor.
6. Check power contactor main tips for any slackness. Ensure there is
no loose contact.
7. Check for magnet valve coil connection. The coil connections should
be tight and no loose crimped wires.
8. Ensure connector tightness at MEP-660. (Cable ID: AY).
80
PARAMETER
DESCRIPTION
FAULT CODE
1077
FAULT MESSAGE
Loose Contact in S21 circuit. Run Auto/Manual Test
Power Limited: Power Circuit Problem
RESTRICTIONS
TM3 and TM6 are cut out in 2S-3P mode only. Dynamic brake
prohibited.
ALARM BELL
30 seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
--
RECOVERY
PROBABLE
1. Fluttering of power contactor due to improper air supply.
CAUSES
2. Power contactor itself defective.
3. Loose connections in the wiring.
FAULT
1. Ensure control air pressure is 5kg. /Sq.Cm. Adjust if necessary.
ISOLATION
2. Check for air leakages in the pneumatic pipeline connected to
power contactor. If necessary replace the pneumatic pipe.
3. Manually operate the power contactor by pressing the armature
plate.
4. Check for air leakages from the magnet valve and power contactor
cylinder. There should not be any leakages.
5. The contactor should pick up with out any sluggish operation. If
found sluggish, replace power contactor.
6. Check power contactor main tips for any slackness. Ensure there is
no loose contact.
7. Check for magnet valve coil connection. The coil connections should
be tight and no loose crimped wires.
8. Ensure connector tightness at MEP-660. (Cable ID: AY).
81
PARAMETER
DESCRIPTION
FAULT CODE
1078
FAULT MESSAGE
Loose Contact in S31 circuit. Run Auto/Manual Test
Power Limited: Power Circuit Problem
RESTRICTIONS
TM2 and TM5 are cut out in 2S-3P mode only. Dynamic brake
prohibited.
ALARM BELL
30 seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
--
RECOVERY
PROBABLE
1. Fluttering of power contactor due to improper air supply.
CAUSES
2. Power contactor itself defective.
3. Loose connections in the wiring.
FAULT
1. Ensure control air pressure is 5kg. /Sq.Cm. Adjust if necessary.
ISOLATION
2. Check for air leakages in the pneumatic pipeline connected to
power contactor. If necessary replace the pneumatic pipe.
3. Manually operate the power contactor by pressing the armature
plate.
4. Check for air leakages from the magnet valve and power contactor
cylinder. There should not be any leakages.
5. The contactor should pick up with out any sluggish operation. If
found sluggish, replace power contactor.
6. Check power contactor main tips for any slackness. Ensure there is
no loose contact.
7. Check for magnet valve coil connection. The coil connections should
be tight and no loose crimped wires.
8. Ensure connector tightness at MEP-660. (Cable ID: AY).
82
PARAMETER
DESCRIPTION
FAULT CODE
1079
FAULT MESSAGE
Loose Contact in P1 circuit. Run Auto/Manual Test
Power Limited: Power Circuit Problem
RESTRICTIONS
TM4 is cut out in 6P mode only. Dynamic brake prohibited.
ALARM BELL
30 seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
--
RECOVERY
PROBABLE
1. Fluttering of power contactor due to improper air supply.
CAUSES
2. Power contactor itself defective.
3. Loose connections in the wiring.
FAULT
1. Ensure control air pressure is 5kg. /Sq.Cm. Adjust if necessary.
ISOLATION
2. Check for air leakages in the pneumatic pipeline connected to
power contactor. If necessary replace the pneumatic pipe.
3. Manually operate the power contactor by pressing the armature
plate.
4. Check for air leakages from the magnet valve and power contactor
cylinder. There should not be any leakages.
5. The contactor should pick up with out any sluggish operation. If
found sluggish, replace power contactor.
6. Check power contactor main tips for any slackness. Ensure there is
no loose contact.
7. Check for magnet valve coil connection. The coil connections should
be tight and no loose crimped wires.
8. Ensure connector tightness at MEP-660. (Cable ID: AY).
83
PARAMETER
DESCRIPTION
FAULT CODE
1080
FAULT MESSAGE
Loose Contact in P21 circuit. Run Auto/Manual Test
Power Limited: Power Circuit Problem
RESTRICTIONS
TM6 is cut out in 6P mode only. Dynamic brake prohibited.
ALARM BELL
30 seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
--
RECOVERY
PROBABLE
1. Fluttering of power contactor due to improper air supply.
CAUSES
2. Power contactor itself defective.
3. Loose connections in the wiring.
FAULT
1. Ensure control air pressure is 5kg. /Sq.Cm. Adjust if necessary.
ISOLATION
2. Check for air leakages in the pneumatic pipeline connected to
power contactor. If necessary replace the pneumatic pipe.
3. Manually operate the power contactor by pressing the armature
plate.
4. Check for air leakages from the magnet valve and power contactor
cylinder. There should not be any leakages.
5. The contactor should pick up with out any sluggish operation. If
found sluggish, replace power contactor.
6. Check power contactor main tips for any slackness. Ensure there is
no loose contact.
7. Check for magnet valve coil connection. The coil connections should
be tight and no loose crimped wires.
8. Ensure connector tightness at MEP-660. (Cable ID: AY).
84
PARAMETER
DESCRIPTION
FAULT CODE
1081
FAULT MESSAGE
Loose Contact in P31 circuit. Run Auto/Manual Test
Power Limited: Power Circuit Problem
RESTRICTIONS
TM5 is cut out in 6P mode only. Dynamic brake prohibited.
ALARM BELL
30 seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
--
RECOVERY
PROBABLE
1. Fluttering of power contactor due to improper air supply.
CAUSES
2. Power contactor itself defective.
3. Loose connections in the wiring.
FAULT
1. Ensure control air pressure is 5kg. /Sq.Cm. Adjust if necessary.
ISOLATION
2. Check for air leakages in the pneumatic pipeline connected to
power contactor. If necessary replace the pneumatic pipe.
3. Manually operate the power contactor by pressing the armature
plate.
4. Check for air leakages from the magnet valve and power contactor
cylinder. There should not be any leakages.
5. The contactor should pick up with out any sluggish operation. If
found sluggish, replace power contactor.
6. Check power contactor main tips for any slackness. Ensure there is
no loose contact.
7. Check for magnet valve coil connection. The coil connections should
be tight and no loose crimped wires.
8. Ensure connector tightness at MEP-660. (Cable ID: AY).
85
PARAMETER
DESCRIPTION
FAULT CODE
1082
FAULT MESSAGE
Loose Contact in P2 circuit. Run Auto/Manual Test
Power Limited: Power Circuit Problem
RESTRICTIONS
TM1 is cut out in 6P mode only. Dynamic brake prohibited.
ALARM BELL
30 seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
--
RECOVERY
PROBABLE
1. Fluttering of power contactor due to improper air supply.
CAUSES
2. Power contactor itself defective.
3. Loose connections in the wiring.
FAULT
1. Ensure control air pressure is 5kg. /Sq.Cm. Adjust if necessary.
ISOLATION
2. Check for air leakages in the pneumatic pipeline connected to
power contactor. If necessary replace the pneumatic pipe.
3. Manually operate the power contactor by pressing the armature
plate.
4. Check for air leakages from the magnet valve and power contactor
cylinder. There should not be any leakages.
5. The contactor should pick up with out any sluggish operation. If
found sluggish, replace power contactor.
6. Check power contactor main tips for any slackness. Ensure there is
no loose contact.
7. Check for magnet valve coil connection. The coil connections should
be tight and no loose crimped wires.
8. Ensure connector tightness at MEP-660. (Cable ID: AY).
86
PARAMETER
DESCRIPTION
FAULT CODE
1083
FAULT MESSAGE
Loose Contact in P22 circuit. Run Auto/Manual Test
Power Limited: Power Circuit Problem
RESTRICTIONS
TM3 is cut out in 6P mode only. Dynamic brake prohibited.
ALARM BELL
30 seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
--
RECOVERY
PROBABLE
1. Fluttering of power contactor due to improper air supply.
CAUSES
2. Power contactor itself defective.
3. Loose connections in the wiring.
FAULT
1. Ensure control air pressure is 5kg. /Sq.Cm. Adjust if necessary.
ISOLATION
2. Check for air leakages in the pneumatic pipeline connected to
power contactor. If necessary replace the pneumatic pipe.
3. Manually operate the power contactor by pressing the armature
plate.
4. Check for air leakages from the magnet valve and power contactor
cylinder. There should not be any leakages.
5. The contactor should pick up with out any sluggish operation. If
found sluggish, replace power contactor.
6. Check power contactor main tips for any slackness. Ensure there is
no loose contact.
7. Check for magnet valve coil connection. The coil connections should
be tight and no loose crimped wires.
8. Ensure connector tightness at MEP-660. (Cable ID: AY).
87
PARAMETER
DESCRIPTION
FAULT CODE
1084
FAULT MESSAGE
Loose Contact in P32 circuit. Run Auto/Manual Test
Power Limited: Power Circuit Problem
RESTRICTIONS
TM2 is cut out in 6P mode only. Dynamic brake prohibited.
ALARM BELL
30 seconds
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
--
RECOVERY
PROBABLE
1. Fluttering of power contactor due to improper air supply.
CAUSES
2. Power contactor itself defective.
3. Loose connections in the wiring.
FAULT
1. Ensure control air pressure is 5kg. /Sq.Cm. Adjust if necessary.
ISOLATION
2. Check for air leakages in the pneumatic pipeline connected to
power contactor. If necessary replace the pneumatic pipe.
3. Manually operate the power contactor by pressing the armature
plate.
4. Check for air leakages from the magnet valve and power contactor
cylinder. There should not be any leakages.
5. The contactor should pick up with out any sluggish operation. If
found sluggish, replace power contactor.
6. Check power contactor main tips for any slackness. Ensure there is
no loose contact.
7. Check for magnet valve coil connection. The coil connections should
be tight and no loose crimped wires.
8. Ensure connector tightness at MEP-660. (Cable ID: AY).
88
PARAMETER
DESCRIPTION
FAULT CODE
1085
FAULT MESSAGE
P1 stuck closed. Run Auto/manual test.
RESTRICTIONS
Motoring in series prohibited
ALARM BELL
30 seconds
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when the P1 Auxiliary contact detected as open.
RECOVERY
PROBABLE
1.
Low control air pressure can cause delayed operation of power
CAUSES
contactor and cause this fault.
2.
P1 power contactor main contact tips welded.
3.
P1 power contactor auxiliary contact tips welded.
4.
Defective wiring.
5.
Defective Digital output card 1 MLSD16 in slot No. 14.
6.
Defective Digital input card 2 MDIP16 in slot No. 10.
FAULT
1.
Most probably this fault is logged due to delayed operation of the
ISOLATION
power contactor. Fault may not exist while testing. If so
A. Ensure proper over travel of the auxiliary contacts.
B. Ensure control air pressure is 5 Kg./Sq.Cm.
2.
Check the status of Green LED 3 on digital input card in slot 10. If
both Green and yellow LEDs 3 are glowing.
A. Check status of P1 power contactor. If found in energized
position, check the status of magnet valve.
B. If magnet valve is not energized, then the power contactor tips
are welded. Separate them.
C. If magnet valve is energized, then the digital output card 1 in
slot 14 is defective. Replace the card and check
3.
Check for welding of P1 power contactor auxiliary contact tips. If
welded change the auxiliary contacts.
4.
If auxiliary contacts are not welded,
A. Check the status of Green LED 3 on digital input card 2 in slot
10.
B. If green LED is glowing with power contactor de-energised, then
defective wiring. P1FB wire is getting wrong supply. Check
continuity of wiring.
89
PARAMETER
DESCRIPTION
FAULT CODE
1086
FAULT MESSAGE
P21 stuck closed. Run Auto/manual test.
RESTRICTIONS
Motoring in series prohibited
ALARM BELL
30 seconds
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when P21 auxiliary contact is detected as open.
RECOVERY
PROBABLE
1.
Low control air pressure can cause delayed operation of power
CAUSES
contactor and cause this fault.
2.
P21 power contactor main contact tips welded.
3.
P21 power contactor auxiliary contact tips welded.
4.
Defective wiring.
5.
Defective Digital output card 1 MLSD16 in slot No. 14.
6.
Defective Digital input card 2 MDIP16 in slot No. 10.
FAULT
1.
Most probably this fault is logged due to delayed operation of the
ISOLATION
power contactor. Fault may not exist while testing. If so
A. Ensure proper over travel of the auxiliary contacts.
B. Ensure control air pressure is 5 Kg./Sq.Cm.
2.
Check the status of Green LED 4 on digital input card in slot 10. If
both Green and yellow LEDs 4 are glowing.
A. Check status of P21 power contactor. If found in energized
position, check the status of magnet valve.
B. If magnet valve is not energized, then the power contactor tips
are welded. Separate them.
C. If magnet valve is energized, then the digital output card 1 in
slot 14 is defective. Replace the card and check
3.
Check for welding of P21 power contactor auxiliary contact tips. If
welded change the auxiliary contacts.
4.
If auxiliary contacts are not welded,
A. Check the status of Green LED 4 on digital input card 2 in slot
10.
B. If green LED is glowing with power contactor de-energised, then
defective wiring. P21FB wire is getting wrong supply. Check
continuity of wiring.
90
PARAMETER
DESCRIPTION
FAULT CODE
1087
FAULT MESSAGE
P31 stuck closed. Run Auto/manual test.
RESTRICTIONS
Motoring in series prohibited
ALARM BELL
30 seconds
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when P31 auxiliary contact is detected as open.
RECOVERY
PROBABLE
1.
Low control air pressure can cause delayed operation of power
CAUSES
contactor and cause this fault.
2.
P31 power contactor main contact tips welded.
3.
P31 power contactor auxiliary contact tips welded.
4.
Defective wiring.
5.
Defective Digital output card 1 MLSD16in slot No. 14.
6.
Defective Digital input card 2 MDIP16 in slot No. 10.
FAULT
1.
Most probably this fault is logged due to delayed operation of the
ISOLATION
power contactor. Fault may not exist while testing. If so
A. Ensure proper over travel of the auxiliary contacts.
B. Ensure control air pressure is 5 Kg./Sq.Cm.
2.
Check the status of Green LED 5 on digital input card in slot 10. If
both Green and yellow LEDs 5 are glowing.
A. Check status of P31 power contactor. If found in energized
position, check the status of magnet valve.
B. If magnet valve is not energized, then the power contactor tips
are welded. Separate them.
C. If magnet valve is energized, then the digital output card 1 in
slot 14 is defective. Replace the card and check
3.
Check for welding of P31 power contactor auxiliary contact tips. If
welded change the auxiliary contacts.
4.
If auxiliary contacts are not welded,
A. Check the status of Green LED 5 on digital input card 2 in slot
10.
B. If green LED is glowing with power contactor de-energised, then
defective wiring. P31FB wire is getting wrong supply. Check
continuity of wiring.
91
PARAMETER
DESCRIPTION
FAULT CODE
1088
FAULT MESSAGE
P2 stuck closed. Run Auto/manual test.
RESTRICTIONS
Motoring in series prohibited
ALARM BELL
30 seconds
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when P2 auxiliary contact is detected as open.
RECOVERY
PROBABLE
1.
Low control air pressure can cause delayed operation of power
CAUSES
contactor and cause this fault.
2.
P2 power contactor main contact tips welded.
3.
P2 power contactor auxiliary contact tips welded.
4.
Defective wiring.
5.
Defective Digital output card 1 MLSD16 in slot No. 14.
6.
Defective Digital input card 2 MDIP16 in slot No. 10.
FAULT
1.
Most probably this fault is logged due to delayed operation of the
ISOLATION
power contactor. Fault may not exist while testing. If so
A. Ensure proper over travel of the auxiliary contacts.
B. Ensure control air pressure is 5 Kg./Sq.Cm.
2.
Check the status of Green LED 6 on digital input card in slot 10. If
both Green and yellow LEDs 6 are glowing.
A. Check status of P2 power contactor. If found in energized
position, check the status of magnet valve.
B. If magnet valve is not energized, then the power contactor tips
are welded. Separate them.
C. If magnet valve is energized, then the digital output card 1 in
slot 14 is defective. Replace the card and check
3.
Check for welding of P2 power contactor auxiliary contact tips. If
welded change the auxiliary contacts.
4.
If auxiliary contacts are not welded,
A. Check the status of Green LED 6 on digital input card 2 in slot
10.
B. If green LED is glowing with power contactor de-energised, then
defective wiring. P2FB wire is getting wrong supply. Check
continuity of wiring.
92
PARAMETER
DESCRIPTION
FAULT CODE
1089
FAULT MESSAGE
P22 stuck closed. Run Auto/manual test.
RESTRICTIONS
Motoring in series prohibited
ALARM BELL
30 seconds
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when P22 auxiliary contact is detected as open.
RECOVERY
PROBABLE
1.
Low control air pressure can cause delayed operation of power
CAUSES
contactor and cause this fault.
2.
P22 power contactor main contact tips welded.
3.
P22 power contactor auxiliary contact tips welded.
4.
Defective wiring.
5.
Defective Digital output card 1 MLSD16 in slot No. 14.
6.
Defective Digital input card 2 DIP16 in slot No. 10.
FAULT
1.
Most probably this fault is logged due to delayed operation of the
ISOLATION
power contactor. Fault may not exist while testing. If so
A. Ensure proper over travel of the auxiliary contacts.
B. Ensure control air pressure is 5 Kg./Sq.Cm.
2.
Check the status of Green LED 7 on digital input card in slot 10. If
both Green and yellow LEDs 7 are glowing.
A. Check status of P22 power contactor. If found in energized
position, check the status of magnet valve.
B. If magnet valve is not energized, then the power contactor tips
are welded. Separate them.
C. If magnet valve is energized, then the digital output card 1 in
slot 14 is defective. Replace the card and check
3.
Check for welding of P22 power contactor auxiliary contact tips. If
welded change the auxiliary contacts.
4.
If auxiliary contacts are not welded,
A. Check the status of Green LED 7 on digital input card 2 in slot
10.
B. If green LED is glowing with power contactor de-energised, then
defective wiring. P22FB wire is getting wrong supply. Check
continuity of wiring.
93
PARAMETER
DESCRIPTION
FAULT CODE
1090
FAULT MESSAGE
P32 stuck closed. Run Auto/manual test.
RESTRICTIONS
Motoring in series prohibited
ALARM BELL
30 seconds
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when P32 auxiliary contact is detected as open.
RECOVERY
PROBABLE
1.
Low control air pressure can cause delayed operation of power
CAUSES
contactor and cause this fault.
2.
P32 power contactor main contact tips welded.
3.
P32 power contactor auxiliary contact tips welded.
4.
Defective wiring.
5.
Defective Digital output card 1 in slot No. 14.
6.
Defective Digital input card 2 in slot No. 10.
FAULT
1.
Most probably this fault is logged due to delayed operation of the
ISOLATION
power contactor. Fault may not exist while testing. If so
A. Ensure proper over travel of the auxiliary contacts.
B. Ensure control air pressure is 5 Kg./Sq.Cm.
2.
Check the status of Green LED 8 on digital input card in slot 10. If
both Green and yellow LEDs 8 are glowing.
A. Check status of P32 power contactor. If found in energized
position, check the status of magnet valve.
B. If magnet valve is not energized, then the power contactor tips
are welded. Separate them.
C. If magnet valve is energized, then the digital output card 1 in
slot 14 is defective. Replace the card and check
3.
Check for welding of P32 power contactor auxiliary contact tips. If
welded change the auxiliary contacts.
4.
If auxiliary contacts are not welded,
A. Check the status of Green LED 8 on digital input card 2 in slot
10.
B. If green LED is glowing with power contactor de-energised, then
defective wiring. P32FB wire is getting wrong supply. Check
continuity of wiring.
94
PARAMETER
DESCRIPTION
FAULT CODE
1091
FAULT MESSAGE
S1 stuck closed. Run Auto/manual test.
RESTRICTIONS
Motoring in parallel prohibited
ALARM BELL
30 seconds
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when S1 auxiliary contact is detected as open.
RECOVERY
PROBABLE
1.
Low control air pressure can cause delayed operation of power
CAUSES
contactor and cause this fault.
2.
S1 power contactor main contact tips welded.
3.
S1 power contactor auxiliary contact tips welded.
4.
Defective wiring.
5.
Defective Digital output card 1 MLSD16 in slot No. 14.
6.
Defective Digital input card 2 MDIP16 in slot No. 10.
FAULT
1.
Most probably this fault is logged due to delayed operation of the
ISOLATION
power contactor. Fault may not exist while testing. If so
A. Ensure proper over travel of the auxiliary contacts.
B. Ensure control air pressure is 5 Kg./Sq.Cm.
2.
Check the status of Green LED 9 on digital input card in slot 10. If
both Green and yellow LEDs 9 are glowing.
A. Check status of S1 power contactor. If found in energized
position, check the status of magnet valve.
B. If magnet valve is not energized, then the power contactor tips
are welded. Separate them.
C. If magnet valve is energized, then the digital output card 1 in
slot 14 is defective. Replace the card and check
3.
Check for welding of S1 power contactor auxiliary contact tips. If
welded change the auxiliary contacts.
4.
If auxiliary contacts are not welded,
A. Check the status of Green LED 6 on digital input card 2 in slot
10.
B. If green LED is glowing with power contactor de-energised, then
defective wiring. S1FB wire is getting wrong supply. Check
continuity of wiring.
95
PARAMETER
DESCRIPTION
FAULT CODE
1092
FAULT MESSAGE
S21 stuck closed. Run Auto/manual test.
RESTRICTIONS
Motoring in parallel prohibited
ALARM BELL
30 seconds
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when S21 auxiliary contact is detected as open.
RECOVERY
PROBABLE
1.
Low control air pressure can cause delayed operation of power
CAUSES
contactor and cause this fault.
2.
S21 power contactor main contact tips welded.
3.
S21 power contactor auxiliary contact tips welded.
4.
Defective wiring.
5.
Defective Digital output card 1 MLSD16 in slot No. 14.
6.
Defective Digital input card 2 MDIP16 in slot No. 10.
FAULT
1.
Most probably this fault is logged due to delayed operation of the
ISOLATION
power contactor. Fault may not exist while testing. If so
A. Ensure proper over travel of the auxiliary contacts.
B. Ensure control air pressure is 5 Kg./Sq.Cm.
2.
Check the status of Green LED 10 on digital input card in slot 10. If
both Green and yellow LEDs 10 are glowing.
A. Check status of S21 power contactor. If found in energized
position, check the status of magnet valve.
B. If magnet valve is not energized, then the power contactor tips
are welded. Separate them.
C. If magnet valve is energized, then the digital output card 1 in
slot 14 is defective. Replace the card and check
3.
Check for welding of S21 power contactor auxiliary contact tips. If
welded change the auxiliary contacts.
4.
If auxiliary contacts are not welded,
A. Check the status of Green LED 10 on digital input card 2 in slot
10.
B. If green LED is glowing with power contactor de-energised, then
defective wiring. S21FB wire is getting wrong supply. Check
continuity of wiring.
96
PARAMETER
DESCRIPTION
FAULT CODE
1093
FAULT MESSAGE
S31 stuck closed. Run Auto/manual test.
RESTRICTIONS
Motoring in parallel prohibited
ALARM BELL
30 seconds
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
Automatic when S31 auxiliary contact is detected as open.
RECOVERY
PROBABLE
1.
Low control air pressure can cause delayed operation of power
CAUSES
contactor and cause this fault.
2.
S31 power contactor main contact tips welded.
3.
S31 power contactor auxiliary contact tips welded.
4.
Defective wiring.
5.
Defective Digital output card 1 MLSD16 in slot No. 14.
6.
Defective Digital input card 2 MDIP16 in slot No. 10.
FAULT
1.
Most probably this fault is logged due to delayed operation of the
ISOLATION
power contactor. Fault may not exist while testing. If so
A. Ensure proper over travel of the auxiliary contacts.
B. Ensure control air pressure is 5 Kg./Sq.Cm.
2.
Check the status of Green LED 11 on digital input card in slot 10. If
both Green and yellow LEDs 11 are glowing.
A. Check status of S31 power contactor. If found in energized
position, check the status of magnet valve.
B. If magnet valve is not energized, then the power contactor tips
are welded. Separate them.
C. If magnet valve is energized, then the digital output card 1 in
slot 14 is defective. Replace the card and check
3.
Check for welding of S31 power contactor auxiliary contact tips. If
welded change the auxiliary contacts.
4.
If auxiliary contacts are not welded,
A. Check the status of Green LED 11 on digital input card 2 in slot
10.
B. If green LED is glowing with power contactor de-energised, then
defective wiring. S31FB wire is getting wrong supply. Check
continuity of wiring.
97
////////////////////////////////////////// |
||
|
|
|